CHARLES CARROLL ELEMENTARY
2929 W 83rd ST, CHICAGO, IL 60652 · School
24 inspections
- Canvass
1 infraction
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED THE BASE OF THE FAUCET IN THE STAFF WASHROOM WITH A LEAK. ALSO NOTED THE WATER PRESSURE LOW. MUST REPAIR AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- Canvass
1 infraction
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- LOW HOT WATER PRESSURE AND LEAKING FAUCET AT HANDWASH SINK IN FOOD STAFF TOILET ROOM. INSTD TO REPAIR AND MAINTAIN
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- Canvass Re-Inspection
0 infractions
- Canvass Re-Inspection
1 infraction
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- 5-202.12 (A): NO HOT RUNNING WATER UNDER CITY PRESSURE AT HANDWASH SINKS IN ALL TOILET ROOMS (STUDENTS AND STAFF), TEMPERATURES RANGING FROM 82.0F-84.0F. INSTD TO PROVIDE 100F-120F HOT RUNNING WATER AT ALL TIMES. VIOLATION 7-38-030 PRIORITY.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
1 infraction
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- NO HOT RUNNING WATER UNDER CITY PRESSURE AT HANDWASH SINKS IN ALL TOILET ROOMS (STUDENTS AND STAFF), TEMPERATURES RANGING FROM 82.0F-84.0F. INSTD TO PROVIDE 100F-120F HOT RUNNING WATER AT ALL TIMES. VIOLATION 7-38-030 PRIORITY.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
3 infractions
- 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
- NO PROCEDURE OR SUPPLIES ON SITE FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS. INSTD TO PROVIDE PROCEDURE AND NECESSARY SUPPLIES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS(INCLUDING EFFECTIVE SANITIZER AGAINST NOROVIRUS). PRIORITY FOUNDATION 7-38-005
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- NO HOT RUNNING WATER UNDER CITY PRESSURE AT HANDWASH SINKS IN ALL TOILET ROOMS (STUDENTS AND STAFF), TEMPERATURES RANGING FROM 76.0F-78.0F. INSTD TO PROVIDE 100F-120F HOT RUNNING WATER AT ALL TIMES. VIOLATION 7-38-030 PRIORITY.
- 12. FOOD RECEIVED AT PROPER TEMPERATURE
- OBSERVED 2 LARGE TRAYS OF COOKED PASTA AT IMPROPER RECEIVING TEMPERATURE OF 88.0F-90.0F UPON ARRIVAL FROM COOKING SCHOOL. INSTD TO HAVE RECEIVING TEMPERATURE OF HOT FOODS OF 135F OR ABOVE AT ALL TIMES. PASTA DISCARDED AND DENATURED AT THIS TIME. APPROX 20LBS $50 VALUE. PRIORITY VIOLATION 7-38-005.
- 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
- Canvass
2 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED THE 1st HAND SINK IN THE GIRLS 1st FLOOR WASHROOM NOT WORKING PROPERLY. INSTRUCTED ENGINEER WATER SHOULD STAY ON FOR AT LEASE 20 SECONDS FOR PROPER HAND WASHING.
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OBSERVED THE FRONT ENTRY DOOR NOT SEAL AT THE BOTTOM AT THE TOP OF THE STAIRS ACROSS THE HALL. MUST PROVIDE AND MAINTAIN WEATHER STRIPPING TO PROPERLY SEAL DOORS TO PRVENT ENTRY POINT FOR PESTS.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
1 infraction
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- MISSING COVERS FOR RECEPTACLES FEMALE TOILET ROOMS (STAFF). INSTD TO PROVIDE COVERS AND MAINTAIN
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- Canvass
3 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- NO HOT RUNNING WATER UNDER CITY PRESSURE AT HANDWASH SINKS IN ALL TOILET ROOMS (STUDENTS AND STAFF), 68.0F-70.0F. INSTD TO PROVIDE 100F-120F HOT RUNNING WATER AT ALL TIMES. VIOLATION 7-38-030 PRIORITY
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OVER 100 MICE DROPPINGS SCATTERED ON FLOOR IN STORAGE ROOMS AND FURNACE ROOM NEXT TO PREP AREA. INSTD TO REMOVE ALL DROPPINGS, CLEAN AND SANITIZE AFFECTED AREAS AND CONTACT PEST CONTROL FOR SERVICE. PRIORITY FOUNDATION VIOLATION 7-38-020(A)
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- MISSING COVERS FOR RECEPTACLES IN ALL FEMALE TOILET ROOMS (STUDENTS AND STAFF). INSTD TO PROVIDE COVERS AND MAINTAIN
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
2 infractions
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- INTERIOR OF HOT HOLDING UNITS IN NEED OF DETAIL CLEANING TO REMOVE FOOD SPILLS. INTRUCTED TO CORRECT AND MAINTAIN
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- Garbage can is employee restroom must be covered at all times. Correct and maintain.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- Canvass
0 infractions
- Canvass Re-Inspection
2 infractions
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- OBSERVED NO VALID CITY OF CHICAGO SANITATION CERTIFICATE ON PREMISES DURING INSPECTION. INSTRUCTED TO OBTAIN AND MAINTAIN. PRIORITY FOUNDATION VIOLATION. NO CITATION ISSUED. 7-38-012
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED VENTILATION SYSTEM IN WOMEN'S BATHROOM NOT WORKING PROPERLY. INSTRUCTED TO REPAIR AND MAINTAIN.
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- Canvass
5 infractions
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- OBSERVED NO VALID CITY OF CHICAGO SANITATION CERTIFICATE ON PREMISES DURING INSPECTION. INSTRUCTED TO OBTAIN AND MAINTAIN. PRIORITY FOUNDATION VIOLATION. NO CITATION ISSUED. 7-38-012
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OBSERVED APPROX. 100 MOUSE DROPPINGS IN THE MECHANICAL/STORAGE ROOM BY THE SEATING AREA OF THE CAFETERIA, AND APPROX. 40 MOUSE DROPPINGS UNDER THE SHELVING IN THE FOOD STORAGE AREA AND BEHIND THE 2-DOOR COOLER AND 2-DOOR FREEZER. INSTRUCTED TO CALL PEST CONTROL PROVIDER, CLEAN AND SANITIZE AFFECTED AREAS. PRIORITY FOUNDATION VIOLATION. NO CITATION ISSUED. 7-38-020(a)
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED A LEAK IN THE PIPPING UNDER THE THREE COMPARTMENT SINK CONNECTING TO THE GREASE TRAP. INSTRUCTED TO REPAIR AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED 3-COMPARTMENT SINK IN THE CAFETERIA AREA NOT DRAINING PROPERLY AND BACKING UP INTO THE MIDDLE AREA OF THE 3-COMP SINK. INSTRUCTED TO GET SERVICED AND MAINTAINED. PRIORITY VIOLATION. NO CITATION ISSUED. 7-38-030(c)
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED VENTILATION SYSTEM IN WOMEN'S BATHROOM NOT WORKING PROPERLY. INSTRUCTED TO REPAIR AND MAINTAIN.
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- Canvass
2 infractions
- 21. * CERTIFIED FOOD MANAGER ON SITE WHEN POTENTIALLY HAZARDOUS FOODS ARE PREPARED AND SERVED
- OBSERVED NO CITY OF CHICAGO SANITATION CERTIFICATE POSTED AT THIS TIME, INSTRUCTED TO PROVIDE. SERIOUS VIOLATION 7-38-012a.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- OBSERVED #10 CAN OPENER NOT CLEAN, INSTRUCTED TO CLEAN AND SANITIZE.
- 21. * CERTIFIED FOOD MANAGER ON SITE WHEN POTENTIALLY HAZARDOUS FOODS ARE PREPARED AND SERVED
- Canvass Re-Inspection
2 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- REACH IN FREEZER WITH EXCESSIVE ICE BUILD-UP. INSTD TO REMOVE EXCESSIVE ICE AND MAINTAIN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- SUPPORT BEAMS IN PREP AREA/CAFTERIA IN POOR REPAIR, CRUMBLING AND PEELING SURFACE, WRAPPED IN DUCT TAPE. INSTD TO REPAIR SAME SO AS TO BE A SMOOTH, EVEN, EASILY CLEANABLE SURFACE.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
3 infractions
- 11. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, DESIGNED, AND MAINTAINED
- NO COLD NOR TEMPERERED RUNNING WATER UNDER CITY PRESSURE AT EXPOSED HANDSINK IN PREP AREA/DISHWASHING AREA. INSTD TO PROVIDE COLD OR TEMPERED (85F) RUNNING WATER UNDER CITY PRESSURE FOR PROPER HANDWASHING. VIOLATION 7-38-030 CRITICAL.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- REACH IN FREEZER WITH EXCESSIVE ICE BUILD-UP. INSTD TO REMOVE EXCESSIVE ICE AND MAINTAIN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- SUPPORT BEAMS IN PREP AREA/CAFTERIA IN POOR REPAIR, CRUMBLING AND PEELING SURFACE, WRAPPED IN DUCT TAPE. INSTD TO REPAIR SAME SO AS TO BE A SMOOTH, EVEN, EASILY CLEANABLE SURFACE.
- 11. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, DESIGNED, AND MAINTAINED
- Canvass Re-Inspection
0 infractions
- Canvass
1 infraction
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- OBSERVED THE EAST SIDE OUTERMOST DOUBLE DOORS WITH A 1/4 INCH GAP BETWEEN THEM. INSTRUCTED TO PROVIDE RODENT PROOFED OUTER OPENINGS. SERIOUS VIOLATION 7-38-020
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass
2 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- OBSERVED THE LOWER BEAMS REPAIRED WITH DUST TAPE, NOT MAINTAINED THE USE OF DUCT TAPE TO REPAIR IS PROHIBITED. INSTRUCTED TO PROPERLY REPAIR THE LOWER BEAMS IN THE LUNCH ROOM. OBSERVED THE GLASS MISSING FROM THE FRONT HOT HOLDING UNIT, INSTRUCTED TO REPLACE.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- OBSERVED THE INTERIOR OF THE REAR MILK COOLER NOT CLEAN, INSTRUCTED TO CLEAN.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
4 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- FOUND WASH BOWLS IN GIRLS AND BOYS TOILET ROOMS IN NEED OF RECAULKING. INSTRUCTED TO RECAULK AND MAINTAIN.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- MUST REPLACE/PROVIDE MISSING/DAMAGED FLOOR TILES IN THE KITCHEN STORAGE AND DINING AREA.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- FOUND VENTS IN NEED OF CLEANING IN STUDENTS TOILET ROOMS. MUST CLEAN AND MAINTAIN CEILING VENTS.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- FOUND LOWER WALL BEAMS IN KITCHEN AREA CHIPPED/DAMAGED. INSTRUCTED TO FIX AND MAINTAIN.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
3 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- OBSERVED BENT FRONT WHEEL AT STEAM TABLE NEED TO REPLACE. ALSO BROKEN DINING TABLE IN BASEMENT LUNCH ROOM NEED TO REPLACE.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- CLEAN MICROWAVE AND FREEZER IN TEACHERS LOUNGE 1ST.FLOOR
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- CLEAN INSIDE LIGHT SHIELD 1ST. FLOOR GIRLS RESTROOM.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
1 infraction
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- The walls and ceilings shall be in good repair and easily cleaned.OBSERVED SEVERAL WATER DAMAGED CEILING TILES IN BASEMENT LUNCHROOM REAR BY WALK-IN FREEZER/STAIR WAY AND OBSERVED WALLS /PILLARS WITH PEELING PAINT INSTRUCTED TO REPLACE TILES AND REPAINT WALLS/ PILLARS.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- Canvass
1 infraction
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- All rooms in which food or drink is prepared, or in which utensils are washed, shall be lighted so that a minimum of 50-foot candles of light is available on all work surfaces. Shielding to protect against broken glass falling into food shall be provided for all artificial lighting sources in preparation, service, and display facilities. LIGHT SHEILDS NEEDED THROUGH OUT PREP AND EATING AREA. MUST PROPERLY SHEILD ALL LIGHTS WITH TUBES AND END CAPS. MUST CORRECT AND MAINTAIN.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- Canvass
5 infractions
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- INTERIOR OF UNUSED REACH-IN COOLER NOT CLEAN. CLEAN AND MAINTAIN SAME.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOOR TILES MISSING AT BASE OF STAIRS LEADING TO CAFETERIA CAUSING SOME STANDING WATER. REPLACE TILES.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- REPLACE MISSING CEILING TILE IN UTILITY CLOSET.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- LIGHT OUT IN UTILITY CLOSET. REPLACE SAME
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- REPLACE MISSING VENT COVER IN STAFF TOILET ROOM. BASE OF FAUCET AND SINK IN STAFF TOILET ROOM NOT CLEAN. CLEAN SAME AND MAINTAIN.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS