St. Viator

4140 W Addison ST, CHICAGO, IL 60641 · School

16 inspections

  1. Canvass

    0 infractions

  2. Canvass

    4 infractions

    • 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
      • OBSERVED TORN GASKET ON INTERIOR OF COOLER LOCATED IN KITCHEN CLOSER TO CABINETS. INSTRUCTED TO REPAIR OR REPLACE AND MAINTAIN IN GOOD CONDITION.
    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • OBSERVED NO BACKFLOW PREVENTION DEVICE CONNECTED TO UTILITY SINK LOCATED IN BOYS BATHROOM IN LIBRARY. INSTRUCTED TO INSTALL IN ACCORDANCE WITH ALL RELEVANT LAWS, RULES, AND REGULATIONS.
    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • OBSERVED LOW WATER PRESSURE AT WASHBOWL SINKS LOCATED IN TOILET ROOMS LOCATED IN LIBRARY AND NO HOT WATER IN TOILET ROOM LOCATED NEAR GYM. SEE COMMENTS. INSTRUCTED TO REPAIR OR REPLACE AND MAINTAIN IN GOOD CONDITION.
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • OBSERVED NO COVERED TRASH RECEPTACLE INSIDE FEMALE TOILET ROOM LOCATED IN LIBRARY. INSTRUCTED TO PROVIDE.
  3. Canvass

    0 infractions

  4. Canvass

    0 infractions

  5. Canvass

    1 infraction

    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • OBSERVED PEELING PAINT ON THE CEILING IN THE WOMENS TOILET ROOM, LOCATED ON THE FIRST FLOOR. INSTRUCTED TO REPAIR AND ENSURE THAT CEILING REMAINS SMOOTH AND EASILY CLEANABLE.
  6. Canvass

    4 infractions

    • 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
      • OBSERVED LOW COLD WATER PRESSURE AT HANDWASHING SINKS IN THIRD FLOOR MEN'S WASHROOM AND SECOND FLOOR WOMEN'S WASHROOM. MUST REPAIR AND INCREASE PRESSURE.
    • 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
      • OBSERVED NO COVERED WASTE BIN IN BASEMENT WOMEN'S WASHROOMS. MUST PROVIDE AND MAINTAIN.
    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • OBSERVED CHIPPED AND PEELING PAINT ON WOMEN'S THIRD FLOOR WASHROOM CEILING. MUST REPAIR AND MAINTAIN.
    • 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
      • OBSERVED ONE BURNED OUT LIGHTBULB IN TEACHER'S WASHROOM ON FIRST FLOOR. INSTRUCTED TO REPLACE AND MAINTAIN.
  7. Canvass Re-Inspection

    0 infractions

  8. Canvass

    4 infractions

    • 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
      • OBSERVED NO CLEAN UP PROCEDURE ON THE PREMISES FOR VOMIT AND DIARRHEAL EVENTS. MANAGEMENT INSTRUCTED TO PROVIDE A CLEAN UP PROCEDURE AND NECESSARY ITEMS ON THE PREMISES . PRIORITY FOUNDATION 7-38-005. NO CITATION ISSUED. -
    • 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
      • FOUND APPROXIMATELY 20 MICE DROPPINGS INSIDE CLUTTERED LOWER KITCHEN CABINETS AT NORTH-EAST CORNER.INSTRUCTED MANAGER TO DETAIL CLEAN AND SANITIZE ALL AFFECTED AREAS.REMOVE ALL UNNECESSARY ITEMS AND CLUTTER STORED IN NAMED AREAS.PEST CONTROL SERVICE IS NOW RECOMMENDED. PRIORITY FOUNDATION VIOLATION.7-38-020(a), CITATION ISSUED.
    • 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
      • INSTRUCTED TO DETAIL CLEAN AND SANITIZE INTERIORS ALL KITCHEN CABINETS/STORAGE AREAS AND TOPS OF COUNTERS ALONG THE NORTH EAST CORNER OF PREP AREA AND TO MAINTAIN.
    • 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
      • INSTRUCTED TO SEAL OPENING AROUND PLUMBING FIXTURE LOCATED AT EAST CORNER WALL OF THE PREP AREA MAINTENANCE IS AWARE.
  9. Canvass Re-Inspection

    1 infraction

    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • LEAKING ON THE COLD HANDLE OF THE FAUCET OF THE MOP SINK INSIDE THE BOY'S WASHROOM 3RD FLOOR. MUST REPAIR TO STOP TE LEAK.
  10. Canvass

    3 infractions

    • 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
      • NO LAST YEAR AND THIS YEAR INSPECTION REPORT FROM THE PEST CONTROL LOG BOOK (AEREX PEST CONTROL COMPANY). MUST PROVIDE LATEST INSPECTION REPORT. ALSO FRONT ENTRANCE DOOR AND EXIT DOOR BY THE BOILER ROOM WITH OVER 1/3 OF AN INCH GAP ON THE BOTTOM OF THHE DOOR. INSTRUCTED TO RODENT/INSECTS PROOFED THE DOOR. SERIOUS VIOLATION 7-38-020.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • GAP/HOLE ON THE WALL BASE INSIDE THE BOY'S WASHROOM 3RD FLOOR. MUST REPAIR AND MAINTAIN.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • LEAKING ON THE COLD HANDLE OF THE FAUCET OF THE MOP SINK INSIDE THE BOY'S WASHROOM 3RD FLOOR. MUST REPAIR TO STOP TE LEAK.
  11. Canvass

    3 infractions

    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • PEELING PAINT ON THE WALLS IN THE GIRL'S WASHROOM 2ND FLOOR. MUST SCRAPE PEELING PAINT AND RE PAINT.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • MUST INCREASE HOT AND COLD WATER PRESSURE OF THE BOY'S WASHBOWL FAUCET INSIDE THE WASHROOM 2ND FLOOR.
    • 42. APPROPRIATE METHOD OF HANDLING OF FOOD (ICE) HAIR RESTRAINTS AND CLEAN APPAREL WORN
      • EMPLOYEE PREPARING AND HANDLING FOODS IN THE PREP AREA MUST WEAR A HAIR RESTRAINT TO CONFINE THE HAIR.
  12. Canvass

    3 infractions

    • 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
      • OBSERVED FOOD DEBRIS IN MICROWAVE IN KITCHEN. INSTRUCTED TO CLEAN AND MAINTAIN.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • OBSERVED BROKEN URINAL IN BOYS' RESTROOM ON 3RD FLOOR. INSTRUCTED TO REPAIR AND MAINTAIN.
    • 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
      • OBSERVED BOTTLED WATER AND OTHER ITEMS ON FLOORS IN PRE-K CLASSROOMS. INSTRUCTED TO ELEVATE ALL ITEMS AT LEAST 6 INCHES OFF THE FLOOR SO THAT AREAS MAY BE PROPERLY CLEANED.
  13. Canvass

    1 infraction

    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • FLOOR UNDER THE HANDICAP RAMP IN THE LUNCH ROOM WITH DIRT AND DEBRIS. STAFF CLEANED DURING THE INSPECTION. DOOR SWEEP IN THE ENGINEERS TOOL ROOM ADJACENT FROM THE KITCHEN BROKEN/IN POOR REPAIR. MUST REPLACE/REPAIR.
  14. Canvass

    2 infractions

    • 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
      • INSTRUCTED TO DETAIL CLEAN AND MAINTAIN INTERIOR SURFACE OF MICROWAVE OVEN WITH EXCESSIVE DRIED FOOD SPILLAGE IN TEACHER'S LOUNGE (1ST FLOOR) TO PREVENT PEST HARBORAGE.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • NOTED CORNER CEILING IN POOR REPAIR WITH WATER DAMAGED INSIDE GIRLS WASHROOM 2ND FLOOR.
  15. Canvass

    2 infractions

    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • 3RD FLOOR GIRLS TOILET ROOM HAVE PEELING PAINT ON CIELING AND WALL. MUST SCRAPE AND PAINT.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • MOP SINK IN BOILER ROOM HAVE NO BACKFLOW PREVENTION DEVICE. MUST INSTALL BACKFLOW PREVENTION DEVICE. 1ST FLOOR GIRLS TOILET ROOM, 1ST TOILET STALL OUT OF ORDER. MUST REPAIR OR REPLACE TOILET.
  16. Canvass

    3 infractions

    • 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
      • Floor in boiler room along wallbase not cleaned. Instructed to detail clean.
    • 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
      • Ceiling and walls in cafeteria and hallway not maintained. Instructed to remove chipped paint, seal holes and gaps and repaint surface. Ventilation and light covers in prep area not cleaned. Instructed to detail clean.
    • 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
      • Faucet at two compartment sink leaking. Instructed to replace spout to prevent leak.