Jayman BUILT Aquatic Centre - Leisure Pool & Waterslides

Common - 800 Griffin Road E Cochrane AB T4C 2B8 · Aquatic Facility

11 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • High Heterotrophic Plate Count (HPC) noted with sample result showing 290 CFU/mL. Follow treatment procedures provided by district PHI. Ensure that water chemistry balance is maintained to meet health requirements.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Written document / instruction of chlorine dioxide use was not available onsite during the inspection. Please send a copy of the document for review and make sure copy of the document is available onsite.
  3. Demand Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Written document / instruction of chlorine dioxide use was not available onsite during the inspection. Please send a copy of the document for review and make sure copy of the document is available onsite.
  4. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • *Written document / instruction of chlorine dioxide use was not available onsite during the inspection. Please send a copy of the document for review and make sure copy of the document is available onsite.
  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water report for the sample from Aug. 18 was unsatisfactory. HPC>57,000 CFU/ml.
  6. Monitoring Inspection

    0 infractions

  7. Demand Inspection

    0 infractions

  8. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity was measured at 0ppm and operator measured at 48 ppm. Due to lot of water fixtures and waves total alkalinity got affected. Low alkalinity was also causing fluctuation of PH, and also wrong Ph value cause adjustment of PH on ORP. Please make sure investigate the ways how to maintain total alkalinity at required ranges. You could consult with a pool company about the issue with total alkalinity.This seems from the record and previous inspections occurring frequently/ and outstanding deficiency.
  9. Demand Inspection

    0 infractions

  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample from Dec. 4 was not processed by the lab. Sample bottle leaked into the transit.
  11. Risk Management Inspection

    0 infractions