- Routine Inspection
4 infractions
- All components of the filtration, recirculation, and chemical feed systems are in continuous operation and maintained in proper working order.
- Ensure a volume of water not less than three times the total capacity of the pool is filtered, disinfected and passed through the pool each day.
- Ensure Oxidation Reduction Potential (ORP) value is not less than 600 mV and not greater than 900 mV.
- Daily records complete, signed and maintained.
- Ensure emergency phone is tested before the pool is opened each day. Record time of day emergency phone is tested and name of person performing the test.
- Ensure ground fault detector is activated during the daily use period.
- Record total number of bathers admitted to facility each day.
- Other records complete, signed and maintained.
- Ensure water outlet cover inspections are recorded at least once every 30 operating days including the time of day the test was completed and by whom.
- Ensure test buttons associated with the ground current leakage detecting and de-energizing devices are tested either monthly or according to manufacturer's instructions, whichever is more frequent.
- Ensure if an emergency stop button is available, it is labeled and tested and recorded at least once within each period of 30 operating days along with the time of day the test was completed and by whom.
- Safety equipment available, in good repair, and conveniently located for emergency use.
- Provide two buoyant throwing aids with rope (6mm in diameter, 1/2 width of pool plus 3m) are provided.
- All components of the filtration, recirculation, and chemical feed systems are in continuous operation and maintained in proper working order.
- Routine Inspection
3 infractions
- Daily records complete, signed and maintained.
- Record reading of the make-up water meter.
- Ensure emergency phone is tested before the pool is opened each day. Record time of day emergency phone is tested and name of person performing the test.
- Ensure ground fault detector is activated during the daily use period.
- Record total number of bathers admitted to facility each day.
- Other records complete, signed and maintained.
- Ensure water outlet cover inspections are recorded at least once every 30 operating days including the time of day the test was completed and by whom.
- Ensure test buttons associated with the ground current leakage detecting and de-energizing devices are tested either monthly or according to manufacturer's instructions, whichever is more frequent.
- Ensure if an emergency stop button is available, it is labeled and tested and recorded at least once within each period of 30 operating days along with the time of day the test was completed and by whom.
- Safety equipment available, in good repair, and conveniently located for emergency use.
- Daily records complete, signed and maintained.
- Routine Inspection
2 infractions
- Ladders and diving board/ platform are secure and have non-slip surface finish.
- Secure diving board/ladders.
- Safety equipment available, in good repair, and conveniently located for emergency use.
- Ensure all safety equipment is maintained in good repair.
- Ladders and diving board/ platform are secure and have non-slip surface finish.
- Routine Inspection
1 infraction
- Emergency telephone is present, functioning and accessible no farther than 30 metres from the pool.
- Routine Inspection
0 infractions
- Routine Inspection
3 infractions
- Exposed piping within pool enclosure/equipment room is properly colour-coded.
- Ensure exposed piping is colour-coded with bands at least 25mm wide, at intervals no greater than 1.2 m (chlorine - yellow, potable water - green).
- Accurate and functioning make-up water meter present.
- Ensure minimum 15L/bather of make-up water is added to the pool daily.
- Daily records completed, signed and maintained.
- Record reading of the make-up water meter.
- Ensure ground fault detector is activated during the daily use period.
- Exposed piping within pool enclosure/equipment room is properly colour-coded.
- Routine Inspection
2 infractions
- Exposed piping within pool enclosure/equipment room is properly colour-coded.
- Ensure exposed piping is colour-coded with bands at least 25mm wide, at intervals no greater than 1.2 m (chlorine - yellow, potable water - green).
- Safety equipment available and in good repair.
- Ensure all safety equipment is maintained in good repair.
- Exposed piping within pool enclosure/equipment room is properly colour-coded.
- Routine Inspection
2 infractions
- Exposed piping within pool enclosure/equipment room is properly colour-coded.
- Ensure exposed piping is colour-coded with bands at least 25mm wide, at intervals no greater than 1.2 m (chlorine - yellow, potable water - green).
- Total alkalinity between 80mg/L (80ppm) and 120mg/L (120ppm).
- Maintain total alkalinity between 80mg/L (80ppm) - 120mg/L (120ppm).
- Exposed piping within pool enclosure/equipment room is properly colour-coded.
- Routine Inspection
1 infraction
- Safety equipment available and in good repair.
- Ensure all safety equipment is maintained in good repair.
- Safety equipment available and in good repair.
- Routine Inspection
0 infractions
- Routine Inspection
1 infraction
- Other records signed and completed.
- Ensure water outlet cover inspections are recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Ensure ground fault detector is tested either monthly or according to the manufacturer’s instructions, whichever is more frequent.
- Ensure if an emergency stop button is available it is labeled and tested and recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Other records signed and completed.
- Routine Inspection
1 infraction
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Ensure operator is designated and trained,
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Re-inspection
2 infractions
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Total alkalinity between 80mg/L (80ppm) and 120mg/L (120ppm).
- Maintain total alkalinity between 80mg/L (80ppm) - 120mg/L (120ppm).
- Re-inspection
3 infractions
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Ensure operator is designated and trained,
- Water clarity satisfactory/black disc clearly visible 9m away.
- This condition is a health hazard because a bather in difficulty under the water surface cannot be readily seen.
- Ensure black disc is clearly visible 9 m away.
- Daily records completed, signed and maintained.
- Record type and amount of chemicals added manually.
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Routine Inspection
10 infractions
- Water facility inaccessible when closed.
- Ensure there is no access to water facility when closed.
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Ensure operator is designated and trained,
- Pool, deck, equipment, sanitary facility and adjoining areas kept in a safe and sanitary manner and free from hazards.
- Water clarity satisfactory/black disc clearly visible 9m away.
- This condition is a health hazard because a bather in difficulty under the water surface cannot be readily seen.
- Ensure black disc is clearly visible 9 m away.
- Ladders and diving board/ platform are secure and have non-slip surface finish.
- Total alkalinity between 80mg/L (80ppm) and 120mg/L (120ppm).
- Maintain total alkalinity between 80mg/L (80ppm) - 120mg/L (120ppm).
- Manual chemical testing in compliance.
- Daily records completed, signed and maintained.
- Complete and sign records daily.
- Record any emergencies, rescues, or breakdown of equipment that have occurred.
- Automatic sensing device- record clarity of pool ½ hour before opening & every 4 hours while open.
- Record reading of the make-up water meter.
- Record time of day for testing of emergency telephone.
- Record total number of bathers admitted to facility each day.
- Record type and amount of chemicals added manually.
- Other records signed and completed.
- Ensure water outlet cover inspections are recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Ensure ground fault detector is tested either monthly or according to the manufacturer’s instructions, whichever is more frequent.
- Ensure if an emergency stop button is available it is labeled and tested and recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Outlet covers are secure and inspected at least once every 30 operating days.
- Water facility inaccessible when closed.
- Routine Inspection
8 infractions
- Pool operator designated and trained in public pool operation, maintenance, filtration systems, water chemistry and all relevant safety ad emergency procedures.
- Ladders and diving board/ platform are secure and have non-slip surface finish.
- Sufficient supply and storage of chemicals and testing devices.
- Ensure safe storage and handling of all chemicals with operator access only.
- Total alkalinity between 80mg/L (80ppm) and 120mg/L (120ppm).
- Manual chemical testing in compliance.
- Automatic Sensing Device - Ensure pH, alkalinity, Free Available Chlorine, total chlorine or bromine residuals and water clarity are tested manually one half hour before bathers are admitted, and checked at least every 4 hours during the operating day.
- Daily records completed, signed and maintained.
- Record any emergencies, rescues, or breakdown of equipment that have occurred.
- Record time of day for testing of emergency telephone.
- Record total number of bathers admitted to facility each day.
- Other records signed and completed.
- Ensure water outlet cover inspections are recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Ensure ground fault detector is tested either monthly or according to the manufacturer’s instructions, whichever is more frequent.
- Ensure if an emergency stop button is available it is labeled and tested and recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Outlet covers are secure and inspected at least once every 30 operating days.
- Ensure water outlet covers are inspected and secure at least once every 30 operating days.
- Routine Inspection
2 infractions
- Emergency telephone is present and operational.
- Provide fully supplied first aid kit.
- Provide a first-aid box with at least one roll-up splint.
- Routine Inspection
5 infractions
- Ladders and diving board/ platform are secure and have non-slip surface finish.
- Secure diving board/ladders.
- Daily records completed, signed and maintained.
- Other records signed and completed.
- Ensure water outlet cover inspections are recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Ensure ground fault detector is tested either monthly or according to the manufacturer’s instructions, whichever is more frequent.
- Ensure if an emergency stop button is available it is labeled and tested and recorded at least once every 30 operating days along with time of day the test was completed and by whom.
- Outlet covers are secure and inspected at least once every 30 operating days.
- Ensure water outlet covers are inspected and secure at least once every 30 operating days.
- Provide fully supplied first aid kit.
- Ladders and diving board/ platform are secure and have non-slip surface finish.
- Routine Inspection
0 infractions
- Routine Inspection
0 infractions