Skyridge at Harvie Heights - Whirlpool

750 Harvie Heights Road Harvie Heights AB T1W 2W2 · Aquatic Facility

4 inspections

  1. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate is 14.3 GPM/sqft. - Please adjust flow rate so it does not exceed the max flow rate for the filter.2. The pH measured (7.44) is higher than the reading, 7.2 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Wednesday July 2nd, 2025, had Total Coliforms present. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate is 14.3 GPM/sqft. - Please adjust flow rate so it does not exceed the max flow rate for the filter.2. The pH measured (7.44) is higher than the reading, 7.2 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
  3. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Flow rate exceeded max flow rate of 61GPM, flow meter was reading 70 GPM. Filtration rate is 14.3 GPM/sqft. - Please adjust flow rate so it does not exceed the max flow rate for the filter.2. The pH measured (7.44) is higher than the reading, 7.2 (set 7.3).-Ensure the automated and monitoring equipment are well calibrated
  4. Initial Inspection

    0 infractions