SDWS - Minnehaha Camp Resort Drinking Water System - 747002574

120 Peninsula Rd Port Loring ON P0H 1Y0 · Small Drinking Water Systems - Regulation 319

Inspection summary

SDWS - Minnehaha Camp Resort Drinking Water System - 747002574 has been inspected 2 times by North Bay Parry Sound District Health Unit since August 9, 2023. The most recent inspection, on September 18, 2024, recorded 7 infractions.

None of the 2 inspections on record were free of infractions. No inspections are on record from the past 12 months. All recorded findings relate to upkeep, equipment or paperwork rather than water quality or direct safety risks.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 4 times across 2 separate inspections, most recently on September 18, 2024. For example: All reporting requirements for adverse test results/adverse observations complied with

  • Building, plumbing and upkeepLower risk

    Decks, ladders, fencing, drains, washrooms and signage must be in good repair. Damaged drain covers or broken fencing can be real safety hazards, while most other upkeep issues are lower risk.

    Recorded 2 times across 2 separate inspections, most recently on September 18, 2024. For example: System is maintained in good repair, in a safe and sanitary condition and is checked/operated/calibrated at required frequencies and in accordance with requirements under Regulation 319/08 and manufacturers instructions

  • Equipment and utensilsLower risk

    Pumps, filters, chemical feeders and safety equipment such as lifebuoys, reaching poles and first-aid kits must be present and working. Missing safety equipment can matter a great deal in an emergency.

    Recorded once on August 9, 2023. For example: Primary disinfection equipment that does not use chlorination has a functioning audible alarm or a feature that ensures no water is directed to users if the equipment malfunctions/loses power or ceases to provide the appropriate level of disinfection

  • Other findingsLower risk

    Findings that do not fit the categories above, such as follow-ups that confirm an earlier violation was corrected, or requirements specific to this type of facility.

    Recorded 4 times across 2 separate inspections, most recently on September 18, 2024. For example: All sampling, testing and monitoring requirements under Regulation 319/08 are complied with

About this data

These results come from North Bay Parry Sound District Health Unit, which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

2 inspections

  1. Compliance

    7 infractions

    • All reporting requirements for adverse test results/adverse observations complied with
      • Fail to give M.O.H. a written notice of adverse observation/test result within 24 hours
      • Fail to specify actions taken in response to adverse observation/test result
      • Owner/Operator must provide M.O.H. with a written notice within 24 hours
      • Owner/Operator to specify actions taken in response to adverse observation/test result
    • All required records are made and retained
      • Fail to keep water treatment/monitoring equipment maintenance records
      • Fail to record operational checks
      • Owner/Operator to keep water treatment/monitoring equipment maintenance records
      • Owner/Operator to record operational checks
    • System is maintained in good repair, in a safe and sanitary condition and is checked/operated/calibrated at required frequencies and in accordance with requirements under Regulation 319/08 and manufacturers instructions
      • Fail to maintain system and equipment in good repair and in a safe and sanitary condition
      • Owner/Operator to ensure the system and equipment are maintained in good repair and in a safe and sanitary condition
    • Medical Officer of Health (M.O.H.) notified of intent to supply water/ resume supply of water and notified of the identity of the licensed laboratory to be used by the operator for water testing
      • Fail to notify M.O.H. of proposed supply date prior to supplying water to users
      • Fail to ensure a test for E. coli and total coliforms is taken and tested and results submitted to the MOH before supplying water to users after any period of more than 60 days duration during which the system has not been supplying water to users.
      • Owner/operator to notify MOH before supplying water to users after construction, installation, alteration, or extension of the small drinking water system.
      • Owner/Operator to ensure a test for E. coli and total coliforms is taken and tested and results submitted to the MOH before supplying water to users after any period of more than 60 days duration during which the system has not been supplying water to users.
    • All sampling, testing and monitoring requirements under Regulation 319/08 are complied with
      • Fail to ensure microbiological (E. coli and total coliforms) sampling frequency and requirements are complied with
      • Owner/Operator to ensure microbiological (E. coli and total coliforms) sampling frequency and requirements are complied with
    • An operator has been designated and trained to safely operate the system
      • Fail to ensure operator trained as required in operation, maintenance, safety and emergency procedures
      • Owner to ensure operator trained as required by the M.O.H. in operation, maintenance, safety and emergency procedures
    • Appropriate corrective actions taken in response to adverse results
  2. Compliance

    4 infractions

    • An operator has been designated and trained to safely operate the system
      • Fail to ensure operator trained as required in operation, maintenance, safety and emergency procedures
      • Owner to ensure operator trained as required by the M.O.H. in operation, maintenance, safety and emergency procedures
    • Primary disinfection equipment that does not use chlorination has a functioning audible alarm or a feature that ensures no water is directed to users if the equipment malfunctions/loses power or ceases to provide the appropriate level of disinfection
      • Fail to ensure disinfection equipment designed and operated with required feature
      • Fail to ensure system designed and operated with required alarm
      • Fail to ensure audible alarm sounds at appropriate locations
      • Owner/Operator to ensure disinfection equipment designed and operated with required feature
      • Owner/Operator to ensure system designed and operated with required alarm
      • Owner/Operator to ensure audible alarm sounds at appropriate locations
    • System is maintained in good repair, in a safe and sanitary condition and is checked/operated/calibrated at required frequencies and in accordance with requirements under Regulation 319/08 and manufacturers instructions
      • Fail to ensure system operated in accordance with requirements under Regulation 319/08
      • Owner/Operator to ensure system operated in accordance with requirements under Regulation 319/08
    • All required records are made and retained
      • Fail to document required recordings of chlorine residuals
      • Owner/Operator to document required recordings of chlorine residuals