Tuscany Club - Spray Park

212 Tuscany Way NW Calgary AB T3L 2A7 · Aquatic Facility

11 inspections

  1. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flap on flow meter on recirculation system was maxed out. This does not give an accurate reading for the flow rate.-Change the flow meter so that the flap is within the range of the numbers
  2. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken May 28 - 1150 cfu/mL HPC-Resample
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FAC was measured to 0.05 ppm It is required that the spray park water be at 2 ppm minimum or at least 2ppm
    • 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
      • Some reagents used to test the pool chemistry are expired. Please replace.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Facility did not have a Pool permit posted or the facility could not locate the permit.Have the pool permit posted.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Information missing from record on chemical correction.Ensure that there is a record of what chemical is added to the water supply. No record of automated system reading Ensure have a copy of your daily automated reading.
  3. Demand Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • FAC was measured to 0.05 ppm It is required that the spray park water be at 2 ppm minimum or at least 2ppm
    • 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
      • Some reagents used to test the pool chemistry are expired. Please replace.
    • 11. Does the facility have a valid permit and does the facility operate in compliance with the conditions of that permit?
      • Facility did not have a Pool permit posted or the facility could not locate the permit.Have the pool permit posted.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Information missing from record on chemical correction.Ensure that there is a record of what chemical is added to the water supply. No record of automated system reading Ensure have a copy of your daily automated reading.
  4. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC count: 4740 CFU/mL.Sample collected by: Aju Paul-Treat the water and resample.
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample results:HPC count: 1260 CFU/mL.Sample collected by: Aju Paul-Treat the water and resample.
  7. Monitoring Inspection

    0 infractions

  8. Risk Management Inspection

    0 infractions

  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC present - resample to be submitted to the lab on Monday.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample received July 24 had HPC of 550 CFU/mL.
  10. Risk Management Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC present - resample to be submitted to the lab on Monday.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample received July 24 had HPC of 550 CFU/mL.
  11. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample received July 24 had HPC of 550 CFU/mL.