Town of Stony Plain Wading Pool
5210 55 Avenue Stony Plain AB T7Z 1Y1 · Aquatic Facility
22 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- June 4 2026 water sample evidenced 300 cfu/ 100ml
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter for this wading pool was not working at time of inspection. Ensure flow meter is repaired.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Bacteriological water sample this week showed elevated HPC (110 CFU per 100mL).
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Two bacteriological water samples taken from the wading pool showed a presence of total coliforms.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Two bacteriological water samples taken from the wading pool showed a presence of total coliforms.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on June 17, 2025, showed a presence of pseudomonas aeruginosa. Pool operator has closed the pool and restricted access. The pool is to remain closed until a satisfactory bacteriological water sample returns.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on June 17, 2025, showed a presence of total coliforms. Since this is the second week of a critical water sample result, the pool operator has closed the pool and restricted access. The pool is to remain closed until a satisfactory bacteriological water sample returns.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on June 17, 2025, showed HPC count at 3,760 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The two water samples collected on June 10 2025 both evidenced total coliforms present.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined Chlorine reading is greater than 1. Please ensure that combined chlorine is below 1ppm.
- 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
- Pool permit was not posted during time of inspection. Facility operator was informed of the requirement to have the permit posted at a place where it can be viewed by the public.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow rate was not able to be measured at the time of inspection. The floater was stuck at the bottom of the flow meter indicating no flow.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample results from July 30, 2024 showed HPC count at 630 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample results from June 18, 2024 showed HPC count at 210 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected June 11 2024 showed TC 3000 and pseudomonas isolated
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC count was above 100 CFU. Discussed results with facility manager.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC count was above 100 CFU.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?