Town of Stony Plain - Water Spray Park
5210 55 Avenue Stony Plain AB T7Z 1Y1 · Aquatic Facility
20 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The HPC count from sample collected August 18, 2026, was reported at 390 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- REPEAT VIOLATION: The HPC count was elevated this week (sample date: August 4, 2026). HPC value: 290 CFU/mL.The recirculation system is required to be taken out of service immediately. The spray park may remain operational provided it is supplied with municipal water and operated on a straight-to-waste basis, with no recirculation of water.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- REPEAT VIOLATION: The HPC count was elevated this week (sample date: July 28, 2026). HPC value: 230 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The HPC count was elevated this week (sample date: July 21, 2026). HPC value: 190 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- July 7, 2026, water sample returned with elevated HPC at 3070 CFU/mLPool operator to shock chlorinate the recirculation system and submit a new sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted from this spray park on June 17, 2026, showed the Heterotrophic Plate Count was elevated (190 CFU/mL)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
3 infractions
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- One of the 3 sand filters was not operational at time of inspection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for ORP was not working at time of inspection.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- PHI could not get a reading on chlorine levels or total alkalinity (too high)
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for ORP was not working at time of inspection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The bacteriological water sample from this spray park had a presence of total coliform bacteria in sample from August 26, 2025.Pool operator will run the spray park as a flow through system (no recirculation) until a satisfactory water sample returns.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for ORP was not working at time of inspection.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas aeruginosa was present in the east side bacteriological water sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for ORP was not working at time of inspection.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The probe for ORP was not working at time of inspection.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample showed HPC exceedance. 170 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH measured at 8.26.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?