Thornhill Pool - Whirlpool
6725 Centre Street NW Calgary AB T2K 5C4 · Aquatic Facility
7 inspections
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Risk Management Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The chlorine in the pool measured 0.89ppm. Ensure chlorine is above 2ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity was at 50ppm. Ensure total alkalinity is between 60-180ppm.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The automated feeder is not able to calculate and feed chlorine at all times. Operator had to manual feed chlorine and calibrate onsite. Repair or replace unit.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover calculated at 40 mins. Increase flow rate to achieve a 20 min turn over. Repair flow meter sensor.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The automated feeder is not able to calculate and feed chlorine at all times. Operator had to manual feed chlorine and calibrate onsite. Repair or replace unit.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover calculated at 40 mins. Increase flow rate to achieve a 20 min turn over. Repair flow meter sensor.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow is too fast for the hot tub. Filtration rate calculated at 40.15 gal/m/ft2. Slow flowrate down.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Staff are not consistently documenting anti-entrapment checks and steam room checks. Steam room should be monitored when it is operational. Check steam room temp and anti-entrapment daily and document it.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?