Waterfront Parkside Site 2 - Whirlpool
108 Waterfront Court SW Calgary AB T2P 1K7 · Aquatic Facility
11 inspections
- Demand Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There were no visible Clock in the Whirlpool area. - Ensure that a clock must be clearly visible from the whirpool.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Risk Management Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There were no visible Clock in the Whirlpool area. - Ensure that a clock must be clearly visible from the whirpool.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample (25ES-267E00431) collected on September 24th, 2025, came back unsatisfactory as Total Coliforms were present in the sample. Please close the whirlpool, treat the water, rebalance, and resample immediately.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There were no visible Clock in the Whirlpool area. - Ensure that a clock must be clearly visible from the whirpool.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- There were no visible Clock in the Whirlpool area. - Ensure that a clock must be clearly visible from the whirpool.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Demand Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity at 36 mg/L.Ensure the total alkalinity is kept between 60-180 mg/L.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample collected May 1, 2024 had an unsatisfactory result of HPC @ 250 CFU/mL.-Re-sample
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine is measured 1.75 ppm. Operator's own test this morning also showed combined chlorine at 1.65 ppm.-Keep combined chlorine is as low as possible
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The sample collected on March 27, 2024 had an HPC count of 120 CFU/ml.Treat and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine is measured 1.75 ppm. Operator's own test this morning also showed combined chlorine at 1.65 ppm.-Keep combined chlorine is as low as possible
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine is measured 1.75 ppm. Operator's own test this morning also showed combined chlorine at 1.65 ppm.-Keep combined chlorine is as low as possible
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine is measured 1.75 ppm. Operator's own test this morning also showed combined chlorine at 1.65 ppm.-Keep combined chlorine is as low as possible
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas isolated from sample.-Treat and re-sample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC >57000 CFU/mL.-Treat and re-sample
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine is measured 1.75 ppm. Operator's own test this morning also showed combined chlorine at 1.65 ppm.-Keep combined chlorine is as low as possible
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined Chlorine is measured 1.75 ppm. Operator's own test this morning also showed combined chlorine at 1.65 ppm.-Keep combined chlorine is as low as possible
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?