The Salvation Army Pine Lake Camp - Pool

25032 South Pine Lake Road Red Deer County AB T0M 1S0 · Aquatic Facility

16 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was mentioned by the operator to be out of battery. The operator changed the battery of the digital flow meter after a discussion.Please ensure that all parts of the circulation system are maintained in good condition to ensure safe operation.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The pH and alkalinity test strips in the operator's pool test kit were noted to be expired.Please ensure that valid testing equipment is available to help monitor and confirm accurate chemical water quality values.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The July 15, 2025 water sample was reported to have an HPC count of 170 CFU/mL. Please ensure that any necessary treatment is conducted and a re-sample is submitted.
  5. Risk Management Inspection

    0 infractions

  6. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • - June 25, 2025: The total alkalinity of the pool basin was measured to exceed the testing equipment range. Several tests were conducted to confirm the readings. - June 17, 2025: The total alkalinity of the pool basin was measured to exceed the testing equipment range. Several tests were conducted to confirm the readings. - July 9, 2024: The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation. A suggestion was provided to the operator to increase the flow rate to help address the alkalinity.
  7. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • - June 17, 2025: The total alkalinity of the pool basin was measured to exceed the testing equipment range. Several tests were conducted to confirm the readings. - July 9, 2024: The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation. A suggestion was provided to the operator to increase the flow rate to help address the alkalinity.
  8. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • - The June 10, 2025 water sample results were reported to measure 440 CFU/mL for HPC.  - The September 4, 2024 water sample results were reported to measure 210 CFU/mL for HPC. Please ensure that the aquatic system is assessed and a re-sample is submitted as discussed.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • - June 17, 2025: The total alkalinity of the pool basin was measured to exceed the testing equipment range. Several tests were conducted to confirm the readings. - July 9, 2024: The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation. A suggestion was provided to the operator to increase the flow rate to help address the alkalinity.
  9. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • - The June 10, 2025 water sample results were reported to measure 440 CFU/mL for HPC.  - The September 4, 2024 water sample results were reported to measure 210 CFU/mL for HPC. Please ensure that the aquatic system is assessed and a re-sample is submitted as discussed.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  10. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The September 4, 2024 water sample results were reported to measure 210 CFU/mL for HPC. Please ensure that the aquatic system is assessed and a re-sample is submitted as discussed.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  11. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  12. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The July 9, 2024 water sample results were reported to measure 650 CFU/mL for HPC. Please ensure that a re-sample is submitted as discussed.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  13. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 195 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  14. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 280 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  15. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WE-23-0075694HPC = 110CFU/mL shown in July 19, 2023 sample. A water sample was submitted on June 17, 2024. Results are pending.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool basin was measured at 280 ppm at the time of inspection.Please ensure that the alkalinity is lowered to a concentration of 60-180pm to ensure safe pool operation.
  16. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WE-23-0075694HPC = 110CFU/mL shown in July 19, 2023 sample