- Risk Management Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine was measured as 3.12ppm and there was a strong chloramine smell in the pool area. Combined chlorine level to be kept lower.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The clock in the pool area is not working. Repair or replace the clock.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Much of the grout around the tiles is gone. Re-grouting needed.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. Wad advised new anti-entrapment plan is going to be completed. Please provide a copy once completed.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
6 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on June 5/26 was not tested as it was received at the lab after it had closed for the weekend. New water sample is to be submitted as soon as possible this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water sample was submitted the week of May 25/26. A water sample is to be submitted weekly.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine was measured as 3.12ppm and there was a strong chloramine smell in the pool area. Combined chlorine level to be kept lower.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The clock in the pool area is not working. Repair or replace the clock.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Much of the grout around the tiles is gone. Re-grouting needed.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. Wad advised new anti-entrapment plan is going to be completed. Please provide a copy once completed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine was measured as 3.12ppm and there was a strong chloramine smell in the pool area. Combined chlorine level to be kept lower.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The clock in the pool area is not working. Repair or replace the clock.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Much of the grout around the tiles is gone. Re-grouting needed.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. Wad advised new anti-entrapment plan is going to be completed. Please provide a copy once completed.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine levels are not being tested. To be tested and recorded at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed. Wad advised new anti-entrapment plan is going to be completed. Please provide a copy once completed.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Risk Management Inspection
3 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters may not be accurate based on type of flow meter and length of pipe on which they were installed. Current readings indicate the flow through each of these filters is exceeding the maximum flow permitted (88gpm). One flow meter was reading 96gpm and the other was reading 113gpm. Flow meters are to be accurate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine levels are not being tested. To be tested and recorded at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- June 20/25 water sample had Pseudomonas isolated. Whirlpool to be closed until a Pseudomonas disinfection is done. Resample is to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters may not be accurate based on type of flow meter and length of pipe on which they were installed. Current readings indicate the flow through each of these filters is exceeding the maximum flow permitted (88gpm). One flow meter was reading 96gpm and the other was reading 113gpm. Flow meters are to be accurate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine levels are not being tested. To be tested and recorded at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- May 8/25 water sample had Pseudomonas isolated. Whirlpool to be closed until a Pseudomonas disinfection is done. Resample is to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters may not be accurate based on type of flow meter and length of pipe on which they were installed. Current readings indicate the flow through each of these filters is exceeding the maximum flow permitted (88gpm). One flow meter was reading 96gpm and the other was reading 113gpm. Flow meters are to be accurate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine levels are not being tested. To be tested and recorded at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- December 27/24 water sample was not tested. Resample to be submitted.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters may not be accurate based on type of flow meter and length of pipe on which they were installed. Current readings indicate the flow through each of these filters is exceeding the maximum flow permitted (88gpm). One flow meter was reading 96gpm and the other was reading 113gpm. Flow meters are to be accurate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine levels are not being tested. To be tested and recorded at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters may not be accurate based on type of flow meter and length of pipe on which they were installed. Current readings indicate the flow through each of these filters is exceeding the maximum flow permitted (88gpm). One flow meter was reading 96gpm and the other was reading 113gpm. Flow meters are to be accurate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Combined chlorine levels are not being tested. To be tested and recorded at least once a day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- July 18/24 water sample had Pseudomonas isolated. Close whirlpool until water is treated to remove contamination. Submit a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- March 25/24 water sample had Pseudomonas isolated. Treat water and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- March 11, 2024 water sample had Pseudomonas isolated. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Feb. 12, 2024 water sample had Pseudomonas isolated. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Dec. 11, 2023 water sample has Pseudomonas isolated. Treat the water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate according to flow meter at last inspection was 200gpm. Minimum required flow rate for the whirlpool is 257gpm. Flow rate to maintained between 257-265gpm.Flow rate could not be determined at this time as the float was stuck in the flow meter so reading would not be accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The two flow meters for the sand filters were not working. Flow meters are to be repaired or replaced so the flow through each filter can be determined.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Second page is missing from the anti-entrapment plan. Second page to be completed.No general sanitation of safety & supervision plan could be located. Written general sanitation and safety & supervision plan required.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?