Solara Resort And Spa - Swimming Pool
187 Kananaskis Way Canmore AB T1W 0A3 · Aquatic Facility
11 inspections
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chorine was measured as 3.32ppm and there was a strong chloramine smell in the pool area. Combined chlorine level is to be kept lower.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The float for the flow meter appeared to be stuck so an accurate flow rate could not be determined. Repair or replace the flow meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water sample was submitted the week of May 25/26. A water sample is required to be submitted each week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on June 5/26 was not tested as it was dropped off after the lab had closed for the weekend. New sample to be submitted as soon as possible this week.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chorine was measured as 3.32ppm and there was a strong chloramine smell in the pool area. Combined chlorine level is to be kept lower.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The float for the flow meter appeared to be stuck so an accurate flow rate could not be determined. Repair or replace the flow meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chorine was measured as 3.32ppm and there was a strong chloramine smell in the pool area. Combined chlorine level is to be kept lower.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The float for the flow meter appeared to be stuck so an accurate flow rate could not be determined. Repair or replace the flow meter.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- One of the skimmer weirs is missing. To be replaced.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Risk Management Inspection
4 infractions
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Drain covers are now likely "expired" based on the type of cover and when they were installed. Missing page from anti-entrapment plan that states the model of cover and when the current ones were installed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- One of the skimmer weirs is missing. To be replaced.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- December 27, 2024 water sample was not tested. Please resample.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Drain covers are now likely "expired" based on the type of cover and when they were installed. Missing page from anti-entrapment plan that states the model of cover and when the current ones were installed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- One of the skimmer weirs is missing. To be replaced.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
4 infractions
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- One of the skimmer weirs is missing. To be replaced.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Drain covers are now likely "expired" based on the type of cover and when they were installed. Missing page from anti-entrapment plan that states the model of cover and when the current ones were installed.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken August 22, 2024 was not tested as on requisition form it was written that it was taken on September 22, 2024.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Feb. 26/24 water sample had a plate count of 210cfu/ml. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Jan 15/24 water sample had a plate count of over 57,000 cfu/ml. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- November 20/23 water sample had a plate count of 180cfu/ml. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?