Jolly Roger Inn & Resort - Indoor Pool
1 J.R. Ln Seguin ON P2A 2W8 · Indoor - Swimming Pool
12 inspections
- Re-inspection
0 infractions
- Re-inspection
3 infractions
- pH is within range of 7.2 to 7.8
- CLOSE POOL
- Fail to maintain pH within acceptable range
- Proper test kit is available for use to determine water chemistry (no dip and read strips)
- Fail to provide proper test kit to determine water chemistry
- Total alkalinity within range of 60-180 ppm
- Fail to maintain total alkalinity within range of 60-180 ppm
- pH is within range of 7.2 to 7.8
- Compliance (Required)
5 infractions
- Emergency telephone is present and operational
- Fail to ensure telephone is operational
- Proper test kit is available for use to determine water chemistry (no dip and read strips)
- Fail to provide proper test kit to determine water chemistry
- Provide proper test kit to determine water chemistry
- Safe storage, handling and sufficient supply of all chemicals
- Fail to maintain safe storage and handling of all chemicals
- Fail to provide a sufficient supply chemicals
- Free available chlorine (FAC) within range of 0.5-10 ppm (5-10 ppm if water temperature =>35°C or if pool is a cold plunge or flotation pool)
- Fail to maintain FAC within range of 0.5 – 10 ppm
- Ensure FAC is maintained within range of 0.5 – 10 ppm
- Total alkalinity within range of 60-180 ppm
- Fail to maintain total alkalinity within range of 60-180 ppm
- Ensure total alkalinity within range of 60-180 ppm
- Emergency telephone is present and operational
- Compliance (Required)
0 infractions
- Compliance (Required)
1 infraction
- Public pool has a designated operator who is trained
- Fail to ensure designated operator is trained
- Public pool has a designated operator who is trained
- Compliance (Required)
0 infractions
- Re-inspection
1 infraction
- Oxidation Reduction Potential (ORP) within range of 600-900 mV (if equipped with automatic sensing device)
- Fail to maintain ORP with range of 600-900 mV
- Oxidation Reduction Potential (ORP) within range of 600-900 mV (if equipped with automatic sensing device)
- Re-inspection
4 infractions
- pH is within range of 7.2 to 7.8
- Fail to maintain pH within acceptable range
- Free available chlorine (FAC) within range of 0.5 – 10 ppm
- Fail to maintain FAC within range of 0.5 – 10 ppm
- Oxidation Reduction Potential (ORP) within range of 600-900 mV (if equipped with automatic sensing device)
- Fail to maintain ORP with range of 600-900 mV
- Water clarity satisfactory
- CLOSE POOL
- pH is within range of 7.2 to 7.8
- Compliance (Required)
2 infractions
- Total alkalinity within range of 80-120 ppm
- Fail to maintain total alkalinity within range of 80-120 ppm
- Oxidation Reduction Potential (ORP) within range of 600-900 mV (if equipped with automatic sensing device)
- Total alkalinity within range of 80-120 ppm
- Compliance (Required)
0 infractions
- Compliance (Required)
2 infractions
- Minimum amount of make-up water added daily
- Fail to ensure make-up water (minimum 15 L/bather) is added to the pool daily
- Ensure minimum make-up water of 15L/bather is added to the pool daily
- Daily records completed, signed and available for viewing
- Fail to record reading of the make-up water meter
- Minimum amount of make-up water added daily
- Compliance (Required)
1 infraction
- Depth markings present in appropriate locations (for all pools and spas > 3 m in horizontal dimension)
- Fail to ensure markings are printed in figures not less than 100 mm high
- Ensure markings are printed in figures not less than 100 mm high
- Ensure markings are indicated at the appropriate locations
- Depth markings present in appropriate locations (for all pools and spas > 3 m in horizontal dimension)