Travers Ridge RV Resort - Swimming Pool

150116 Range Road 222 Vulcan County AB T0L · Aquatic Facility

23 inspections

  1. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The bacterial water sample submitted on September 4th was unsatisfactory. TC present.Treat the pool and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  2. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 8/21. The bacterial water sample submitted on August 18th was unsatisfactory. TC: AbsentHPC: 4020 CFU/mLOperator has stated that they are going to treat the pool and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  4. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  5. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 8/13. The bacterial water sample submitted on August 12th was unsatisfactory. - TC present. Treat pool, balance water chemistry, and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  6. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  7. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 6/25. The bacterial water sample submitted on June 24th, 2025, was unsatisfactory. Treat the pool, balance water chemistry, and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  8. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The bacteriological water sample submitted on August 27th, 2024 was unsatisfactory. - Total coliforms present. Treat the pool and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  11. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The bacteriological water sample submitted on July 22, 2024 was unsatisfactory. - Total coliforms present in the sample. Please treat the pool and resample when the water chemistry has been rebalanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  12. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automatic controller reading for pH (7.7) and the manual test results for pH (7.17) were not consistent.Recalibrate automatic controller and ensure the test results are consistent.
  13. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The measured concentration of cyanuric acid in the pool was 68ppm. The maximum concentration of cyanuric acid allowed is 50ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The top flow meter was not operating properly. Please repair or replace flow meter.
  14. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 28th of May 2024: Received bacteriological water sample indicated a presence of total coliforms.A bacteriological water sample was submitted on August 28, 2023. Sample was unsatisfactory: - Total coliforms present.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 28th of May 2024: Received bacteriological water sample indicated a Heterotropic Plate Count of 200CFU/100mL.8/31.The water sample that was submitted on the 28th of August was unsatisfactory (HPC of 310/100mL)8/24. The water sample that was submitted on August 22, 2023 was unsatisfactory. - HPC was 140 CFUBalance water chemistry and resample. A water sample was submitted on August 15 that was unsatisfactory. - HPC was 110.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The measured concentration of cyanuric acid in the pool was 68ppm. The maximum concentration of cyanuric acid allowed is 50ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The top flow meter was not operating properly. Please repair or replace flow meter.
  15. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • A bacteriological water sample was submitted on August 28, 2023. Sample was unsatisfactory: - Total coliforms present.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 8/31.The water sample that was submitted on the 28th of August was unsatisfactory (HPC of 310/100mL)8/24. The water sample that was submitted on August 22, 2023 was unsatisfactory. - HPC was 140 CFUBalance water chemistry and resample. A water sample was submitted on August 15 that was unsatisfactory. - HPC was 110.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The measured concentration of cyanuric acid in the pool was 68ppm. The maximum concentration of cyanuric acid allowed is 50ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The top flow meter was not operating properly. Please repair or replace flow meter.
  16. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • A bacteriological water sample was submitted on August 28, 2023. Sample was unsatisfactory: - Total coliforms present.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 8/24. The water sample that was submitted on August 22, 2023 was unsatisfactory. - HPC was 140 CFUBalance water chemistry and resample. A water sample was submitted on August 15 that was unsatisfactory. - HPC was 110.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The measured concentration of cyanuric acid in the pool was 68ppm. The maximum concentration of cyanuric acid allowed is 50ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The top flow meter was not operating properly. Please repair or replace flow meter.
  17. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 8/24. The water sample that was submitted on August 22, 2023 was unsatisfactory. - HPC was 140 CFUBalance water chemistry and resample. A water sample was submitted on August 15 that was unsatisfactory. - HPC was 110.
  18. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • A water sample was submitted on August 15 that was unsatisfactory. - HPC was 110.
  19. Risk Management Inspection

    0 infractions

  20. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample that was submitted on August 3 was unsatisfactory. - Total coliforms were present in the sample. Actions:- Close the pool, superchlorinate, rebalance water chemistry, and resample the water.
  21. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample submitted on July 25, 2023 was unsatisfactory. - HPC was 570Actions:- CYA must be lowered. Max 50ppm is allowed. - Balance water chemistry and resample water.
  22. Risk Management Inspection

    0 infractions

  23. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 7/20. Water sample that was submitted on 7/17 was unsatisfactory. High in HPC7/14. A water sample was submitted on 7/10 was satisfactory. A water sample was submitted on July 5th. Sample was unsatisfactory. Total Coliforms: AbsentHPC = 3000 CFUWater must be resampled and check water chemistry.