Cascade Lodge Hot Tub #2 (next to pool door) has been inspected 34 times by Vancouver Coastal Health since October 15, 2015. The most recent inspection, on June 4, 2026, recorded 3 infractions.

12 of 34 inspections on record found no infractions at all. In the past 12 months there were 2 inspections with 6 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 32 times across 17 separate inspections, most recently on June 4, 2026. For example: The pool cyanuric acid stabilizer level is properly maintained

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded once on July 14, 2017. For example: Chemicals are stored in a safe manner and location

  • Equipment and utensilsLower risk

    Pumps, filters, chemical feeders and safety equipment such as lifebuoys, reaching poles and first-aid kits must be present and working. Missing safety equipment can matter a great deal in an emergency.

    Recorded 12 times across 12 separate inspections, most recently on June 4, 2026. For example: Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications

  • Other findingsLower risk

    Findings that do not fit the categories above, such as follow-ups that confirm an earlier violation was corrected, or requirements specific to this type of facility.

    Recorded once on August 30, 2016. For example: The hot tub enclosure has a clock and instructions for safe use of the hot tub, in clear view

About this data

These results come from Vancouver Coastal Health, which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

34 inspections

  1. Routine

    3 infractions

    • The pool cyanuric acid stabilizer level is properly maintained
    • Pool water velocity and recirculation rate is properly maintained
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  2. Routine

    3 infractions

    • The pool disinfectant is properly maintained
      • Free available chlorine is in excess of 10 ppm.
    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • Pool water velocity and recirculation rate is properly maintained
  3. Routine

    0 infractions

  4. Routine

    3 infractions

    • The pool disinfectant is properly maintained
      • Chlorine Cyanurate is less than 2.0 ppm at temperature above 30°C
    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
  5. Routine Follow-up

    0 infractions

  6. Routine

    2 infractions

    • Pool water velocity and recirculation rate is properly maintained
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  7. Routine Follow-up

    0 infractions

  8. Routine

    1 infraction

    • The operator maintains the pool in good repair.
  9. Routine

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  10. Routine Follow-up

    1 infraction

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
  11. Routine

    3 infractions

    • The Permit to Operate a pool is valid and is posted in a prominent location.
    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
  12. Routine

    0 infractions

  13. Routine

    0 infractions

  14. Request

    0 infractions

  15. Routine

    0 infractions

  16. Routine

    0 infractions

  17. Routine

    4 infractions

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool disinfectant is properly maintained
      • Chlorine Cyanurate is less than 2.0 ppm at temperature > 30°C
    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  18. Routine Follow-up

    1 infraction

    • Pool water velocity and recirculation rate is properly maintained
  19. Routine

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  20. Routine

    2 infractions

    • Pool water velocity and recirculation rate is properly maintained
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  21. Routine

    1 infraction

    • The pool has controlled access
      • Pool security fencing with a self-closing gate is lacking or inadequate
  22. Routine Follow-up

    0 infractions

  23. Routine

    2 infractions

    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  24. Routine Follow-up

    0 infractions

  25. Routine

    5 infractions

    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
    • Pool water velocity and recirculation rate is properly maintained
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
    • Chemicals are stored in a safe manner and location
  26. Routine

    4 infractions

    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • The pool cyanuric acid stabilizer level is properly maintained
      • The cyanuric acid stabilizer level is greater than 80 ppm
    • Pool water velocity and recirculation rate is properly maintained
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  27. Routine Follow-up

    0 infractions

  28. Routine Follow-up

    1 infraction

    • The pool has controlled access
      • The fence or barrier does not prevent access by animals and persons who are not pool patrons
  29. Routine

    1 infraction

    • The pool has controlled access
      • The fence or barrier does not prevent access by animals and persons who are not pool patrons
  30. Routine

    1 infraction

    • The hot tub enclosure has a clock and instructions for safe use of the hot tub, in clear view
      • Clock prominently displaying the time is not present or in clear view
  31. Routine Follow-up

    0 infractions

  32. Routine

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  33. Routine Follow-up

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
  34. Routine

    4 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • The pool is clean, clear of obstructions, and adequately supplied
      • The pool is not kept clean and clear of obstructions.
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications