Melcor YMCA at Crowfoot - Women's Whirlpool
8100 John Laurie Boulevard NW Calgary AB T3G 3S3 · Aquatic Facility
13 inspections
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on 02/04/2026, had a HPC of 150 CFU/ml.Treat and resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on 20/03/2026 was rejected because there was no identification number on the bottle.Resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity measured 42 ppm. The aquatic coordinator measured it and recorded 30 ppm.Ensure the total alkalinity concentration is maintained between 60 to180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on 08/05/2025 had a heterotrophic plate count (HPC) of 210 CFU/mL.Treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- There was no identification number on the bottle.Resample and ensure to affix the identification number on the requisition form to the bottle.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on Jan 16/25 indicated the presence of Total coliform.Treat and resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on Jan 9/25 indicated the presence of Total coliform.Treat and resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- October 25, 2024 sample had TC present. Treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate of 25 minutes obtained from 8.79 Cubic meter basin. 90.7GPM flow rate recorded. Turn over rate must achieve under 20 minutes for a basin over 4 cubic meters.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- WC-24-0008526Sample not processedSubmit a resample
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **Repeated violation: Anti-entrapment plan not submitted for review.Complete and submit anti-entrapment plan for review.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan not submitted.Complete and submit anti-entrapment plan for review.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- WC-23-0077866TC Present Treat and resample
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **Repeated violation: Anti-entrapment plan not submitted for review.Complete and submit anti-entrapment plan for review.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan not submitted.Complete and submit anti-entrapment plan for review.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 01. Is the pool in compliance with verbal and/or written approvals and/or orders issued by an Executive Officer, and is the Executive Officer not being obstructed or interfered with in the exercise of his/her powers?
- Accession WC-23- 0061402Pseudomonas Isolated - spoke to Michael to treat and resample; He was going to refer to colleague Bharpu as Michael is off.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **Repeated violation: Anti-entrapment plan not submitted for review.Complete and submit anti-entrapment plan for review.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan not submitted.Complete and submit anti-entrapment plan for review.
- 01. Is the pool in compliance with verbal and/or written approvals and/or orders issued by an Executive Officer, and is the Executive Officer not being obstructed or interfered with in the exercise of his/her powers?