Canalta Hotel - Swimming Pool

500 - 6700 46 Street Olds AB T4H 0A2 · Aquatic Facility

Inspection summary

Canalta Hotel - Swimming Pool has been inspected 15 times by Alberta Health Services (Environmental Public Health) since October 19, 2023. The most recent inspection, on July 23, 2026, found no infractions.

10 of 15 inspections on record found no infractions at all. In the past 12 months there were 3 inspections with 0 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.

The last 4 inspections in a row found no infractions. The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 5 times across 5 separate inspections, most recently on April 15, 2025. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

15 inspections

  1. Monitoring Inspection

    0 infractions

  2. Monitoring Inspection

    0 infractions

  3. Monitoring Inspection

    0 infractions

  4. Risk Management Inspection

    0 infractions

  5. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Volume: 24,825 usgFlow Rate: 96 gpmTurnover: 4.3 hrAn automated control system is installed and functioning.*Operator noted the filter needed to be backwashed, which was the cause of the reduced flow rate. Backwash filter and adjust flow rate to at least 105 gpm to meet the required 4 hour turnover time.
  6. Risk Management Inspection

    0 infractions

  7. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Vol: 24,825 usgFlow: 92 gpmTurnover: 4.5 hrNote: Minimum flow rate to meet 4 hour turnover time is: 105 gpm.Adjust flow rate to meet or exceed 105 gpm.
  8. Risk Management Inspection

    0 infractions

  9. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the water sample collected on November 13, 2024, which had the following results: - Total Coliform bacteria - ABSENT - HPC bacteria - 2870 CFU/mL.This is an unsatisfactory result.The following steps were given to the operator, they were: - to close the main pool from public use immediately. - to shock chlorinate the pool when all persons are removed. - after shock chlorinating - to backwash the filter - re-balance the water chemistry - the pool can then be re-opened to the public - resample on your regular sampling day.
  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • the water sample collected on November 13, 2024, which had the following results: - Total Coliform bacteria - ABSENT - HPC bacteria - 2870 CFU/mL.This is an unsatisfactory result.The following steps were given to the operator, they were: - to close the main pool from public use immediately. - to shock chlorinate the pool when all persons are removed. - after shock chlorinating - to backwash the filter - re-balance the water chemistry - the pool can then be re-opened to the public - resample on your regular sampling day.
  11. Demand Inspection

    0 infractions

  12. Monitoring Inspection

    0 infractions

  13. Monitoring Inspection

    0 infractions

  14. Risk Management Inspection

    0 infractions

  15. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • HPC result 450 / 100mlSample Date: 4 Oct 2023Accession NUmb: WE-23-0107761