Mariner's Village - Indoor Pool

11391 Seventh Ave, Richmond BC V7E 4J4 · Pool

Inspection summary

Mariner's Village - Indoor Pool has been inspected 37 times by Vancouver Coastal Health since July 20, 2015. The most recent inspection, on March 12, 2026, recorded 3 infractions.

10 of 37 inspections on record found no infractions at all. In the past 12 months there was 1 inspection with 3 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 44 times across 24 separate inspections, most recently on March 12, 2026. For example: The pool alkalinity is properly maintained

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 4 times across 4 separate inspections, most recently on June 22, 2023. For example: Chemicals are stored in a safe manner and location

  • Equipment and utensilsLower risk

    Pumps, filters, chemical feeders and safety equipment such as lifebuoys, reaching poles and first-aid kits must be present and working. Missing safety equipment can matter a great deal in an emergency.

    Recorded 10 times across 10 separate inspections, most recently on March 12, 2026. For example: Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications

About this data

These results come from Vancouver Coastal Health, which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

37 inspections

  1. Routine

    3 infractions

    • The pool alkalinity is properly maintained
      • Total Alkalinity is too low and is not at a level to maintain chemically balanced pool water.
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
    • Daily pool records are adequately maintained and available on site
      • Results of water testing are inadequately recorded.
  2. Routine Follow-up

    0 infractions

  3. Routine

    2 infractions

    • The operator maintains the pool in good repair.
      • Handrails at steps, ladders and diving boards are not secure.
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • The pool chemical test kit is absent/not in good condition and/or cannot produce accurate readings for required chemical parameters.
  4. Routine

    2 infractions

    • The operator maintains the pool in good repair.
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  5. Routine

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Floating weir and/or skimmer basket is missing from the skimmer box.
  6. Routine

    1 infraction

    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  7. Routine Follow-up

    1 infraction

    • Chemicals are stored in a safe manner and location
  8. Routine

    4 infractions

    • The pool disinfectant is properly maintained
      • Free available chlorine is less than 1.5 ppm at temperature above 30°C.
    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • Chemicals are stored in a safe manner and location
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • The pool chemical test kit is absent/not in good condition and/or cannot produce accurate readings for required chemical parameters.
  9. Routine Follow-up

    0 infractions

  10. Routine

    3 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
    • Daily pool records are adequately maintained and available on site
      • Results of water testing are inadequately recorded.
  11. Routine Follow-up

    0 infractions

  12. Routine

    1 infraction

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
  13. Routine

    4 infractions

    • The pool disinfectant is properly maintained
      • Free available chlorine is less than 1.5 ppm at temperature above 30°C.
    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • The operator maintains the pool in good repair.
      • Handrails at steps, ladders and diving boards are not secure.
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • Flow meter is not functioning correctly
  14. Routine Follow-up

    0 infractions

  15. Routine

    2 infractions

    • The pool disinfectant is properly maintained
      • Free available chlorine is less than 1.5 ppm at temperature above 30°C.
    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
  16. Routine

    0 infractions

  17. Routine Follow-up

    1 infraction

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
  18. Routine Follow-up

    1 infraction

    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
  19. Routine

    1 infraction

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
  20. Routine Follow-up

    0 infractions

  21. Routine

    2 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
  22. Routine Follow-up

    1 infraction

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
  23. Routine

    4 infractions

    • The pool pH level is properly maintained
    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Handrails at steps, ladders and diving boards are not secure
    • Adequate pool supervision and/or safety equipment is provided
      • Pool is not equipped with a reaching assist and/or the reaching assist is made of conducting materials (N/A for pools < 10m²)
    • Daily pool records are adequately maintained and available on site
      • Results of daily water testing are inadequately recorded: Free Available Chlorine, Combined Available Chlorine and pH are tested and recorded at least twice daily; Alkalinity and Cyanuric Acid are tested and recorded at least weekly.
  24. Routine

    4 infractions

    • Construction of the pool is in accordance with approved plans and specifications.
      • Construction or alterations has occurred without a construction permit.
    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Floating weir or skimmer basket is missing from the skimmer box.
  25. Routine Follow-up

    2 infractions

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Hot water provided in pool facilities is ≥ 49°C
  26. Routine Follow-up

    2 infractions

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Numerical depth of water in the pool is not clearly marked
      • Hot water provided in pool facilities is ≥ 49°C
  27. Routine

    4 infractions

    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Numerical depth of water in the pool is not clearly marked
      • Hot water provided in pool facilities is ≥ 49°C
    • Pool equipment is regularly tested for safety and maintained in accordance with the manufacturers' specifications
      • The pool chemical test kit is absent/not in good condition and/or cannot produce accurate readings for required chemical parameters.
      • A cross-connection control device is not present on the make-up water line
    • Daily pool records are adequately maintained and available on site
      • Results of daily water testing is inadequately recorded: Free Available Chlorine, Combined Available Chlorine and pH is tested and recorded at least twice daily; Alkalinity and Cyanuric Acid is tested and recorded at least weekly.
  28. Routine

    0 infractions

  29. Routine

    1 infraction

    • Daily pool records are adequately maintained and available on site
      • Results of daily water testing is inadequately recorded: Free Available Chlorine, Combined Available Chlorine and pH is tested and recorded at least twice daily; Alkalinity and Cyanuric Acid is tested and recorded at least weekly.
  30. Routine

    0 infractions

  31. Routine Follow-up

    2 infractions

    • Chemicals are stored in a safe manner and location
    • Daily pool records are adequately maintained and available on site
  32. Routine

    5 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool alkalinity is properly maintained
      • Alkalinity is not between 80 ppm and 120 ppm
    • The pool combined chlorine level is properly maintained
      • The pool combined chlorine level is greater than or equal to 1.0 ppm
    • Chemicals are stored in a safe manner and location
      • Chemicals are stored directly on the floor.
    • Daily pool records are adequately maintained and available on site
      • Results of daily water testing is inadequately recorded: Free Available Chlorine, Combined Available Chlorine and pH is tested and recorded at least twice daily; Alkalinity and Cyanuric Acid is tested and recorded at least weekly.
  33. Routine Follow-up

    1 infraction

    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Handrails at steps, ladders and diving boards are not secure
  34. Routine

    2 infractions

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8
    • The pool is regularly maintained and kept in good repair by an appropriately trained person
      • Handrails at steps, ladders and diving boards are not secure
  35. Routine

    0 infractions

  36. Routine Follow-up

    0 infractions

  37. Routine

    1 infraction

    • The pool pH level is properly maintained
      • pH level is not within 7.2 and 7.8