Tall Timber Leisure Park - Pool
606 Main Avenue E Sundre AB T0M 1X0 · Aquatic Facility
Inspection summary
Tall Timber Leisure Park - Pool has been inspected 15 times by Alberta Health Services (Environmental Public Health) since May 3, 2024. The most recent inspection, on September 18, 2026, found no infractions.
8 of 15 inspections on record found no infractions at all. In the past 12 months there were 2 inspections with 0 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.
The last 2 inspections in a row found no infractions. The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 8 times across 7 separate inspections, most recently on September 2, 2025. For example:
Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
15 inspections
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water result: HPC: 360 CFU/mlResample *Pool last day of opening is September 7, 2025.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Routine water sample result: TC PresentVerify free chlorine and pH levels are withing the required range.Please resample to confirm test result. Make sure to mark the bottle as "Resample".
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. Routine water sample result: TC PresentPlease resample to confirm test result. Make sure to mark the bottle as "Resample".
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Pool Volume 39097 GalCirculation Rate 105 GPMTurnover time = 6.2 hrMinimum flow rate required to meet 6 hour turnover is: 109 GPM
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Risk Management Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Pool Volume 148,000 L = 39097 GalCirculation Rate 300 L/Min = 79.25 GPMTurnover Rate = 8.2hr (must be 6 hours)(Pool constructed in 1980's)Filter: 2x Pentair Tagelus TA100Max Filtration Rate: 100 GPMMinimum flow rate required to meet 6 hour turnover is: 109 GPM (413 L/min)
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Monitoring Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. Pool filled after winter hiatus. Pool does not open until the coming weekend. BacT sample submitted 2 days prior to inspection. Results should be known on Friday prior to opening..
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Pool Volume 148,000 L = 39097 GalCirculation Rate 300 L/Min = 79.25 GPMTurnover Rate = 8.2hr (must be 6 hours)(Pool constructed in 1980's)Filter: 2x Pentair Tagelus TA100Max Filtration Rate: 100 GPMMinimum flow rate required to meet 6 hour turnover is: 109 GPM (413 L/min)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. Pool filled after winter hiatus. Pool does not open until the coming weekend. Inspector will visit and review results with the operator.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
0 infractions