Canalta Camrose - Swimming Pool
4710 73 Street Camrose AB T4V 0E5 · Aquatic Facility
28 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample received. HPC: 170 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on May 12, 2026: TC AbsentHPC 160 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on April 21, 2026:Total coliforms ABSENTHPC 570 CFU/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample result indicated that HPC was 270 CFU/mL. The reference range for HPC is <= 100 CFU/mL.*Note: Sample collector indicated that the pool was busy the weekend prior. Corrective action: Pool must be resampled.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on February 24, 2026:TC AbsentHPC 150 CFU/mLOperator Kevin was informed to:- Clean the scum line if needed- Ensure bathers take a shower before using the water- Ensure water chemistry is balanced - Ensure circulation and filtration systems are working properly and maintained - Ensure proper turnover- Resample next week
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on December 30, 3035:TC AbsentHPC 110 CFU/mLOperator was informed to:- Clean the scum line as needed- Ensure bathers take a shower before using the water- Ensure maximum bather load is being followed- Ensure water chemistry is within range- Ensure circulation and filtration systems are working properly- Ensure proper turnover- Resample next week
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample results:Sample collected on 2024-11-26HPC = 120 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is below 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample results:Sample collected on 2024-11-19HPC = 700 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is below 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The pool does not have adequate turnover.Turnover = Volume / Flow RateTurnover = 21,400 Gallons / 80 GPMTurnover = 267.5 minutes Turnover = 4.46 hoursPlease ensure turnover (recirculation rate) is within 4 hours.2) The filtration rate for this pool is too fast.Filtration Rate = Flow Rate / Filter AreaFiltration Rate = 80 GPM / 4.9 sq. ft.Filtration Rate = 16.3 GPM/sq. ft.- Please ensure filtration rate is within 15 GPM/sq. ft.*Note: It looks like the filter is designed to operate at 100 GPM with a filter area of 4.9 sq. ft.Manufacturer Specifications:Filter Model: Pentair Tagelus TA100DFilter Area: 4.9 sq. ft.Flow Rate: 100 GPMThis would make:Filtration rate:100 GPM / 4.9 sq. ft. = 20.41 GPM/sq. ft. (this is greater than what the AB Pool Standards requires - 15 GPM/sq. ft.)Turnover (recirculation rate):1,400 Gallons / 100 GPM = 214 minutes = 3.57 hours (this is within what the AB Pool Standards requires - 4 hours)Thus, running at a flow of 100 GPM would be satisfactory if water quality can be sufficiently maintained.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Third consecutive unsatisfactory water sample result:Sample collected on 2024-04-16HPC = 390 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is at or below 100 CFU/mL.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1) The pool does not have adequate turnover.Turnover = Volume / Flow RateTurnover = 21,400 Gallons / 80 GPMTurnover = 267.5 minutes Turnover = 4.46 hoursPlease ensure turnover (recirculation rate) is within 4 hours.2) The filtration rate for this pool is too fast.Filtration Rate = Flow Rate / Filter AreaFiltration Rate = 80 GPM / 4.9 sq. ft.Filtration Rate = 16.3 GPM/sq. ft.Please ensure filtration rate is within 15 GPM/sq. ft.Filter Model: Pentair Tagelus TA100D
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Third consecutive unsatisfactory water sample result:Sample collected on 2024-04-16HPC = 390 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is at or below 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample results:Sample collected on 2024-04-09HPC = 260 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is below 100 CFU/mL.Further treatment is required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample results:Sample collected on 2024-04-02HPC = 1060 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is below 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample results:Sample collected on 2024-03-05HPC = 110 CFU/mLPlease investigate and troubleshoot pool system to ensure HPC is below 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- One of the submerged suction outlets appeared to be broken.- Pool operator mentioned that this was observed, and the replacement cover had already been ordered/delivered and was available on site. It just has not yet been installed.- Issued closure order to close the pool until the suction outlet cover has been replaced.Educated operator that if a submerged suction outlet is broken (even minor damage), this presents a major entrapment hazard and the pool is to be immediately closed until the cover is appropriately replaced. If in the future, if you are ever unsure, please close the pool and contact AHS Environmental Public Health to further discuss.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample:TC - ABSENTHPC - 270 CFUSample collected on Sept 5.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?