Wingate Inn Edmonton West - Swimming Pool

18220 100 Avenue NW Edmonton AB T5S 2V2 · Aquatic Facility

17 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity was tested three times at 50, 53, and 57 mg/l (ppm). Upon reviewing records, total alkalinity was tested and recorded by staff at less than 60 mg/l (ppm) each day in the last 4 days.Ensure total alkalinity is maintained at no less than 60 mg/l (ppm) and no greater than 180 mg/l (ppm).
  3. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was >1ppm and was not being maintained as low as possible for bather comfortMarch 5, 2025: Water chemistry not tested
  4. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was >1ppm and was not being maintained as low as possible for bather comfort
  5. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity was tested at 24ppm.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine was >1ppm and was not being maintained as low as possible for bather comfort
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter was not functional. Turnover period and filtration rate could not be calculated.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample results collected on 17/10/2024. Heterotrophic plate count: 110cfu/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  8. Risk Management Inspection

    0 infractions

  9. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity: 48ppmCombined Chlorine: 1.36ppmMaintain combined chlorine minimum ideally less than 1ppm for bather comfort.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1-floating weirs were missing from all the skimmers. Install floating weirs in or round weirs.2-There were discrepancies noted between manual test reading vs automated controller readings. manual reading for pH: 7.64 vs automated reading 7.21 (Set point: 7.2)Have your service provider (automated) onsite to service the controller and probs.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The floor of the pool basin was noted in disrepair near the main drains. Repair/patching required.
  10. Risk Management Inspection

    0 infractions

  11. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result submitted on 14-12-2023 Accession #WE-23-0133905 was unsatisfactory. Total Coliform present.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result submitted 2023-11-30 [Accession #: WE-23-0128567] was unsatisfactory: HPC 640 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  14. Risk Management Inspection

    0 infractions

  15. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample WE-23-0096773 submitted on Sep 07, 2023, was unsatisfactory: HPC 1140 CFU/mL.Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  16. Risk Management Inspection

    0 infractions

  17. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample result submitted on 2023-07-13 [Accession #: WE-23-0072857] was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.