Sheraton Suites - Swimming Pool
255 Barclay Parade SW Calgary AB T2P 5C2 · Aquatic Facility
8 inspections
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was measured to be 1.70ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 320CFU/mL present
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was measured to be 1.70ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was measured to be 1.70ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH was recorded to be: 8.14, 8.07, 7.71, 7.79 (tested multiple times during inspection). This pH is too high; pH is to be maintained between 6.8-7.6. Operator temporarily closed the pool while they began manually adding acid to the pool to lower the pH. As well Ecolab was called to come service the automatic controller.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorine was measured to be 1.54ppm. Combined chlorines are to be kept as low as possible. Please add fresh water to dilute the combined chlorine in the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated controller was reading the pH was high (reading 7.81, set point: 7.35) but was not pumping acid or displaying an error message/alarm. Ecolab was called and arrived while the PHI was on-site to service the automatic controller. The pool is to be kept closed until the automatic controller can be fixed and the pH of the basin is within range (6.8-7.6).
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was measured at 15 ppm. **Maintain Alkalinity level between 60 - 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?