Skip to content
Loading map…

Melcor YMCA at Crowfoot - Women's Whirlpool

8100 John Laurie Boulevard NW Calgary AB T3G 3S3 · Aquatic Facility

13 inspections

  1. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
  2. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 02/04/2026, had a HPC of 150 CFU/ml.Treat and resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 20/03/2026 was rejected because there was no identification number on the bottle.Resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
  4. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 08/05/2025 had a heterotrophic plate count (HPC) of 210 CFU/mL.Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • There was no identification number on the bottle.Resample and ensure to affix the identification number on the requisition form to the bottle.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
  7. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Jan 16/25 indicated the presence of Total coliform.Treat and resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Jan 9/25 indicated the presence of Total coliform.Treat and resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • October 25, 2024 sample had TC present. Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
  10. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
  11. Monitoring Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WC-24-0008526Sample not processedSubmit a resample
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Repeated violation: Anti-entrapment plan not submitted for review.Complete and submit anti-entrapment plan for review.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan not submitted.Complete and submit anti-entrapment plan for review.
  12. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • WC-23-0077866TC Present Treat and resample
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Repeated violation: Anti-entrapment plan not submitted for review.Complete and submit anti-entrapment plan for review.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan not submitted.Complete and submit anti-entrapment plan for review.
  13. Demand Inspection

    3 infractions

    • 01. Is the pool in compliance with verbal and/or written approvals and/or orders issued by an Executive Officer, and is the Executive Officer not being obstructed or interfered with in the exercise of his/her powers?
      • Accession WC-23- 0061402Pseudomonas Isolated - spoke to Michael to treat and resample; He was going to refer to colleague Bharpu as Michael is off.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • **Repeated violation: Anti-entrapment plan not submitted for review.Complete and submit anti-entrapment plan for review.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment plan not submitted.Complete and submit anti-entrapment plan for review.