Stonegate Recreation Centre - Swimming Pool
9318 47 Avenue Grande Prairie AB T8W 2G6 · Aquatic Facility
3 inspections
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water result received. Collection date 9 July 2025.Total Coliforms - Present.Ensure to super chlorinate pool.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- At time of inspection:1. The anti-entrapment plan submitted indicates that the main drain covers have a 5-year expiry. Installation of the main drain covers (according to the anti-entrapment plan) were installed on August 24, 2018.The owner / operator of this facility is requested to conduct the following, namely:1. Replace all main drain covers. Ensure they are installed as per the manufacturer's requirements.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- At time of inspection:1. The anti-entrapment plan submitted indicates that the main drain covers have a 5-year expiry. Installation of the main drain covers (according to the anti-entrapment plan) were installed on August 24, 2018.The owner / operator of this facility is requested to conduct the following, namely:1. Replace all main drain covers. Ensure they are installed as per the manufacturer's requirements.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- CHEMICAL PARAMETER RESULTSpH @ 7.9 - TOO HIGHFAC @ 6.5 - TOO HIGHTAC @ 7.2CAC @ 0.7ALKALINITY @ 93ORP (Meter) @ 675 mVThe owner / operator of this facility is requested to conduct the following, namely:1. Decrease both free chlorine to less than 5.0 PPM and pH to between 6.8-7.6.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- At time of inspection:1. The anti-entrapment plan submitted indicates that the main drain covers have a 5-year expiry. Installation of the main drain covers (according to the anti-entrapment plan) were installed on August 24, 2018.The owner / operator of this facility is requested to conduct the following, namely:1. Replace all main drain covers. Ensure they are installed as per the manufacturer's requirements.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?