Skip to content
Loading map…

Coast Lethbridge Hotel & Conf Centre - Swimming Pool

526 Mayor Magrath Drive S Lethbridge AB T1J 3M2 · Aquatic Facility

Inspection summary

Coast Lethbridge Hotel & Conf Centre - Swimming Pool has been inspected 16 times by Alberta Health Services (Environmental Public Health) since January 15, 2024. The most recent inspection, on April 10, 2026, found no infractions.

3 of 16 inspections on record found no infractions at all. In the past 12 months there were 3 inspections with 1 infraction recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 14 times across 11 separate inspections, most recently on April 2, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 7 times across 7 separate inspections, most recently on December 9, 2024. For example: Is the chemical quality of the water in this pool satisfactory (Critical)?

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 5 times across 5 separate inspections, most recently on December 5, 2024. For example: Are proper testing, monitoring, and other records being properly maintained?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

16 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms were isolated in the sample collected March 31/26.Please shock the pool and submit a resample once complete.
  3. Monitoring Inspection

    0 infractions

  4. Risk Management Inspection

    0 infractions

  5. Risk Management Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms were present in the sample collected December 3.
  6. Monitoring Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms were present in the sample collected December 3.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH of the pool was 7.69. Please ensure that the pH is between 6.8 and 7.6.
  7. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms were present in the sample collected December 3.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 45 ppm. Please ensure that the alkalinity is maintained between 60-180 ppm at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The record keeping for the water chemistry requires improvement. The water is being tested almost every day; however, some of the pages with records on them are not dated, others have two dates on them with no indication which tests are for which days. Others show that the chlorine was measured to be 0 ppm but there is no indication of any response to this level. Please ensure proper daily records are kept and are organized.
  8. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 45 ppm. Please ensure that the alkalinity is maintained between 60-180 ppm at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The record keeping for the water chemistry requires improvement. The water is being tested almost every day; however, some of the pages with records on them are not dated, others have two dates on them with no indication which tests are for which days. Others show that the chlorine was measured to be 0 ppm but there is no indication of any response to this level. Please ensure proper daily records are kept and are organized.
  9. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms were isolated in the sample collected June 11. Please shock the pool and submit a resample once complete.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 45 ppm. Please ensure that the alkalinity is maintained between 60-180 ppm at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The record keeping for the water chemistry requires improvement. The water is being tested almost every day; however, some of the pages with records on them are not dated, others have two dates on them with no indication which tests are for which days. Others show that the chlorine was measured to be 0 ppm but there is no indication of any response to this level. Please ensure proper daily records are kept and are organized.
  10. Risk Management Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 45 ppm. Please ensure that the alkalinity is maintained between 60-180 ppm at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The record keeping for the water chemistry requires improvement. The water is being tested almost every day; however, some of the pages with records on them are not dated, others have two dates on them with no indication which tests are for which days. Others show that the chlorine was measured to be 0 ppm but there is no indication of any response to this level. Please ensure proper daily records are kept and are organized.
  11. Monitoring Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms were present in the sample collected May 21. Total coliforms present in the sample collected May 14. Note: no sample was collected the week of May 6.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured to be 45 ppm. Please ensure that the alkalinity is maintained between 60-180 ppm at all times.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The record keeping for the water chemistry requires improvement. The water is being tested almost every day; however, some of the pages with records on them are not dated, others have two dates on them with no indication which tests are for which days. Others show that the chlorine was measured to be 0 ppm but there is no indication of any response to this level. Please ensure proper daily records are kept and are organized.
  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms present in the sample collected May 14/23. Note: no sample was collected the week of May 6.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 130 for sample taken on May 2, 2024.
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 130 for sample taken on May 2, 2024.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The new Pool Operator has not yet completed his pool safety training.Operator indicated that this should be completed in March of this year.
  14. Risk Management Inspection

    1 infraction

    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The new Pool Operator has not yet completed his pool safety training.Operator indicated that this should be completed in March of this year.
  15. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • ProvLab results for the pool water sample collected on April 10 indicate a moderately high HPC (680 CFU/mL).
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The new Pool Operator has not yet completed his pool safety training.Operator indicated that this should be completed in March of this year.
  16. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH for the pool was a bit high. The operator adjusted the automated controller settings and will monitor the pH in the pool. Ensure that no patrons use the pool until the pH is back in the range of 6.8 - 7.6.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • The new Pool Operator has not yet completed his pool safety training.Operator indicated that this should be completed in March of this year.