Travelodge - Swimming Pool
7012 Macleod Trail SE Calgary AB T2H 0L3 · Aquatic Facility
12 inspections
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimming devices were not skimming the water, and it appeared there wasn't even flow.-main drain valve (~40%) and skimming valves (~80%) were adjusted which seemed to make a difference.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on Aug 15, 2025 was rejected by the Prov Lab as there was no identification on the bottle.-resample
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There are chips and gouges in the basin. Ensure this is repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There are chips and gouges in the basin. Ensure this is repaired.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. There were major discrepancies between automated control pH reading and manual reading. - Repair and maintain automated controller.2. The service light was on at the salt cell controller box. Repair salt cell.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow rate for the pool was 35gpm and the turnover rate was calculated at 11 hours. Increase flow to meet a turnover rate of 6 hours or less.2. Chlorine pucks observed in skimmer basket. Remove pucks from site.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There are chips and gouges in the basin. Ensure this is repaired.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Recording keeping was not complete - automated controller readings. Ensure records are completed daily.* On going violation*July 18 2025 observations- Total alkalinity was logged at 15ppm on July 15 2025 with no corrective action.- Operator is not recording ORP.- No records for July 17 2025.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The flow rate for the pool was 35gpm and the turnover rate was calculated at 11 hours. Increase flow to meet a turnover rate of 6 hours or less.2. Chlorine pucks observed in skimmer basket. Remove pucks from site.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. There were major discrepancies between automated control pH reading and manual reading. - Repair and maintain automated controller.2. The service light was on at the salt cell controller box. Repair salt cell.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There are chips and gouges in the basin. Ensure this is repaired.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Recording keeping was not complete - automated controller readings. Ensure records are completed daily.* On going violation*July 18 2025 observations- Total alkalinity was logged at 15ppm on July 15 2025 with no corrective action.- Operator is not recording ORP.- No records for July 17 2025.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH measured 7.74. Ensure the pH is between 6.8-7.6
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 2. There was a major discrepancy between automated control pH reading and manual reading. - Repair and maintain automated controller.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There are chips and gouges in the basin. Ensure this is repaired.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Recording keeping was not complete - automated controller readings. Ensure records are completed daily.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The operator indicated the automated feed system is not able to achieve required free chlorine. 2. There was a major discrepancy between automated control pH reading and manual reading. 3. There is a build of debris on the probes for the automated controller.- Repair and maintain automated controller. 4. Chlorine pucks were used in skimmers to achieve free chlorine residual. - Chlorine pucks are not permitted.5. There were no floating weirs in the skimmers. Install floating weirs.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- 1. The drain covers install do not indicate that they are compliant with the VGB standard. Provide a certificate of compliance or install new drain covers. Pool cannot open for the season until this is completed.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- There is a leak at the filter pipe. Repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Recording keeping was not complete - facility did not record TA, automated controller readings and anti-entrapment checks. Ensure records are completed daily.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter in the mechanical room is not working and has a build up of debris and calcium on the meter.Please repair or replace the flow meter so that it is in working order.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample collected on July 25, 2024 had an HPC count of 220 CFU/ml.Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter in the mechanical room is not working and has a build up of debris and calcium on the meter.Please repair or replace the flow meter so that it is in working order.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter in the mechanical room is not working and has a build up of debris and calcium on the meter.Please repair or replace the flow meter so that it is in working order.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?