Skip to content
Loading map…

The Palladio - Outdoor Whirlpool

1228 W Hastings St, Vancouver BC V6E 4S6 · Hot Tub

Inspection summary

The Palladio - Outdoor Whirlpool has been inspected 16 times by Vancouver Coastal Health since August 11, 2015. The most recent inspection, on September 3, 2025, found no infractions.

2 of 16 inspections on record found no infractions at all. No inspections are on record from the past 12 months. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 27 times across 12 separate inspections, most recently on July 17, 2025. For example: The pool pH level is properly maintained

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded once on January 22, 2019. For example: Chemicals are stored in a safe manner and location

  • Equipment and utensilsLower risk

    Pumps, filters, chemical feeders and safety equipment such as lifebuoys, reaching poles and first-aid kits must be present and working. Missing safety equipment can matter a great deal in an emergency.

    Recorded 7 times across 6 separate inspections, most recently on January 9, 2020. For example: Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications

About this data

These results come from Vancouver Coastal Health, which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

16 inspections

  1. Routine Follow-up

    0 infractions

  2. Routine

    4 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool alkalinity is properly maintained
      • Total Alkalinity is too low and is not at a level to maintain chemically balanced pool water.
    • Pool water velocity and recirculation rate is properly maintained
    • Daily pool records are adequately maintained and available on site
  3. Routine

    0 infractions

  4. Routine Follow-up

    4 infractions

    • The pool disinfectant is properly maintained
      • Chlorine Cyanurate is less than 2.0 ppm at temperature above 30°C
    • The pool pH level is properly maintained
    • The pool is kept in good repair by an appropriately trained person.
    • Daily pool records are adequately maintained and available on site
      • Results of water testing are inadequately recorded.
  5. Routine

    4 infractions

    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
    • Pool water velocity and recirculation rate is properly maintained
      • There is no observable flow of surface water over the skimmers
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
    • Daily pool records are adequately maintained and available on site
      • Results of water testing are inadequately recorded.
  6. Routine Follow-up

    1 infraction

    • Pool water velocity and recirculation rate is properly maintained
      • The pool water is not being recirculated at the design flow rate.
  7. Routine

    2 infractions

    • Pool water velocity and recirculation rate is properly maintained
      • The pool water is not being recirculated at the design flow rate.
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  8. Routine Follow-up

    1 infraction

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
  9. Routine

    4 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
    • Chemicals are stored in a safe manner and location
      • Chemical containers are not properly labeled
      • Chemicals are stored directly on the floor.
    • An operator of a pool has prepared, maintains, and follows a written pool safety plan to ensure the health and safety of pool patrons
      • Pool safety plan not readily available to employees.
  10. Routine

    2 infractions

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
    • Adequate pool supervision and/or safety equipment is provided
      • Pool is not equipped with a reaching assist and/or the reaching assist is made of conducting materials (N/A for pools < 10m²)
  11. Routine

    3 infractions

    • The pool alkalinity is properly maintained
    • The pool disinfectant is properly maintained
    • Daily pool records are adequately maintained and available on site
      • Results of daily water testing is inadequately recorded: Free Available Chlorine, Combined Available Chlorine and pH is tested and recorded at least twice daily; Alkalinity and Cyanuric Acid is tested and recorded at least weekly.
  12. Routine

    3 infractions

    • The pool alkalinity is properly maintained
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
    • Daily pool records are adequately maintained and available on site
      • Results of daily water testing is inadequately recorded: Free Available Chlorine, Combined Available Chlorine and pH is tested and recorded at least twice daily; Alkalinity and Cyanuric Acid is tested and recorded at least weekly.
  13. Routine

    1 infraction

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
  14. Routine

    3 infractions

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  15. Routine

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  16. Routine

    2 infractions

    • The pool pH level is properly maintained
    • The pool disinfectant is properly maintained

Nearby inspected facilities