The Livingston Hub - Splash Park

1248 Livingston Way NE Calgary AB T3P 0V6 · Aquatic Facility

7 inspections

  1. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • At the time of the inspection, the flow rate measured 280 GPM which resulted in a filtering rate of 19.8 GPM/sq.ft. This exceeded the expected operational parameters for the system.The flow was subsequently adjusted, and the flow meter then recorded a flow rate of 210 GPM resulting in a filtering rate of 14.8 GPM/sq.ft. This adjustment brought the system within the required filtering rate for effective circulation and filtration for a pool (splash park) built after November 2006.Continue monitoring the flow rate and filtering rate to ensure the system remains within the acceptable operating parameters.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 02/09/2025 was rejected because the sample was received more than 24 hours after collection.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity reading were 27 ppm, 24 ppm, and last 22 ppm.- Ensure that the Total alkalinity is between 60-180ppm
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 08/06/2025, was rejected due to no identification number on the bottle.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity reading were 27 ppm, 24 ppm, and last 22 ppm.- Ensure that the Total alkalinity is between 60-180ppm
  4. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity reading were 27 ppm, 24 ppm, and last 22 ppm.- Ensure that the Total alkalinity is between 60-180ppm
  5. Monitoring Inspection

    0 infractions

  6. Risk Management Inspection

    0 infractions

  7. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine measured 0.5 ppm.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The floor drain covers were not screwed in place. A child could lift the grate and reach under. Please screw in the covers.