William Lutsky YMCA - Swimming Pool
1975 111 Street NW Edmonton AB T6J 7C6 · Aquatic Facility
6 inspections
- Risk Management Inspection
0 infractions
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter appears to have sand surrounding the float and may be stuck. Clean or replace flow meter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The metal plate on the west side of the shallow end over the gutter system is bent and an edge was protruding out. Check and ensure the edge does not become a safety hazard.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on [Date] was unsatisfactory: HPC 610 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate of the swimming pool was 316 GPM and the calculated turnover is higher than 6 hours. Circulation pump was noted to be making a louder than normal noise. Operator instructed to investigate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?