Westgate Park - Whirlpool

33 Spruce Place SW Calgary AB T3C 3X5 · Aquatic Facility

5 inspections

  1. Monitoring Inspection

    0 infractions

  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on "August 5, 2024" wasn't processed because it was received more than 24hours after collected.--suspected error filling out the requisition form.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The whirlpool turnover rate was high, at 27 minutes.-Please adjust the flow rate and ensure turnover rate is within 20 minutes as required by the Pool Standards, 2014 (amended 2018).
  3. Demand Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The whirlpool turnover rate was high, at 27 minutes.-Please adjust the flow rate and ensure turnover rate is within 20 minutes as required by the Pool Standards, 2014 (amended 2018).
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 2) June 20, 2024 water sample24ES173E00023HPC= 120 CFU/mL1) June 13, 2024 water sample24ES-166E00035Req ID #: 2282234HPC= >57,000 CFU/mLPseudomonas aeruginosa = ISOLATED
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The whirlpool turnover rate was high, at 27 minutes.-Please adjust the flow rate and ensure turnover rate is within 20 minutes as required by the Pool Standards, 2014 (amended 2018).
  5. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • June 13, 2024 water sample24ES-166E00035Req ID #: 2282234HPC= >57,000 CFU/mLPseudomonas aeruginosa = ISOLATED
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • June 13, 2024 water sample24ES-166E00035Req ID #: 2282234HPC= >57,000 CFU/mLPseudomonas aeruginosa = ISOLATED
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The whirlpool turnover rate was high, at 27 minutes.-Please adjust the flow rate and ensure turnover rate is within 20 minutes as required by the Pool Standards, 2014 (amended 2018).