Skip to content
Loading map…

160 Magrath Road NW - Whirlpool

160 Magrath Road NW Edmonton AB T6R 3T7 · Aquatic Facility

16 inspections

  1. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  2. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 26EN-154E01072 submitted on June 3, 2026, was unsatisfactory: Pseudomonas aeruginosa was isolated.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  3. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  4. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 25EN-300E00071 submitted on October 27, 2025, was unsatisfactory: Pseudomonas aeruginosa was isolated.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  5. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  6. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 25EN-209E00061 submitted on July 28, 2025, was unsatisfactory: Pseudomonas aeruginosa was isolated.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  7. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Combined maximum flow rate was185 gpm (recirculation pump maximum flow rate 80 gpm and jet pump maximum flow rate 105 gpm, both determined by the flow meters maximum flow), which exceeds the maximum allowed flow rate of the main drain outlet cover (150 gpm). The flow on the circulation pump has to be set to 45GPM and the valve has to be secured and tagged.
  8. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • An updated anti-entrapment compliance plan assessing the entrapment risks must be developed and available for review. Develop a new anti-entrapment compliance plan reflecting the updated equipment and submit the plan for review to Environmental Public Health.
  9. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • There was a discrepancy between the manual pH reading 7.25, and the automated controller reading pH 6.47. Please address.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • An updated anti-entrapment compliance plan assessing the entrapment risks must be developed and available for review. Develop a new anti-entrapment compliance plan reflecting the updated equipment and submit the plan for review to Environmental Public Health.
  10. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • There was a discrepancy between the manual pH reading 7.25, and the automated controller reading pH 6.47. Please address.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The main drain outlet covers (Aquastar 914101) expired on December 20, 2024. Replace themain drain outlets.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • An updated anti-entrapment compliance plan assessing the entrapment risks must be developed and available for review. Develop a new anti-entrapment compliance plan reflecting the updated equipment and submit the plan for review to Environmental Public Health.
  11. Risk Management Inspection

    0 infractions

  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The sample 25EN-013E00128, submitted on January 13, 2025, was unsatisfactory: Pseudomonas aeruginosa isolated and HPC 350.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample 25EN-013E00128, submitted on January 13, 2025, was unsatisfactory: Pseudomonas aeruginosa isolated and HPC 350.
  13. Monitoring Inspection

    0 infractions

  14. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample WE-23-0118566 submitted on November 6, 2023, was unsatisfactory: Pseudomonas aeruginosa isolated.
  15. Risk Management Inspection

    0 infractions

  16. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample WE-23-0076225 submitted on July 24, 2023, was unsatisfactory: Pseudomonas aeruginosa isolated.