- Risk Management Inspection
0 infractions
- Monitoring Inspection
2 infractions
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The automated controller was not able to feed sufficient chlorine; thus the operator was adding chlorine manually to the water, which is not allowed. Ensure the pool is closed until automated controller is repaired and a satisfactory water result is achieved.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There are missing information on the anti-entrapment plan. Please complete.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- TA = 88 ppmFAC = 3.13 ppmpH = 8.09, not in compliance, please adjust to 6.8 - 7.6CC = 0.15 ppm
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample collected on June 10, 2025:Pseudomonas aeruginosa ISOLATED
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on June 10, 2025:HPC >57,000 CFU/mL
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Sample collected on May 06, 2025:TC absentP. aeruginosa ISOLATEDPool manager was called and informed to close the hot tub, do the treatment, and resample next week. Treatment procedure was emailed to the pool manager.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on May 06, 2025:HPC 300 CFU/mL
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Risk Management Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water sample received.Pseudomonas - ISOLATEDACTION: Please treat for Pseudomonas as outlined in the document below. Resample after treatment.https://www.albertahealthservices.ca/assets/wf/eph/wf-eh-pseudomona-in-hot-tubs.pdf
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- PH=7.96, please adjust to 6.8-7.6
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover=23.7min, please adjust flow rate to allow for a ≤ 20min turnover.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water sample received.Pseudomonas - ISOLATEDACTION: Please treat for Pseudomonas as outlined in the document below. Resample after treatment.https://www.albertahealthservices.ca/assets/wf/eph/wf-eh-pseudomona-in-hot-tubs.pdf
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- PH=7.96, please adjust to 6.8-7.6
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover=23.7min, please adjust flow rate to allow for a ≤ 20min turnover.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- PH=7.96, please adjust to 6.8-7.6
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover=23.7min, please adjust flow rate to allow for a ≤ 20min turnover.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The anti-entrapment plan was not complete. Please see the attached anti-entrapment document and complete the missing information.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Demand Inspection