Tonquin Motor Inn - Whirlpool North Blue Octagon
100 Juniper Street Jasper AB T0E 1E0 · Aquatic Facility
10 inspections
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer weirs were missing. Reinstall the weirs to ensure proper skimmer function.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on December 29 was unsatisfactory: total coliforms present, and pseudomonas aeruginosa isolated.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Heterotrophic Plate Count is present on the water sample submitted on December 29, 2025.HPC - 40 CFU/ml
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer weirs were missing. Reinstall the weirs to ensure proper skimmer function.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer weirs were missing. Reinstall the weirs to ensure proper skimmer function.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The hot tub pump was observed to be leaking at the time of inspection. Repair is required to maintain proper function and prevent further damage.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample submitted on Aug 25, 2025, is reported as unsatisfactory.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The hot tub pump was observed to be leaking at the time of inspection. Repair is required to maintain proper function and prevent further damage.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The hot tub pump was observed to be leaking at the time of inspection. Repair is required to maintain proper function and prevent further damage.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Water chemical parameters—such as chlorine, pH, and ORP—were not recorded in the maintenance logbook for several days during the week. Ensure water testing and equipment/device monitoring are conducted at least once per day, and that all results are accurately documented to meet regulatory requirements and maintain safe water quality.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. The flow rate meter is leaking water, which cause water pooling on the floor in the mechanical room. - Repair or replace the flow rate meter.2. Calibrate the ORP probe of the automated controller so that the reading of the controller is accurate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Concentration of free chlorine in the water was at 0.9 ppm, while ORP tested to be 670mv. It was found that the liquid chlorine in the container of the chemical dosing system was almost running out. - Ensure free chlorine in the water is kept above 2 ppm. This was corrected during inspection. Free chlorine was at 2.1 at the second test during inspection.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- No clock is provided at the deck for monitoring length of use by bathers.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- The clock at the deck was not working. - Repair or replacement is required.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?