Vivo for Healthier Generations - Whirlpool

11950 Country Village Link NE Calgary AB T3K 6E3 · Aquatic Facility

9 inspections

  1. Demand Inspection

    0 infractions

  2. Monitoring Inspection

    0 infractions

  3. Monitoring Inspection

    0 infractions

  4. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 18/03/2025 09:29 is LATER than the Date/Time of receipt. (When this occurs, the Date and Time defaults to the date and time the specimen was received by the laboratory). Date and Time of collection was given as 2025/03/25 @0700.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. There was a discrepancy between the system readings and the manual readings. System reading said pH was 7.61 and manual reading indicated it was 7.37. 2. Flow meter for the jet pump is not accurately recording flow rate as it was bouncing around.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Water temperature was 40.7 C
  5. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. There was a discrepancy between the system readings and the manual readings. System reading said pH was 7.61 and manual reading indicated it was 7.37. 2. Flow meter for the jet pump is not accurately recording flow rate as it was bouncing around.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Water temperature was 40.7 C
  6. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. There was a discrepancy between the system readings and the manual readings. System reading said pH was 7.61 and manual reading indicated it was 7.37. 2. Flow meter for the jet pump is not accurately recording flow rate as it was bouncing around.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • Water temperature was 40.7 C
  7. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter for the jet pump is not accurately recording flow rate. Please install the correct flow meter.
  8. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity measured 27 ppm. Please ensure that alkalinity is between 60-120 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter for the jet pump is not accurately recording flow rate. Please install the correct flow meter.
  9. Risk Management Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Free available chlorine was less than the minimum 2 ppm.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • System has been updated to chlorine gas, but is currently being fed chemicals (chlorine and acid) manually to keep balanced. Facility must ensure that the automation system is fully operational before opening.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate was measured to be every 25 minutes vs the required 20 min. The minimum flow rate should be 495 GPM.