Wingate by Wyndham Fort Saskatchewan - Swimming Pool

10120 86 Avenue Fort Saskatchewan AB T8L 0N6 · Aquatic Facility

23 inspections

  1. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool water temperature was measured at 30.7 degrees Celsius. If temperature is kept above 30 operators must test for pseudomonas.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • Flow of the pool was 80 at the time of the inspection. It was lowered to 70 as max flow rating for sand filter is 74.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Pool rules are missing from sign:-Bathers must take a shower using soap prior to entering the public swimming pool-Patrons must wash their hands using soap after using the washroomor changing diapers-Street footwear must not be worn in wet traffic areas-Patrons who are intoxicated will not be allowed to use the poolPlease ensure these rules are posted somewhere around the pool.
  2. Demand Inspection

    6 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool was measured at 29 ppm. Ensure total alkalinity is raised and maintained between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow of the water was not maximized through the skimming devices. Ensure water flow is maximized through the skimming devices.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The water level of the pool was too low. Raise water level to halfway up the skimmers.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was sand accumulating in the corners of the pool. Investigate the source of the sand and repair.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. Pool testing is not occurring regularly to ensure proper chemical parameters are being maintained. 2. No records of pool sampling have been kept since Nov 20, 2025. Ensure the pool is being tested daily and results logged.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Pool rules are missing from sign:-Bathers must take a shower using soap prior to entering the public swimming pool-Patrons must wash their hands using soap after using the washroomor changing diapers-Street footwear must not be worn in wet traffic areas-Patrons who are intoxicated will not be allowed to use the poolPlease ensure these rules are posted somewhere around the pool.
  3. Monitoring Inspection

    7 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • No pool samples had been submitted since Nov 18, 2025. Pool sample was taken during inspection and submitted. Also, since the pool temperature is kept over 30C, testing must be performed for pseudomonas aeruginosa as well as HPC and TC. Ensure you are sampling water every week, and either select to sample for pseudomonas aeruginosa as well, or lower pool temperature to below 30C.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity of the pool was measured at 29 ppm. Ensure total alkalinity is raised and maintained between 60-180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow of the water was not maximized through the skimming devices. Ensure water flow is maximized through the skimming devices.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The water level of the pool was too low. Raise water level to halfway up the skimmers.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was sand accumulating in the corners of the pool. Investigate the source of the sand and repair.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. Pool testing is not occurring regularly to ensure proper chemical parameters are being maintained. 2. No records of pool sampling have been kept since Nov 20, 2025. Ensure the pool is being tested daily and results logged.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Pool rules are missing from sign:-Bathers must take a shower using soap prior to entering the public swimming pool-Patrons must wash their hands using soap after using the washroomor changing diapers-Street footwear must not be worn in wet traffic areas-Patrons who are intoxicated will not be allowed to use the poolPlease ensure these rules are posted somewhere around the pool.
  4. Risk Management Inspection

    0 infractions

  5. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • First test of pH was unreadable. Second reading pH was 8.2.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate measured 80 GPM.Sand filter maximum rate of filtration is 73 GPM.
  6. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Ensure pool samples are submitted every week.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • pH was unreadable and automated reader stated pH was 6.45Total Alkalinity was 0.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The facility has recently undergone a name change and a new permit application has not been received.
  7. Risk Management Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Ensure pool samples are submitted every week.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • pH was unreadable and automated reader stated pH was 6.45Total Alkalinity was 0.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The facility has recently undergone a name change and a new permit application has not been received.
  8. Risk Management Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Ensure pool samples are submitted every week.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • pH was unreadable and automated reader stated pH was 6.45Total Alkalinity was 0.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The facility has recently undergone a name change and a new permit application has not been received.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a plumbing leak in the pool mechanical room coming from one of the water feed pipes.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No pool operator onsite. Ensure plans are in place for pool monitoring.
  9. Risk Management Inspection

    7 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Ensure pool samples are submitted every week.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • pH was unreadable and automated reader stated pH was 6.45Total Alkalinity was 0.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The common area appeared have heavy condensation on the walls and ceiling. Ensure HVAC system is assessed, and the source of condensation is determined.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The facility has recently undergone a name change and a new permit application has not been received.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition. Provide AHS-EPH a timeline with completion for the work needed. This is an on-going violation and must be corrected.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a plumbing leak in the pool mechanical room coming from one of the water feed pipes.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No pool operator onsite. Ensure plans are in place for pool monitoring.
  10. Demand Inspection

    12 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Ensure pool samples are submitted every week.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free chlorine concentration of the swimming pool was 0.11 milligrams per litre.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The recirculation valves for both the main drain and skimmer valves were fully opened and were not set in a way to maximize the flow of the water through the skimming devices.Neither of the skimmer drains had floating weirs or floating baskets.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow meter was not operational at the time of inspection2. The automated chemical feeding and monitoring equipment was not operating at the time of inspection.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The common area appeared have heavy condensation on the walls and ceiling. Ensure HVAC system is assessed, and the source of condensation is determined.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • The facility has recently undergone a name change and a new permit application has not been received.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was an accumulation of sand at the bottom of the swimming pool.The was a fine layer of pollen or poplar fluff floating on the surface of the swimming pool.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a plumbing leak in the pool mechanical room coming from one of the water feed pipes.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition. Provide AHS-EPH a timeline with completion for the work needed. This is an on-going violation and must be corrected.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No pool operator onsite. Ensure plans are in place for pool monitoring.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Ensure reagents are valid and available onsite.Records are not maintained. Gaps were noted. Automated controller readings must be consistent with any manual tests.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Gaps for several days observed for manual chemistry of the pool. Ensure testing is done and records are maintained.
  11. Monitoring Inspection

    9 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Ensure pool samples are submitted every week.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FC and pH low
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity for the pool was tested to be at 4 ppm.Please note that Total Alkalinity must be maintained between 60ppm - 180ppm. This is an ongoing non-compliance.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The common area appeared have heavy condensation on the walls and ceiling. Ensure HVAC system is assessed, and the source of condensation is determined.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition. Provide AHS-EPH a timeline with completion for the work needed. This is an on-going violation and must be corrected.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No pool operator onsite. Ensure plans are in place for pool monitoring.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Gaps for several days observed for manual chemistry of the pool. Ensure testing is done and records are maintained.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Ensure reagents are valid and available onsite.Records are not maintained. Gaps were noted. Automated controller readings must be consistent with any manual tests.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan. Please work with your pool service provider to ensure an anti-entrapment plan is created. Note that this violation has been ongoing and must be corrected immediately, if not corrected, further enforcement actions may be used.
  12. Risk Management Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Last sample was submitted in January.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity for the pool was tested to be at 40/47 ppm. Please note that Total Alkalinity must be maintained between 60ppm - 180ppm. This is an ongoing non-compliance.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition. Provide AHS-EPH a timeline with completion for the work needed. March 27, 2024: The surface finishing for the swimming pool steps was still in disrepair (chipping off). This is an on-going violation and must be corrected.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Ensure reagents are valid and available onsite.Records are not maintained. Gaps were noted. Automated controller readings must be consistent with any manual tests.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.March 27, 2024: Anti-entrapment plan was not provided at the time of inspection. Please work with your pool service provider to ensure an anti-entrapment plan is created. Note that this violation has been ongoing and must be corrected immediately, if not corrected, further enforcement actions may be used.
  13. Risk Management Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Last sample was submitted in January.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity for the pool was tested to be at 56 ppm. Please note that Total Alkalinity must be maintained between 60ppm - 180ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.March 27, 2024: The surface finishing for the swimming pool steps was still in disrepair (chipping off). This is an on-going violation and must be corrected.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.Jan 25, 2024; the manager promised to enroll the maintenance staff to the next CPO course and monitor daily tests closely.March 27, 2024: The certificate provided for a pool operator associated with the facility who was not on site had expired. The current manager stated that he will enroll for CPO course.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.Jan 25, 2024; FAC and Phenol red reagents are up to date. Ensure all other expired reagents are replaced.March 27, 2024: Most observed reagents had expired, including reagents for total alkalinity, pH, total choline and one free chlorine reagent. Please ensure the reagents are replaced. This is an on-going violation and must be corrected immediately.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.March 27, 2024: Anti-entrapment plan was not provided at the time of inspection. Please work with your pool service provider to ensure an anti-entrapment plan is created. Note that this violation has been ongoing and must be corrected immediately, if not corrected, further enforcement actions may be used.
  14. Monitoring Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Pool samples are not submitted to Prov Lab every week. Last sample was submitted in January.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity for the pool was tested to be at 56 ppm. Please note that Total Alkalinity must be maintained between 60ppm - 180ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.March 27, 2024: The surface finishing for the swimming pool steps was still in disrepair (chipping off). This is an on-going violation and must be corrected.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.Jan 25, 2024; the manager promised to enroll the maintenance staff to the next CPO course and monitor daily tests closely.March 27, 2024: The certificate provided for a pool operator associated with the facility who was not on site had expired. The current manager stated that he will enroll for CPO course.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.Jan 25, 2024; FAC and Phenol red reagents are up to date. Ensure all other expired reagents are replaced.March 27, 2024: Most observed reagents had expired, including reagents for total alkalinity, pH, total choline and one free chlorine reagent. Please ensure the reagents are replaced. This is an on-going violation and must be corrected immediately.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.March 27, 2024: Anti-entrapment plan was not provided at the time of inspection. Please work with your pool service provider to ensure an anti-entrapment plan is created. Note that this violation has been ongoing and must be corrected immediately, if not corrected, further enforcement actions may be used.
  15. Risk Management Inspection

    5 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total Alkalinity for the pool was tested to be at 56 ppm. Please note that Total Alkalinity must be maintained between 60ppm - 180ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.March 27, 2024: The surface finishing for the swimming pool steps was still in disrepair (chipping off). This is an on-going violation and must be corrected.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.Jan 25, 2024; the manager promised to enroll the maintenance staff to the next CPO course and monitor daily tests closely.March 27, 2024: The certificate provided for a pool operator associated with the facility who was not on site had expired. The current manager stated that he will enroll for CPO course.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.Jan 25, 2024; FAC and Phenol red reagents are up to date. Ensure all other expired reagents are replaced.March 27, 2024: Most observed reagents had expired, including reagents for total alkalinity, pH, total choline and one free chlorine reagent. Please ensure the reagents are replaced. This is an on-going violation and must be corrected immediately.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.March 27, 2024: Anti-entrapment plan was not provided at the time of inspection. Please work with your pool service provider to ensure an anti-entrapment plan is created. Note that this violation has been ongoing and must be corrected immediately, if not corrected, further enforcement actions may be used.
  16. Risk Management Inspection

    5 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH was measured at 7.94 and read at 7.90 on the automated controller.Ensure pH is maintained between 6.8-7-6
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.Jan 25, 2024; the manager promised to enroll the maintenance staff to the next CPO course and monitor daily tests closely.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. FAC results were observed to range from 0.29 - 0.33 from November 2023 - December 19, 2023, with ORP of 698mV. Operator stated they don't have reagent for the first testing for FAC. Ensure to maintain the FAC at more than or equals to 1 or maintain ORP of 700mV to keep the FAC at more than or equals to 0.5.2. Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.Jan 25, 2024; FAC and Phenol red reagents are up to date. Ensure all other expired reagents are replaced.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.
  17. Risk Management Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • January 2, 2024 water sample.HPC was measured to be over 57000 CFU/mL.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. FAC results were observed to range from 0.29 - 0.33 from November 2023 - December 19, 2023, with ORP of 698mV. Operator stated they don't have reagent for the first testing for FAC. Ensure to maintain the FAC at more than or equals to 1 or maintain ORP of 700mV to keep the FAC at more than or equals to 0.5.2. Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.
  18. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • January 2, 2024 water sample.HPC was measured to be over 57000 CFU/mL.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. FAC results were observed to range from 0.29 - 0.33 from November 2023 - December 19, 2023, with ORP of 698mV. Operator stated they don't have reagent for the first testing for FAC. Ensure to maintain the FAC at more than or equals to 1 or maintain ORP of 700mV to keep the FAC at more than or equals to 0.5.2. Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.
  19. Monitoring Inspection

    4 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Surface finishing (concrete) of the swimming pool steps was observed to be chipping off. Please repair to maintain the pool in a clean and sanitary condition.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • No certified pool operator was available onsite. Ensure to have a certified pool operator available to monitor pool operation.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. FAC results were observed to range from 0.29 - 0.33 from November 2023 - December 19, 2023, with ORP of 698mV. Operator stated they don't have reagent for the first testing for FAC. Ensure to maintain the FAC at more than or equals to 1 or maintain ORP of 700mV to keep the FAC at more than or equals to 0.5.2. Incomplete and expired reagents for FAC and other parameters (TC and pH) were observed. Purchase new reagents as soon as possible.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Ongoing violation: Anti-entrapment plan was not provided at the time of inspection. Please send a complete anti-entrapment plan.
  20. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Anti-entrapment plan is incomplete. Please provide information/drawings/pictures regarding your sump pump.
  21. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample result was unsatisfactory. HPC>57000.Increase Free Available Chlorine (FAC) level to 10 ppm and maintain pH at or near 7.2.Run the water through the circulation system for at least one turnover. Balance the water, resample.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Anti-entrapment plan is incomplete. Please provide information/drawings/pictures regarding your sump pump.
  22. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Anti-entrapment plan is incomplete. Please provide information/drawings/pictures regarding your sump pump.
  23. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The swimming pool bacteriological water sample result from the August 16, 2023 submission came back with high number of HPC (830).
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Anti-entrapment plan is incomplete. Please provide information/drawings/pictures regarding your sump pump.