Pasteur
5825 S Kostner (4400W), CHICAGO, IL 60629 · School
22 inspections
- Canvass
1 infraction
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- OBSERVED PLASTIC COATING ON SANITARY PRODUCT CONTAINERS IN RESTROOMS. INSTRUCTED PERSON IN CHARGE TO REMOVE PLASTIC AND MAINTAIN STAINLESS STEEL BOX SMOOTH AND EASILY CLEANABLE.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- Canvass Re-Inspection
0 infractions
- Canvass
1 infraction
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- NO HOT RUNNING WATER AT HANDWASH SINKS IN BOYS AND GIRLS 1ST AND 2ND FLOOR TOILET ROOMS (MAIN BUILDING SOUTH END), TEMPERATURES RANGING FROM 58.0F-64.0F. INSTD TO HAVE AT 100F-120F AT ALL TIMES. PRIORITY VIOLATION 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
0 infractions
- Canvass
4 infractions
- 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
- MISSING SUPPLIES AND PROCEDURE FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS. INSTD TO PROVIDE PROCEDURE AND SUPPLIES (INCLUDING SANITIZER EFFECTIVE AGAINST NOROVIRUS) AND MAINTAIN ON SITE AT ALL TIMES. PRIORITY FOUNDATION 7-38-005
- 22. PROPER COLD HOLDING TEMPERATURES
- OBSERVED CONTAINERS OF MILK AT IMPROPER COLD HOLDING TEMPERATURES RANGING FROM 50.2F-51.2F IN 2-DOOR REFRIGERATION UNIT AT SERVING LINE. ALL MILK DISCARDED AND DENATURED AT THIS TIME. INSTD TO MAINTAIN COLD FOODS AT 41F OR BELOW AT ALL TIMES. PRIORITY VIOLATION 7-38-005. APPROX 20LBS $50 VALUE
- 33. PROPER COOLING METHODS USED; ADEQUATE EQUIPMENT FOR TEMPERATURE CONTROL
- 2-DOOR REFRIGERATION UNIT IN USE AT SERVICE LINE AT IMPROPER TEMPERATURE OF 49.0F. 2 DOOR REFRIGERATION UNIT IN PREP AREA AT IMPROPER TEMPERATURE OF 50.9F. BOTH UNITS TAGGED AND HELD FOR INSPECTION AT THIS TIME. INSTD NOT TO USE UNTIL REPAIRED AND REINSPECTED BY CDPH. PRIORITY VIOLATION 7-38-005
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OVER 50 MICE DROPPINGS SCATTERED ALONG WALL BASE AND BEHIND ROLLING CARTS IN DRY FOOD STORAGE ROOM AND NEXT TO LOCKERS IN REAR. INSTD TO REMOVE ALL DROPPINGS, CLEAN AND SANITIZE AFFECTED AREAS AND CONTACT PEST CONTROL FOR SERVICE. PRIORITY FOUNDATION 7-38-020(A)
- 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
- Canvass Re-Inspection
1 infraction
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- PREVIOUS PRIORITY FOUNDATION FROM 1/26/23 REPORT 2570372 NOT CORRECTED. OBSERVED FOOD HANDLERS WITH MULTIPLE TRAYS OF COOKED PIZZA AND BROCCOLI TO BE HANDLED, PRE PORTIONED, PLATED AND SERVED TO STUDENTS IN HALLWAY OF ANNEX. PREMISES SETS UP TABLE IN HALLWAY OF ANNEX BUILDING DAILY TO USE AS A SERVING LINE, HANDLING OPEN FOODS AND PLATING MEALS FOR STUDENTS WHO EAT IN CLASSROOMS. NO HANDWASH SINK LOCATED IN THIS AREA. INSTD TO PROVIDE HANDWASH SINK UNDER CITY PLUMBING IN SAME AREA OR PROVIDE ONLY PRE PACKAGED MEALS, OR HAVE STUDENTS OBTAIN MEALS AT SERVICE LINES IN LUNCHROOM IN MAIN BUILDING . A HANDWASH SINK IS REQUIRED IN ANY AREA HANDLING OPEN FOODS, MULTI USE EQUIPMENT, ETC. DURING INSPECTION, PERSON IN CHARGE CONTACTED AREA MGR TO DISCUSS AND CORRECT VIOLATION. TABLE, PLATES, AND TRAYS WERE RETURNED TO MAIN PREP AREA. OBSERVED FOOD HANDLERS PRE PORTIONING, WRAPPING TO GIVE TO PRE- K STUDENTS IN ANNEX BUILDING AND REMAINING ANNEX STUDENTS BEING SERVED AND EATING IN CAFETERIA IN MAIN BUILDING. PRIORITY VIOLATION 7-42-090
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- Canvass
1 infraction
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- PREMISES SETS UP TABLE IN HALLWAY OF ANNEX BUILDING DAILY TO USE AS A SERVING LINE, HANDLING OPEN FOODS AND PLATING MEALS FOR STUDENTS WHO EAT IN CLASSROOMS. OBSERVED HOT HOLDING UNIT AND PLATES IN SAME AREA. NO HANDWASH SINK LOCATED IN THIS AREA. INSTD TO PROVIDE HANDWASH SINK UNDER CITY PLUMBING IN SAME AREA OR PROVIDE ONLY PRE PACKAGED MEALS, OR HAVE STUDENTS OBTAIN MEALS AT SERVICE LINES IN LUNCHROOM IN MAIN BUILDING . A HANDWASH SINK IS REQUIRED IN ANY AREA HANDLING OPEN FOODS, MULTI USE EQUIPMENT, ETC. PRIORITY FOUNDATION VIOLATION 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
1 infraction
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LOOSE FAUCET ON HAND WASHING SINK IN BOYS ANNEX WASHROOM AND LEAKING FAUCET ON HAND WASHING SINK IN MODULAR 403. INSTRUCTED MANAGER TO REPAIR.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- Canvass
4 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER AT HAND WASHING SINKS IN FIRST FLOOR GIRLS NORTH WASHOOM (89.1F), FIRST FLOOR BOYS NORTH WASHROOM (67.1F), AND SECOND FLOOR BOYS NORTH WASHROOM (90.3F). INSTRUCTED MANAGER TO PROVIDE 100-120F WATER AT ALL HAND WASHING SINKS. PRIORITY 7-38-030
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OBSERVED 1/4" GAP ON BOTTOM RIGHT EXIT DOOR NEAR AUDITORIUM. INSTRUCTED MANAGER TO SEAL ALL OUTER OPENINGS ON DOOR TO PREVENT PEST ENTRY.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LOOSE FAUCET ON HAND WASHING SINK IN BOYS ANNEX WASHROOM AND LEAKING FAUCET ON HAND WASHING SINK IN MODULAR 403. INSTRUCTED MANAGER TO REPAIR.
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- OBSERVED NO COVERED WASTE RECEPTACLE IN GIRLS SECOND FLOOR WASHROOMS. INSTRUCTED MANAGER TO PROVIDE.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
1 infraction
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED LOWER WALLS IN POOR REPAIR BEHIND STORAGE UNIT. INSTRUCTED TO REPAIR.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- Canvass
3 infractions
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- WATER FOUNTAINS IN POOR REPAIR NORTH 2ND FLOOR. INSTD TO REPAIR AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- PEELING PAINT ON CEILING IN FLOOR IN 2ND FLOOR SOUTH BOY AND GIRL TOILET ROOMS. BROKEN, CRACKED FLOOR TILES IN 2ND FLOOR SOUTH BOYS TOILET ROOM. INSTD TO REPAIR AND MAINTAIN SAME.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- LIGHT OUT IN WALK IN FREEZER. INSTD TO PROVIDE LIGHT AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- Canvass
0 infractions
- Canvass
0 infractions
- Canvass
1 infraction
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- OBSERVED THE WALL AND LOCKER'S BETWEEN CLASS ROOM 118-120 PEELING PAINT, INSTRUCTED TO REMOVE AND RESEAL.MAIN BUILDING.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- Canvass
3 infractions
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOORS UNDER 3 COMPARTMENT SINK IN NEED OF TILES. MUST REPLACE. COVING IN NEED OF REPAIR. CORRECT AND MAINTAIN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- WALL AT OVEN AREA IN NEED OF REPAIR TO REPLACE MISSING TILES. MUST CORRECT AND MAINTAIN.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- GIRLS WASHROOM AT 1ST FLOOR 1 HANDBOWL NOT WORKING PROPERLY. MUST CORRECT. 2 OTHER HANDBOWLS AVAILABLE.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- Canvass
4 infractions
- 27. TOILET ROOMS ENCLOSED CLEAN, PROVIDED WITH HAND CLEANSER, SANITARY HAND DRYING DEVICES AND PROPER WASTE RECEPTACLES
- OBSERVED THE PAPER TOWEL DISPENSER STUCK NOT DESPENSING THE PAPER TOWEL IN THE MAIN 1ST. BOYS AND GIRLS REAT ROOMS, INSTRUCTED TO REPAIR. ENG. REPAIRED AFTER WALK-THRU OF SCHOOL.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- OBSERVED THE COOLER, AND MICROWAVE IN THE TEACHERS LOUNGE NOT CLEAN, INSTRUCTED TO CLEAN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- OBSERVED THE ANNEX REST ROOMS BOYS, AND GIRLS CEILING LIGHT SHIELDS NOT CLEAN,INSTRUCTED TO CLEAN. OBSERVED HOLES IN THE MAIN SCHOOL 1ST FLOOR WALL WHERE GATE WAS TAKEN OFF, INSTRUCTED TO FILL HOLES AND REPAIR WALL.
- 37. TOILET ROOM DOORS SELF CLOSING: DRESSING ROOMS WITH LOCKERS PROVIDED: COMPLETE SEPARATION FROM LIVING/SLEEPING QUARTERS
- OBSERVED THE PRE-K TOILET ROOM EXHAUST FAN NOT PROPERLY WORKING, AND THE 2ND GRADE TOILET ROOM EXHAUST FAN MISSING, IN MOBIL UNIT 401/402, INSTRUCTED TO REPAIR AND REPLACE MISSING FAN.
- 27. TOILET ROOMS ENCLOSED CLEAN, PROVIDED WITH HAND CLEANSER, SANITARY HAND DRYING DEVICES AND PROPER WASTE RECEPTACLES
- Canvass
3 infractions
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- OBSERVED THE TEACHERS LOUNGE FREEZER NOT CLEAN, INSTRUCTED TO CLEAN.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOOR IN BOYS RESTROOM 1ST. FLOOR HAS A FOUL ODOR, INSTRUCTED TO CLEAN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- OBSERVED TOILET PAPER ON THE CEILING OF THE GIRLS RESTROOM 1ST. FLOOR, INSTRUCTED TO REMOVE.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- Canvass Re-Inspection
1 infraction
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- LUNCHROOM STAFF TOILET ROOM COLD WATER FAUCET IN POOR REPAIR. INSTD TO REPAIR SAME TO PROVIDE ADEQUATE WATER SUPPLY WITHOUT CONSTANT PRESSURE OF HAND ON FAUCET
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Canvass
2 infractions
- 26. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, PROPERLY DESIGNED AND INSTALLED
- ALL TOILET ROOM FAUCETS IN MOBILE UNIT 403-404 (KDG) WITHOUT HOT RUNNING WATER UNDER CITY PRESSURE (TEMPERATURE OF WATER IS 43.3F) INSTD TO REPAIR SAME. ANNEX BUILDING STUDENTS TOILET ROOM (BOYS & GIRLS) SANITARY DRYING DEVICE (HAND DRYERS) IN POOR REPAIR. INSTD TO REPAIR SAME OR PROVIDE PAPER TOWELS AT ALL TIMES. CITATION ISSUED 7-38-030 SERIOUS.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- LUNCHROOM STAFF TOILET ROOM COLD WATER FAUCET IN POOR REPAIR. INSTD TO REPAIR SAME TO PROVIDE ADEQUATE WATER SUPPLY WITHOUT CONSTANT PRESSURE OF HAND ON FAUCET.
- 26. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, PROPERLY DESIGNED AND INSTALLED
- Canvass
1 infraction
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- FAUCET IN EMPLOYEE WASHROOM IN NEED OF ADJUSTING. WATER SLOW. MUST CORRECT AND MAINTAIN AT ALL TIMES.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Canvass
1 infraction
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline. Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. ONE URINAL IN POOR REPAIR IN BOYS ROOM ON 1ST FLOOR, ONE HANDWASH SINK IN NEED OF HOT WATER. MUST REPAIR AND MAINTAIN AT ALL TIMES.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Canvass
2 infractions
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.THE URINAL IN THE BOYS IST FLOOR TOILET ROOM IS BROKEN AND WON'T FLUSH PROPERLY. INETRUCTED TO REPAIR. TIGHTEN ALL THE TOILET SEATS THAT ARE LOOSE.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.SOME CLUTTER FOUND IN THE BASEMENT.INSTRUCTED TO CLEAN AND ORGNIZE SO NO INSECT OR RODENT HARBORAGE.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED