Red Earth Spa - Whirlpool

521 Banff Avenue Banff AB T1L 1H8 · Aquatic Facility

11 inspections

  1. Demand Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH initially too high at 7.8 as measured on AHS photometer. Records and automated controller indicate pH is set/been measured at 7.2. pH level measured at 7.5 by end of inspection (no additional chemical added, controller adjusted). Please continue to monitor that pH stays within range of 6.8 to 7.6 and that controller is reading accurately (recommend having third party testing of pH levels to confirm ColorQ on-site is reading accurately).
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • NOT observed on Dec.31/25: Flow meter for circulation flow after the filters was not working properly. Unable to determine an accurate flow reading for the system. - Please repair the flow meter.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Combined chlorine measured very high at approximately 2 to 3ppm. To avoid skin/eye/respiratory irritation, immediately reduce combined chlorine levels (plan to address by 12pm). Combined chlorine can be reduced by diluting/dumping water, doing a shock chlorination procedure, or using a non-chlorine shock product (note that if using non-chlorine products, there is potential for interference in regular chemical tests- additional reagents would be required to account for interference). Please have plan in place to address high combined chlorine levels in periods of high bather use.
  2. Demand Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter for circulation flow after the filters was not working properly. Unable to determine an accurate flow reading for the system. - Please repair the flow meter.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Written logs indicate that there have been several days where the pH was out of range (around 6.5). Likely staff adjusted but did not re-test and record the adjusted pH. - Please ensure that if an out-of-range reading is observed, chemistry is re-tested and new readings are recorded.
  3. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Monday November 24th, 2025, had Pseudomonas isolated. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter for circulation flow after the filters was not working properly. Unable to determine an accurate flow reading for the system. - Please repair the flow meter.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Written logs indicate that there have been several days where the pH was out of range (around 6.5). Likely staff adjusted but did not re-test and record the adjusted pH. - Please ensure that if an out-of-range reading is observed, chemistry is re-tested and new readings are recorded.
  4. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter for circulation flow after the filters was not working properly. Unable to determine an accurate flow reading for the system. - Please repair the flow meter.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Written logs indicate that there have been several days where the pH was out of range (around 6.5). Likely staff adjusted but did not re-test and record the adjusted pH. - Please ensure that if an out-of-range reading is observed, chemistry is re-tested and new readings are recorded.
  5. Risk Management Inspection

    0 infractions

  6. Monitoring Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow meter on the jet was not working properly, no reading was able to be obtained. - Please repair the flow meter to determine an accurate flow rate for the jets.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a missing tile on the staircase in the whirlpool. - Tiles to be replaced the next time the whirlpool is drained.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Sanitation plan onsite is incomplete. - Please update sanitation plan to include information about frequency of sanitation in the pool area.
  7. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was very low, was measured at around 50 ppm. - Raise the alkalinity level, ensure it is maintained between 60-180 ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a missing tile on the staircase in the whirlpool. - The tile will be replaced the next time the whirlpool is drained.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The sanitation plan and the safety and supervision plans could not be located onsite. - Ensure these plans are created/located and kept onsite in a location that is known to staff.
  8. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from May 21st was not processed due to missing an ID number on the bottle. - Operators were informed to submit a re-sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was very low, was measured at around 50 ppm. - Raise the alkalinity level, ensure it is maintained between 60-180 ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a missing tile on the staircase in the whirlpool. - The tile will be replaced the next time the whirlpool is drained.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The sanitation plan and the safety and supervision plans could not be located onsite. - Ensure these plans are created/located and kept onsite in a location that is known to staff.
  9. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was very low, was measured at around 50 ppm. - Raise the alkalinity level, ensure it is maintained between 60-180 ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a missing tile on the staircase in the whirlpool. - The tile will be replaced the next time the whirlpool is drained.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The sanitation plan and the safety and supervision plans could not be located onsite. - Ensure these plans are created/located and kept onsite in a location that is known to staff.
  10. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Feb. 20th, 2024 was not processed by the lab due to a missing ID number on the bottle. - Operators were informed to submit a re-sample on Thursday.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was very low, was measured at around 50 ppm. - Raise the alkalinity level, ensure it is maintained between 60-180 ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a missing tile on the staircase in the whirlpool. - The tile will be replaced the next time the whirlpool is drained.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The sanitation plan and the safety and supervision plans could not be located onsite. - Ensure these plans are created/located and kept onsite in a location that is known to staff.
  11. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity was very low, was measured at around 50 ppm. - Raise the alkalinity level, ensure it is maintained between 60-180 ppm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a missing tile on the staircase in the whirlpool. - The tile will be replaced the next time the whirlpool is drained.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The sanitation plan and the safety and supervision plans could not be located onsite. - Ensure these plans are created/located and kept onsite in a location that is known to staff.