Siding 16 Lodge - Whirlpool

3806 56 Street Wetaskiwin AB T9A 2B2 · Aquatic Facility

24 inspections

  1. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • PHI water test results were,Total Alkalinity was 43 - UNSATISFACTORYCombined Chlorine was 0.34 ppmTotal Chlorine was 4.14 ppmCorrective action - Total alkalinity needs to be in the range of 60 - 180 ppm for providing pH stability. Please adjust as necessary.
  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on June 16, 2026 for the Whirlpool, had these results: - Total Coliforms - Absent - Pseudomonas - ISOLATED - HPC 90 CFU/mLThis is an Unsatisfactory result.This was discussed with the pool operator.The Whirlpool will need to be CLOSED immediately, complete the Pseudomonas protocols, re-balance the water chemistry, the Whirlpool can then be re-opened to the public and then resample on Tues June 23, 2026.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • PHI water test results were,Total Alkalinity was 43 - UNSATISFACTORYCombined Chlorine was 0.34 ppmTotal Chlorine was 4.14 ppmCorrective action - Total alkalinity needs to be in the range of 60 - 180 ppm for providing pH stability. Please adjust as necessary.
  3. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • PHI water test results were,Total Alkalinity was 43 - UNSATISFACTORYCombined Chlorine was 0.34 ppmTotal Chlorine was 4.14 ppmCorrective action - Total alkalinity needs to be in the range of 60 - 180 ppm for providing pH stability. Please adjust as necessary.
  4. Risk Management Inspection

    0 infractions

  5. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on March 17, 2026 had the following results: - Total Coliforms - Absent - Pseudomonas - ISOLATED - HPC 10 CFU/mLThis is an unsatisfactory result.This was discussed with the operator, to close the Whirlpool immediately.Follow the Pseudomonas Response Protocols.Once those are completed the whirlpool water chemistry can be re-balanced and then the whirlpool can re-open to the public.Resample on next Tuesday.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on Dec 16, 2025, from the whirlpool had the following results: - Total Coliforms - ABSENT - Pseudomonas - ISOLATED - HPC - >57000 CFU/mLThis is an unsatisfactory result.Corrective ActionsImmediately close the whirlpool to public access.Implement the Pseudomonas Response Protocol as per established guidelines.After completing the Pseudomonas Response Protocol and re-balancing the whirlpool water chemistry to proper levels, the whirlpool may be re-opened to the public (since this is the first unsatisfactory result).Collect a resample on the next regular sampling day.Spoke with Jeff
  8. Monitoring Inspection

    0 infractions

  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on Dec 16, 2025, from the whirlpool had the following results: - Total Coliforms - ABSENT - Pseudomonas - ISOLATED - HPC - 10 CFU/mLThis is an unsatisfactory result.Corrective ActionsImmediately close the whirlpool to public access.Implement the Pseudomonas Response Protocol as per established guidelines.After completing the Pseudomonas Response Protocol and re-balancing the whirlpool water chemistry to proper levels, the whirlpool may be re-opened to the public (since this is the first unsatisfactory result).Collect a resample on the next regular sampling day.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • In the mechanical room, PHI observed a water leak on the floor. Operator reports that they have ordered a new gasket for the water pump. Gasket will be installed once it arrives.
  10. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • In the mechanical room, PHI observed a water leak on the floor. Operator reports that they have ordered a new gasket for the water pump. Gasket will be installed once it arrives.
  11. Monitoring Inspection

    0 infractions

  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on Dec 30, 2024 from the whirlpool had the following results: - Total Coliforms - ABSENT - Pseudomonas - ISOLATED - HPC - 60 CFU/mLThis is an unsatisfactory result.Corrective Actions:a) immediately close the whirlpool from public access.b) follow the Pseudomonas Response protocol.c) once the Pseudomonas response protocol has been completed and the whirlpool water chemistry is re-balanced to proper levels - the whirlpool can be re-opened to the public ( as this is just the first unsatisfactory result ).d) resample on the regular sampling day next week.
  14. Monitoring Inspection

    0 infractions

  15. Monitoring Inspection

    0 infractions

  16. Risk Management Inspection

    0 infractions

  17. Monitoring Inspection

    0 infractions

  18. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample collected on May 14, 2024 had the following results: - Total Coliforms - PRESENT - Pseudomonas - Absent - HPC 30 CFU/mLThis is an unsatisfactory water report.In discussion with the operator, he reported that he has already taken corrective actions, that include: - draining the whirlpool water to waste - scrubbing the whirlpool basin and fittings. - refilled the whirlpool basin with balanced water from the main pool basin.
  19. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Unsatisfactory water report.The water sample collected on May 14, 2024, from the hot tub, shows the presence of total coliforms.Pseudomonas - AbsentHPC 30 CFU/mL
  20. Risk Management Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PHI water test results were:Free Chlorine 1.03pH 7.42
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • PHI water test results were:Total Chlorine 3.55 ppmCombined chlorine 2.52 ppmalkalinity 52 ppmObserved readingsORP 638 mVFlow meter 67 gpmCorrective actionCombined chlorine should be kept at less than 1.0 ppm.Alkalinity is to be kept at 60 to 180 ppm.Adjust these parameters as needed.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The clock for the whirlpool was not working/functioning.Corrective action - repair or replace the clock.
  21. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PHI water test results were:Free Chlorine 1.03pH 7.42
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • PHI water test results were:Total Chlorine 3.55 ppmCombined chlorine 2.52 ppmalkalinity 52 ppmObserved readingsORP 638 mVFlow meter 67 gpmCorrective actionCombined chlorine should be kept at less than 1.0 ppm.Alkalinity is to be kept at 60 to 180 ppm.Adjust these parameters as needed.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The clock for the whirlpool was not working/functioning.Corrective action - repair or replace the clock.
  22. Risk Management Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The automatic reader indicates that pH is at 7.0 when we have tested it at pH is at 7.51. Operator records are also closer to PHI readings. Operator should look into calibrating this issue.
  23. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Nov 21, 2023 had the following result: - Total Coliforms - ABSENT - Pseudomonas - NOT ISOLATED - HPC 1230 CFU/mLThis is an unsatisfactory result due to the HPC being greater than 100 CFU/mL.PHI spoke with the pool operator Kelly. - the whirlpool will be closed - it will be shock chlorinated overnight - the water chemistry will be rebalanced the next morning - the public can then have access to the whirlpool - resample can be submitted next Tuesday, on the regular sampling day.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The automatic reader indicates that pH is at 7.0 when we have tested it at pH is at 7.51. Operator records are also closer to PHI readings. Operator should look into calibrating this issue.
  24. Monitoring Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The automatic reader indicates that pH is at 7.0 when we have tested it at pH is at 7.51. Operator records are also closer to PHI readings. Operator should look into calibrating this issue.