Town of Bonnyville Pool - Main Pool
4712 48 Street Bonnyville AB T9N 2J7 · Aquatic Facility
8 inspections
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine levels were recorded at 1.43 ppm. Ensure that combined chlorine levels are maintained as low as possible.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC- 57,000 CFU/mL.Results have been discussed with pool supervisor. Instructed to treat the pool and submit a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC- 810cfu/mLResults have been discussed with pool supervisor. Instructed to treat the pool and submit a resample. Procedure:1. Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.2. Run the water through the circulation system for at least 4-6 hours. 3. Adjust water chemistry to regular operating parameters.4. Take a bacteriological water sample and send it to the lab.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- -One of the pool handrails (on the left side from the main entrance) was moving, it was not sturdy.Action required:-Please fix the indicated handrail.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC = 230 CFU/mLTC ABSENT
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Pool volume = 165714Gflow rate = 425gpmturnover = 165714/425/60=6.5hPlease adjust flow rate to enable a turnover within 6h.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?