Sheraton Suites - Swimming Pool

255 Barclay Parade SW Calgary AB T2P 5C2 · Aquatic Facility

Inspection summary

Sheraton Suites - Swimming Pool has been inspected 7 times by Alberta Health Services (Environmental Public Health) since January 25, 2024. The most recent inspection, on January 8, 2026, recorded 1 infraction.

3 of 7 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 7 infractions recorded. The higher-risk findings here relate to: Chemicals and toxic substances and Pool and spa water quality.

Recent inspections have recorded more infractions than earlier ones, so it is worth reading the latest reports closely.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 5 times across 4 separate inspections, most recently on January 8, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 2 times across 2 separate inspections, most recently on January 2, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

7 inspections

  1. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured to be 1.70ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC of 320CFU/mL present
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured to be 1.70ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
  3. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured to be 1.70ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
  4. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was recorded to be: 8.14, 8.07, 7.71, 7.79 (tested multiple times during inspection). This pH is too high; pH is to be maintained between 6.8-7.6. Operator temporarily closed the pool while they began manually adding acid to the pool to lower the pH. As well Ecolab was called to come service the automatic controller.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorine was measured to be 1.54ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated controller was reading the pH was high (reading 7.81, set point: 7.35) but was not pumping acid or displaying an error message/alarm. Ecolab was called and arrived while the PHI was on-site to service the automatic controller. The pool is to be kept closed until the automatic controller can be fixed and the pH of the basin is within range (6.8-7.6).
  5. Demand Inspection

    0 infractions

  6. Monitoring Inspection

    0 infractions

  7. Monitoring Inspection

    0 infractions