Government Centre North Plaza - Reflecting Pool
9718 107 Street NW Edmonton AB T5K 1E4 · Aquatic Facility
20 inspections
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the microbiological water sample 26EN-188E01103 submitted on July 7, 2026, was unsatisfactory: HPC was 3740. This is a second consecutive unsatisfactory result.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the microbiological water sample 26EN-181E01267 submitted on June 30, 2026, was unsatisfactory: HPC was 170.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the microbiological water sample 26EN-181E01267 submitted on June 30, 2026, was unsatisfactory: HPC was 170.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 16 June 2026 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Actual FC reading on the controller was lower than manual test. Operator recalibrated the controller to align with manual testing.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 13 May 2026 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 13 May 2026 was unsatisfactory: HPC 2250 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Main drains in basin were missing a screw and some of the screws/hardware were not fully secured in place. Since further investigation is ongoing to identify water loss main drain covers will likely be removed. Ensure the main drains are fully secured and all hardware is installed as per manufactures instructions.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample result submitted on 20/08/2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample result submitted on 23-07-2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 2 June 2025 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 11 June 2025 was unsatisfactory: Total Coliform present. Pool operator had raised the free chlorine to 10ppm overnight. Water sample was taken onsite and will be submitted to the lab for analysis.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 4 June 2025 was unsatisfactory: HPC 660 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Circulation pump systems have been turning off overnight due to BMS programing and scheduling. Pool must remain operational at all times. Ensure BMS system programing is adjusted.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 4 June 2025 was unsatisfactory: HPC 660 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 24EN-206E01241 submitted on July 24, 2024, was unsatisfactory: HPC 580.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 10 July 2024 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Operator confirmed the pumps were tripping due to debris build up in the strainer baskets leading to the system shutting off. They have adjusted the controller and checks on the system.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Initial Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Microbiological water sample submitted on 12 June 2024 had 320 CFU/mL HPC. Additional microbiological water samples taken onsite from 2 locations (east and west). Awaiting results.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Chemical controller readings for pH and free chlorine were not consistent with manual readings. Commissioning agent from AME Group adjusted the controller and corrected the readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Spill over into the gutters was not consistent throughout the perimeter of the basin. Operation team advised to adjust and optimize overflow skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?