The Meadows Community Recreation Centre - Competition Pool

2704 17 Street NW Edmonton AB T6T 0X1 · Aquatic Facility

8 inspections

  1. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Rusting is noted along the bubbler system for the diving platform. The facility has identified this as a concern and will be looking to address the deterioration of the system during the next pool shut down. They are continuing to monitor and ensure further deterioration does not occur.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result collected on 03/03/2026 [25EN-062E00709] was unsatisfactory: HPC 550 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Rusting is noted along the bubbler system for the diving platform. The facility has identified this as a concern and will be looking to address the deterioration of the system during the next pool shut down. They are continuing to monitor and ensure further deterioration does not occur.
  3. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Rusting is noted along the bubbler system for the diving platform. The facility has identified this as a concern and will be looking to address the deterioration of the system during the next pool shut down. They are continuing to monitor and ensure further deterioration does not occur.
  4. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment suction outlets were replaced during the shutdown. Anti-entrapment compliance plan must be updated. Ensure it is updated and a copy provided for review. For any assistance with completing the plan please contact the undersigned.
  5. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 11 March 2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment suction outlets were replaced during the shutdown. Anti-entrapment compliance plan must be updated. Ensure it is updated and a copy provided for review. For any assistance with completing the plan please contact the undersigned.
  6. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment suction outlets were replaced during the shutdown. Anti-entrapment compliance plan must be updated. Ensure it is updated and a copy provided for review. For any assistance with completing the plan please contact the undersigned.
  7. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Controller values for pH were not consistent with manual pH readings. Check controller calibration and adjust as required.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment suction outlets were replaced during the shutdown. Anti-entrapment compliance plan must be updated. Ensure it is updated and a copy provided for review. For any assistance with completing the plan please contact the undersigned.
  8. Monitoring Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Staff were unable to find the daily visual check records for the submerged suction outlets. Confirm the location and ensure documentation is kept and recorded daily.