  1. Risk Management Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chorine was measured as 3.32ppm and there was a strong chloramine smell in the pool area. Combined chlorine level is to be kept lower.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The float for the flow meter appeared to be stuck so an accurate flow rate could not be determined. Repair or replace the flow meter.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
  2. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • No water sample was submitted the week of May 25/26. A water sample is required to be submitted each week.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on June 5/26 was not tested as it was dropped off after the lab had closed for the weekend. New sample to be submitted as soon as possible this week.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chorine was measured as 3.32ppm and there was a strong chloramine smell in the pool area. Combined chlorine level is to be kept lower.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The float for the flow meter appeared to be stuck so an accurate flow rate could not be determined. Repair or replace the flow meter.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
  3. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chorine was measured as 3.32ppm and there was a strong chloramine smell in the pool area. Combined chlorine level is to be kept lower.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The float for the flow meter appeared to be stuck so an accurate flow rate could not be determined. Repair or replace the flow meter.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
  4. Risk Management Inspection

    3 infractions

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • One of the skimmer weirs is missing. To be replaced.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed. Was advised new anti-entrapment plans will be completed.
  5. Risk Management Inspection

    4 infractions

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Drain covers are now likely "expired" based on the type of cover and when they were installed. Missing page from anti-entrapment plan that states the model of cover and when the current ones were installed.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • One of the skimmer weirs is missing. To be replaced.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed.
  6. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • December 27, 2024 water sample was not tested. Please resample.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Drain covers are now likely "expired" based on the type of cover and when they were installed. Missing page from anti-entrapment plan that states the model of cover and when the current ones were installed.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • One of the skimmer weirs is missing. To be replaced.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed.
  7. Monitoring Inspection

    4 infractions

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • One of the skimmer weirs is missing. To be replaced.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Drain covers are now likely "expired" based on the type of cover and when they were installed. Missing page from anti-entrapment plan that states the model of cover and when the current ones were installed.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Combined chlorine level is not being checked. Please ensure combined chlorine level is checked at least once a day.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed. This page would include information on the main drain covers and when they were installed.
  8. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken August 22, 2024 was not tested as on requisition form it was written that it was taken on September 22, 2024.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
  9. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Feb. 26/24 water sample had a plate count of 210cfu/ml. Treat water to remove contamination.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
  10. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Jan 15/24 water sample had a plate count of over 57,000 cfu/ml. Treat water to remove contamination.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
  11. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • November 20/23 water sample had a plate count of 180cfu/ml. Treat water to remove contamination.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was reading 88gpm. The maximum flow rate for the filter is only 74gpm. Flow rate needs to be kept between 30-74gpm.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.