William Lutsky YMCA - Women's Whirlpool
1975 111 Street NW Edmonton AB T6J 7C6 · Aquatic Facility
9 inspections
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 3 June 2025 was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 3 June 2025 was unsatisfactory: HPC 650 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate exceeds the maximum filtration rate of the sand filters installed. The flow rate was 155 GPM and must be between 120-130 GPM. Adjust the flow rate to ensure proper filtration in the system.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH reading for the automated controller is not consistent with the actual pH readings in the pool. Operator stated they have a service call scheduled for next week to replace the pH probe. Ensure the system is adjusted to maintain consistent pH values.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 20 Feb 2024 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 2024-02-27 [Accession #: WE-24-0019715] was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 20 Feb 2024 was unsatisfactory: Pseudomonas aeruginosa isolated, Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?