Inspection summary

Somerset Waterpark - Spray Park has been inspected 7 times by Alberta Health Services (Environmental Public Health) since July 9, 2024. The most recent inspection, on August 19, 2026, found no infractions.

3 of 7 inspections on record found no infractions at all. In the past 12 months there were 3 inspections with 1 infraction recorded. The higher-risk findings here relate to: Pool and spa water quality.

Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 8 times across 4 separate inspections, most recently on August 13, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

7 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample collected on August 11, 2026 had a heterotrophic plate count of 180 CFU/mL.
  3. Monitoring Inspection

    0 infractions

  4. Demand Inspection

    0 infractions

  5. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Automated system pH reading was 7.7 and manual reading 7.29- Ensure that automated and manual readings are consistent.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • One of spray features on the west side was too strong, over spraying onto grass. - Adjust the spray features. Water from showers was spraying down the walkway to the main spray park area. - Limit the water pressure and/or direct the shower nozzles in a way so water enters drains only and not surrounding areas. - Consider limiting one side of each shower that sprays water onto the spray park.
  6. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on July 23/24- had HPC 170 cfu/ml. - Let a message for Maddie to resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Automated system pH reading was 7.7 and manual reading 7.29- Ensure that automated and manual readings are consistent.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • One of spray features on the west side was too strong, over spraying onto grass. - Adjust the spray features. Water from showers was spraying down the walkway to the main spray park area. - Limit the water pressure and/or direct the shower nozzles in a way so water enters drains only and not surrounding areas. - Consider limiting one side of each shower that sprays water onto the spray park.
  7. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Automated system pH reading was 7.7 and manual reading 7.29- Ensure that automated and manual readings are consistent.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • One of spray features on the west side was too strong, over spraying onto grass. - Adjust the spray features. Water from showers was spraying down the walkway to the main spray park area. - Limit the water pressure and/or direct the shower nozzles in a way so water enters drains only and not surrounding areas. - Consider limiting one side of each shower that sprays water onto the spray park.