WM PENN ELEMENTARY SCHOOL
1616 S Avers, CHICAGO, IL 60623 · School
29 inspections
- Canvass Re-Inspection
2 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- 5-202.12 (B-D) OBSERVED TIMED FAUCETS NOT FUNCTIONING PROPERLY IN LOWER-LEVEL, FIRST, SECOND AND THIRD FLOOR GIRLS AND BOYS' WASHROOMS. WATER MUST RUN CONTINUOUSLY FOR AT LEAST 15 SECONDS BEFORE REACTIVATING FAUCET.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-501.11 OBSERVED DAMAGED FLOOR TILES THROUGHOUT KITCHEN NEAR REACH-IN COOLERS, FREEZERS, DRY STORAGE, PREP TABLES, OVEN, ETC. OBSERVED PEELING PAINT ON CEILING AND DUCT EQUIPMENT IN SERVING AREA. OBSERVED LOOSE AND DAMAGED BASEBOARDS ALONG WALLS AND DAMAGED WALL SURFACES IN PREP AREA. OBSERVED LEFT HANDWASHING SINK NOT SECURE TO WALL IN LOWER-LEVEL GIRLS' WASHROOM. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
5 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- 5-202.12 (B-D) OBSERVED TIMED FAUCETS NOT FUNCTIONING PROPERLY IN LOWER-LEVEL, FIRST, SECOND AND THIRD FLOOR GIRLS AND BOYS' WASHROOMS. WATER MUST RUN CONTINUOUSLY FOR AT LEAST 15 SECONDS BEFORE REACTIVATING FAUCET.
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- 5-501.17 OBSERVED NO COVERED RECEPTACLE IN LUNCHROOM STAFF AND TEACHER STAFF WASHROOMS. INSTRUCTED MANAGER TO PROVIDE COVERED RECEPTACLES IN ALL WOMEN AND UNISEX WASHROOMS.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-501.11 OBSERVED DAMAGED AND MISSING FLOOR TILES THROUGHOUT KITCHEN NEAR REACH-IN COOLERS, FREEZERS, DRY STORAGE, PREP TABLES, OVEN, ETC. OBSERVED PEELING PAINT ON CEILING AND DUCT EQUIPMENT IN SERVING AREA. OBSERVED LOOSE AND DAMAGED BASEBOARDS ALONG WALLS AND DAMAGED WALL SURFACES IN PREP AREA. OBSERVED LEFT HANDWASHING SINK NOT SECURE TO WALL IN LOWER-LEVEL GIRLS' WASHROOM. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- 6-303.11 OBSERVED NO LIGHT INSIDE WALK-IN COOLER AND WALK-IN FREEZER. INSTRUCTED MANAGER TO PROVIDE ADEQUATE LIGHTING INSIDE WALK-IN COOLER AND FREEZER.
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- 8-404.13 (B:3) PREVIOUS PRIORITY FOUNDATION NOT CORRECTED FROM REPORT #2631007 ON 2-9-26:60-PREVIOUS CORE VIOLATION NOT CORRECTED FROM REPORT #2611531 ON 2-3-25:55- OBSERVED CRUMBLED FLOOR IN PREP AREA IN FRONT OF 3-COMPARTMENT SINK AND FRONT OF WALK-IN FREEZER. INSTRUCTED TO PROVIDE SMOOTH AND EASILY CLEANABLE FLOORS AND MAINTAIN. PRIORITY 7-42-090
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
10 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HANDWASHING SIGNS AT HANDWASHING SINKS IN PREP AND SERVING AREAS. INSTRUCTED MANAGER TO PROVIDE HANDWASHING SIGNS AT ALL HANDWASHING SINKS USED BY EMPLOYEES.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER (75.9F-79.5F) AT HANDWASHING SINKS IN LOWER-LEVEL BOYS' AND GIRLS' WASHROOM. INSTRUCTED MANAGER TO PROVIDE HOT WATER ALL HANDWASHING SINKS. PRIORITY 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO SOAP AT HANDWASHING SINKS IN THIRD FLOOR BOYS' AND GIRLS' WASHROOMS. INSTRUCTED MANAGER TO PROVIDE SOAP AT ALL HANDWASHING SINKS FOR PROPER HANDWASHING. PRIORITY FOUNDATION 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED TIMED FAUCETS NOT FUNCTIONING PROPERLY IN LOWER-LEVEL, FIRST, SECOND AND THIRD FLOOR GIRLS AND BOYS' WASHROOMS. WATER MUST RUN CONTINUOUSLY FOR AT LEAST 15 SECONDS BEFORE REACTIVATING FAUCET.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKING HOT WATER FAUCET AT HANDWASHING SINK IN KITCHEN STAFF WASHROOM AND LEAKING FAUCET AT HANDWASHING SINK IN SERVING AREA. OBSERVED RIGHT FACUET NOT OPERABLE AT 3 FAUCET SINK IN GIRLS SECOND FLOOR WASHROOM. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- OBSERVED NO COVERED RECEPTACLE IN LUNCHROOM STAFF AND TEACHER STAFF WASHROOMS. INSTRUCTED MANAGER TO PROVIDE COVERED RECEPTACLES IN ALL WOMEN AND UNISEX WASHROOMS.
- 54. GARBAGE & REFUSE PROPERLY DISPOSED; FACILITIES MAINTAINED
- OBSERVED OUTSIDE GARBAGE AREA NOT MAINTAINED. DUMPSTERS OVERFLOWING WITH TRASH AND LIDS NOT TIGHT-FITTING. INSTRUCTED MANAGER TO CLEAN AND MAINTAIN OUTSIDE GARBAGE/DUMPSTER AREA. PRIORITY FOUNDATION 7-38-020(B)
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED DAMAGED AND MISSING FLOOR TILES THROUGHOUT KITCHEN NEAR REACH-IN COOLERS, FREEZERS, DRY STORAGE, PREP TABLES, OVEN, ETC. OBSERVED PEELING PAINT ON CEILING AND DUCT EQUIPMENT IN SERVING AREA.OBSERVED LOOSE AND DAMAGED BASEBOARDS ALONG WALLS AND DAMAGED WALL SURFACES IN PREP AREA. OBSERVED LEFT HANDWASHING SINK NOT SECURE TO WALL IN LOWER-LEVEL GIRLS' WASHROOM. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED NO LIGHT INSIDE WALK-IN COOLER AND WALK-IN FREEZER. INSTRUCTED MANAGER TO PROVIDE ADEQUATE LIGHTING INSIDE WALK-IN COOLER AND FREEZER.
- 60. PREVIOUS CORE VIOLATION CORRECTED
- PREVIOUS CORE VIOLATION NOT CORRECTED FROM REPORT #2611531 ON 2-3-25:55- OBSERVED CRUMBLED FLOOR IN PREP AREA IN FRONT OF 3-COMPARTMENT SINK AND FRONT OF WALK-IN FREEZER. INSTRUCTED TO PROVIDE SMOOTH AND EASILY CLEANABLE FLOORS AND MAINTAIN. PRIORITY FOUNDATION 7-42-090
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
3 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HAND DRYING PROVISION AVAILABLE AT HANDSINK LOCATED IN CAFETERIA SERVING AREA. INSTRUCTED TO PROVIDE AND MAINTAIN. PRIORITY FOUNDATION VIOLATION. #7-38-030 (C). NO CITATION ISSUED. MANAGER PROVIDED PAPERTOWELS.
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OBSERVED REAR EXIT DOOR IN PREP AREA PROPPED OPEN DURING TIME OF INSPECTION. INSTRUCTED TO CLOSE IN ORDER TO PREVENT PEST ENTRY.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED CRUMBLED FLOOR IN PREP AREA IN FRONT OF 3-COMPARTMENT SINK AND FRONT OF WALK-IN FREEZER. INSTRUCTED TO PROVIDE SMOOTH AND EASILY CLEANABLE FLOORS AND MAINTAIN.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
4 infractions
- 36. THERMOMETERS PROVIDED & ACCURATE
- 4-204.112(B) OBSERVED BROKEN THERMOMETER ON MILK COOLER IN SERVING AREA. INSTRUCTED TO REPLACE THERMOMETER.NOTED MILK STORED INSIDE @ 35 DURING THIS TIME.
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- 6-202.16 OBSERVED REAR EXIT DOOR IN CAFETERIA NOT RODENT PROOF. INSTRUCTED TO PROVIDE AND MAINTAIN IN ORDER TO PREVENT PEST ENTRY.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- 4-501.11 OBSERVED MISSING SPLASH GUARD ON HANDSINK CONNECTED TO 3 COMPARTMENT SINK. INSTRUCTED TO PROVIDE TO PREVENT MISCELLANEOUS FORMS OF CONTAMINATION
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-201.13 OBSERVED BROKEN WALL BASE IN CAFETERIA FACING NORTH BROKEN AND OR MISSING, INSTRUCTED TO REPAIR, REPLACE AND MAINTAIN.
- 36. THERMOMETERS PROVIDED & ACCURATE
- Canvass
5 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED HANDWASHING SINK IN BASEMENT NEAR CAFETERIA @ IMPROPER TEMPERATURES FOR HOT WATER. NOTED HANDSINKS IN BOYS' TOILET @ 67F, HANDSINKS IN GIRLS' TOILET RANGING BETWEEN 64-69F, AND STAFF TOILET ROOM HANDSINK @68.6F. INSTRUCTED TO PROVIDE HOT WATER @ MINIMUM REQUIREMENT OF 100F AND MAINTAIN FOR PROPER HANDWASHING. INSTRUCTED TO PROVIDE. PRIORITY VIOLATION. 7-38-030 (C). NO CITATION ISSUED.
- 36. THERMOMETERS PROVIDED & ACCURATE
- OBSERVED BROKEN THERMOMETER ON MILK COOLER IN SERVING AREA. INSTRUCTED TO REPLACE THERMOMETER.NOTED MILK STORED INSIDE @ 35 DURING THIS TIME.
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OBSERVED REAR EXIT DOOR IN CAFETERIA NOT RODENT PROOF. INSTRUCTED TO PROVIDE AND MAINTAIN IN ORDER TO PREVENT PEST ENTRY.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- OBSERVED MISSING SPLASH GUARD ON HANDSINK CONNECTED TO 3 COMPARTMENT SINK. INSTRUCTED TO PROVIDE TO PREVENT MISCELLANEOUS FORMS OF CONTAMINATION.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED BROKEN WALL BASE IN CAFETERIA FACING NORTH BROKEN AND OR MISSING, INSTRUCTED TO REPAIR, REPLACE AND MAINTAIN.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
4 infractions
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- OBSERVED FACILITY WITHOUT AN ORIGINAL CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE POSTED ONSITE FOR FOOD EMPLOYEES. INFORMED PERSON IN CHARGE CITY OF CHICAGO ORIGINAL FOOD SERVICE CERTIFICATE MUST BE POSTED ALONG WITH THE CERTIFIED MANAGER ON SITE WHEN TIME AND TEMPERATURE CONTROL FOR SAFETY(TCS) FOODS ARE STORED. PRIORITY FOUNDATION VIOLATION #7-38-012. NO CITATION ISSUED.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- NOTED SOME USE OF MILK CRATES FOR ELEVATION AT THE WALK IN FREEZER. INSTRUCTED NOT TO USE MILK CRATES FOR ELEVATION TO PREVENT HIDING PLACES FOR PEST. MUST PROVIDE APPROPRIATE SHELVING FOR STORAGE. ALL FOOD ITEMS MUST ALSO BE STORED 6" AWAY FROM THE WALL
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- OBSERVED NO COVERED RECEPTACLES INSIDE OF WOMENS TOILET ROOM. INSTRUCTED TO PROVIDE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED SOILED MOP HEAD NOT PROPERLY STORED. INSTRUCTED MANAGER TO HANG MOP HEADS TO PREVENT INSECT BREEDING.
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- Canvass
2 infractions
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED THE HANDSINK IN THE WASHROOM OF CLASSROOM #115 WAS LEAKING FROM THE PIPE UNDERNEATH; INSTRUCTED TO REPAIR LEAK FROM PIPE. OBSERVED A SEWER SMELL FROM THE EXPOSED HANDSINK IN CLASSROOM #107; INSTRUCTED TO SERVICE SINK TO ELIMINATE ODOR.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- THE LIGHTS ARE NOT WORKING INSIDE OF THE WALK-IN COOLER AND WALK-IN FREEZER IN THE KITCHEN; MUST PROVIDE ADEQUATE LIGHTING FOR BOTH UNITS.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- Canvass Re-Inspection
4 infractions
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- NO COVERED WASTE RECEPTACLE PROVIDED IN THE EMPLOYEE WASHROOM. MUST PROVIDE AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED DUST BUILD UP INSIDE LIGHT SHIELD COVERS ABOVE PREP TABLES IN KITCHEN FOOD PREPARATION AREA AND EMPLOYEE WASHROOM MUST CLEAN AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED A FEW MISSING LIGHT SHIELDS COVERS IN KITCHEN FOOD PREPARATION AREA. MUST PROVIDE LIGHT SHIELDS COVERS AND MAINTAIN.
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- PREVIOUS PRIORITY FOUNDATION VIOLATIONS NOT CORRECTED FROM INSPECTION REPORT# 2531768 ON 9/22/2021 #55 OBSERVED BROKEN AND MISSING FLOOR TILES IN KITCHEN, IN FRONT OF WALK-IN COOLER AND OVEN. INSTRUCTED TO REPAIR AND MAINTAIN. PRIORITY FOUNDATION VIOLATION 7-42-090. NO CITATION ISSUED
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- Canvass Re-Inspection
4 infractions
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- NO COVERED WASTE RECEPTACLE PROVIDED IN THE EMPLOYEE WASHROOM. MUST PROVIDE AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED DUST BUILD UP INSIDE LIGHT SHIELD COVERS ABOVE PREP TABLES IN KITCHEN FOOD PREPARATION AREA AND EMPLOYEE WASHROOM MUST CLEAN AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED A FEW MISSING LIGHT SHIELDS COVERS IN KITCHEN FOOD PREPARATION AREA. MUST PROVIDE LIGHT SHIELDS COVERS AND MAINTAIN.
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- PREVIOUS PRIORITY FOUNDATION VIOLATIONS NOT CORRECTED FROM INSPECTION REPORT# 2531768 ON 9/22/2021 #55 OBSERVED BROKEN AND MISSING FLOOR TILES IN KITCHEN, IN FRONT OF WALK-IN COOLER AND OVEN. INSTRUCTED TO REPAIR AND MAINTAIN. PRIORITY FOUNDATION VIOLATION 7-42-090. NO CITATION ISSUED
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- Canvass
4 infractions
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- NO COVERED WASTE RECEPTACLE PROVIDED IN THE EMPLOYEE WASHROOM. MUST PROVIDE AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED DUST BUILD UP INSIDE LIGHT SHIELD COVERS ABOVE PREP TABLES IN KITCHEN FOOD PREPARATION AREA AND EMPLOYEE WASHROOM MUST CLEAN AND MAINTAIN.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED A FEW MISSING LIGHT SHIELDS COVERS IN KITCHEN FOOD PREPARATION AREA. MUST PROVIDE LIGHT SHIELDS COVERS AND MAINTAIN.
- 60. PREVIOUS CORE VIOLATION CORRECTED
- PREVIOUS CORE VIOLATIONS NOT CORRECTED FROM 9/22/2020 INSPECTION#2401490. #55 OBSERVED BROKEN AND MISSING FLOOR TILES IN KITCHEN, IN FRONT OF WALK-IN COOLER AND OVEN. INSTRUCTED TO REPAIR AND MAINTAIN. PRIORITY FOUNDATION VIOLATION 7-42-090. NO CITATION ISSUED.
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- Canvass
3 infractions
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- FOUND TORN REFRIGERATION GASKETS ON MULTIPLE REFRIGERATION UNITS IN SERVERY. INSTRUCTED FACILITY TO REPLACE ALL TORN GASKETS AND MAINTAIN.
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- FOUND RUST ON STORAGE RACKS IN WALK IN COOLER, INSTRUCTED TO REMOVE RUST, SO SURFACES IS SMOOTH AND EASILY CLEANABLE. INSTRUCTED TO MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- FOUND BROKEN AND MISSING FLOOR TILES IN KITCHEN, IN FRONT OF WALK IN COOLER AND OVEN. INSTRUCTED TO REPAIR AND MAINTAIN.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- Canvass
0 infractions
- Complaint Re-Inspection
7 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Inspector Comments: MUST REPAIR OR REPLACE WORN DOOR GASKET ON 2- DOOR REACH IN COOLER NEAR OVENS.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- Inspector Comments: MUST CLEAN DEBRIS FROM MILK COOLER ON SERVING LINE,PRE-K ROOM 109 SHELVES ,EXTERIOR OF GARBAGE CANS IN LUNCHROOM.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- Inspector Comments: MUST REPAIR OR REPLACE DAMAGED FLOOR TILES AND FLOORING IN PREP AREA,DRY FOOD STORAGE,LUNCHROOM.MUST CLEAN FLOOR IN WALK IN COOLER AND FREEZER.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- Inspector Comments: MUST REPAIR OR REPLACE DAMAGED WALLS AND CEILING IN PREP AREA BEHIND OVEN AND ABOVE 3- COMP SINK AND THROUGHTOUT PREP AREA AND PRE- K ROOM 109.MUST CLEAN LIGHT SHIELDS ON SERVING LINE.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- Inspector Comments: MUST REPAIR OR REPLACE BURNTOUT LIGHT IN WALK IN COOLER AND FREEZER,MISSING AND CRACKED LIGHT SHIELD IN PREP AREA,SERVINGLINE.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Inspector Comments: MUST REPAIR OR REPLACE LEAKY TOILET IN KITCHEN STAFF TOILET ROOM,LOW WATER PRESSURE AT 2ND FL.(G)NORTH.MUST ADJUST FAUCET HANDLES TO STAY ON LONGER AT HAND SINKS IN 2ND & 3RD FL (G) MIDDLE,PRE-K ROOM 107.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- Inspector Comments: MUST ELEVATE,REMOVE AND ORGANIZE CLUTTER IN PRE-K ROOM 109 CLOSET AND BASEMENT MAINTENANCE CLOSET.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Complaint
9 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- OBSERVED EVIDENCE OF APPX.60 OR MORE RODENT DROPPINGS IN DRY FOOD STORAGE AREA UNDER SHELVING UNITS IN REAR CORNER,FOOD MANAGERS OFFICE BEHIND FILE CABINET,BASEMENT MAINTENANCE CLOSET ON A CONCRETE BLOCK AND 5- SMALL FLIES IN GARBAGE CAN IN SAME AREA,PRE-K ROOM 107 ON TOY SHELVES,CUBBIES AND OPEN SHELF FILE CABINET,PRE-K ROOM 115 IN LOWER CABINET AT 1- COMP SINK,CUBBIES,TOY SHELVES AND ON FLOOR NEAR 1- COMP SINK.ALSO APPX"1/2-3/4" GAP AT DOOR #3,7 & 8.MUST REMOVE DROPPINGS,CLEAN AND SANITIZE AREAS.RODENT PROOF DOORS.RECOMMENDED TO HAVE A PEST CONTROL OPERATOR TO SERVICE PREMISES ON OR AFTER 1/30/18.(NO CITATION ISSUED)
- 19. OUTSIDE GARBAGE WASTE GREASE AND STORAGE AREA; CLEAN, RODENT PROOF, ALL CONTAINERS COVERED
- OBSERVED OUTSIDE GARABAGE DUMPSTER LID FRAME DAMAGED AND MISSING A LID ON 1 OF 2 DUMPSTERS.MUST REPAIR AND OR REPLACE TO BE TIGHT FITTING.(NO CITATION ISSUED)
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- MUST REPAIR OR REPLACE WORN DOOR GASKET ON 2- DOOR REACH IN COOLER NEAR OVENS.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- MUST CLEAN DEBRIS FROM MILK COOLER ON SERVING LINE,PRE-K ROOM 109 SHELVES ,EXTERIOR OF GARBAGE CANS IN LUNCHROOM.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- MUST REPAIR OR REPLACE DAMAGED FLOOR TILES AND FLOORING IN PREP AREA,DRY FOOD STORAGE,LUNCHROOM.MUST CLEAN FLOOR IN WALK IN COOLER AND FREEZER.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- MUST REPAIR OR REPLACE DAMAGED WALLS AND CEILING IN PREP AREA BEHIND OVEN AND ABOVE 3- COMP SINK AND THROUGHTOUT PREP AREA AND PRE- K ROOM 109.MUST CLEAN LIGHT SHIELDS ON SERVING LINE.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- MUST REPAIR OR REPLACE BURNTOUT LIGHT IN WALK IN COOLER AND FREEZER,MISSING AND CRACKED LIGHT SHIELD IN PREP AREA,SERVINGLINE.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- MUST REPAIR OR REPLACE LEAKY TOILET IN KITCHEN STAFF TOILET ROOM,LOW WATER PRESSURE AT 2ND FL.(G)NORTH.MUST ADJUST FAUCET HANDLES TO STAY ON LONGER AT HAND SINKS IN 2ND & 3RD FL (G) MIDDLE,PRE-K ROOM 107.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- MUST ELEVATE,REMOVE AND ORGANIZE CLUTTER IN PRE-K ROOM 109 CLOSET AND BASEMENT MAINTENANCE CLOSET.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass Re-Inspection
2 infractions
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOORS THROUGHOUT IN NEED OF DETAIL CLEANING TO REMOVE ALL BUILD UP. MUST CLEAN UNDER AND AROUND ALL EQUIPMENT. FLOOR TILES IN STORAGE ROOM AND OFFICE IN POOR REPAIR. REPLACE CORRECT AND MAINTAIN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- WALLS AND CEILINGS IN PREP AREA HAVE LARGE AMOUNTS OF PEELING PAINT. INSTRUCTED TO REMOVE AND MAINTAIN SMOOTH AND EASILY CLEANABLE. CORRECT AND MAINTAIN.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- Canvass
4 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- FOUND EVIDENCE OF MICE ACTIVITY IN CORNER BY REACH IN COOLER APPROXIMATELY 20 DROPPINGS, FOUND ACTIVITY IN CORNER OF EMPLOYEE LOCKER ROOM 10 DROPPINGS, FOUND 3 DROPPINGS BEHIND STORAGE CABINET IN OFFICE. INSTRUCTED TO CLEAN AND SANITIZE THE AREAS. CONTACT PEST CONTROL FOR SERVICE. SERIOUS VIOLATION 7-38-020
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- FLOORS THROUGHOUT IN NEED OF DETAIL CLEANING TO REMOVE ALL BUILD UP. MUST CLEAN UNDER AND AROUND ALL EQUIPMENT. FLOOR TILES IN STORAGE ROOM AND OFFICE IN POOR REPAIR. REPLACE CORRECT AND MAINTAIN.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- WALLS AND CEILINGS IN PREP AREA HAVE LARGE AMOUNTS OF PEELING PAINT. INSTRUCTED TO REMOVE AND MAINTAIN SMOOTH AND EASILY CLEANABLE. CORRECT AND MAINTAIN.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- LIGHT SHEILDS IN STORAE ROOM IN NEED OF REPLACING. 2 SHEILDS BROKEN CORRECT AND MAINTAIN.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass
5 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- OBSERVED 20 MICE DROPPINGS ON FLOOR ALONG WALL BASE AND CORNERS BEHIND A UPRIGHT CABINET IN THE OFFICE AREA NEAR KITCHEN,INSTRUCTED TO CLEAN AND SANITIZED AFFECTED AREA,SERIOUS VIOLATION 7-38-020
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- MUST REPLACE 1 BROKEN SOAP DEPENSER INSIDE THE BOYS WASHROOM ON THE 2ND FLOOR SOUTH LOCATION,INSTRUCTED TO PROVIDE
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- MUST CLEAN FLOORS IN THE OFFICE AREA AND INSIDE ALL JANITORS CLOSETS ON 1ST AND 2ND FLOOR,ALONG WALL BASE AND CORNERS
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- MUST REMOVE PEELING PAINT FROM CEILING IN THE DINNING AREA,INSTRUCTED TO REMOVE PEELING PAINT AND CLEAN THE LIGHT SHIELD COVERS IN THE KITCHEN AREA OF DUST BUILD-UP,INSTRUCTED TO CLEAN AND MAINTAIN AREA
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- MUST REPLACE CRACKED LIGHT SHIELD COVER IN KITCHEN AREA,INSTRUCTED TO REPLACE CRACKED LIGHT SHIELD COVER
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass Re-Inspection
0 infractions
- Canvass
2 infractions
- 14. PREVIOUS SERIOUS VIOLATION CORRECTED, 7-42-090
- PREVIOUS SERIOUS VIOLATION NOT CORRECTED FROM FEB. 17, 2015 REPORT# 1520216, AS DESCRIBED: CONVENTIONAL OVENS (11 KW OR 11,000 WATTS) NOT LOCATED UNDER EXHAUST HOOD ON SITE. INSTD. TO HAVE EXHAUST HOODS IMMEDIATELY ABOVE OVENS. OVENS HAVE BEEN TAGGED. CRITICAL VIOLATION 7-42-090.
- 26. ADEQUATE NUMBER, CONVENIENT, ACCESSIBLE, PROPERLY DESIGNED AND INSTALLED
- OBSERVED HAND WASHING FACILITY IN THE GIRLS BATHROOM (BASEMENT) NOT FUNCTIONING WITHOUT ANY WATER COMING THRU. ENGINEER WAS ABLE TO RESTORE WATER TO THE SINK DURING THE INSPECTION. INSTRUCTED TO MAINTAIN. SERIOUS VIOLATION 7-38-030.
- 14. PREVIOUS SERIOUS VIOLATION CORRECTED, 7-42-090
- Canvass Re-Inspection
4 infractions
- 14. PREVIOUS SERIOUS VIOLATION CORRECTED, 7-42-090
- PREVIOUS SERIOUS VIOLATION NOT CORRECTED FROM FEB. 17, 2015 AS DESCRIBED: OVENS NOT LOCATED UNDER EXHAUST HOOD ON SITE. INSTD. TO HAVE EXHAUST HOODS IMMEDIATELY ABOVE OVENS. CRITICAL VIOLATION 7-42-090.
- 29. PREVIOUS MINOR VIOLATION(S) CORRECTED 7-42-090
- BUMPED UP TO A CRITICAL.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- CEILING IN THE BOYS WASHROOM ON THE SECOND FLOOR IS IN POOR REPAIR DUE TO URINALS ABOVE ON THE THIRD FLOOR IN POOR REPAIR; REPAIR CEILING.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- THE FIRST THREE URINALS ON THE THIRD FLOOR IN THE BOYS WASHROOM ARE OUT OF ORDER; MUST REPAIR. PARTS ORDERED AND ENGINEER STATES THAT THEY WILL BE REPAIRED BY THE END OF THE WEEK.
- 14. PREVIOUS SERIOUS VIOLATION CORRECTED, 7-42-090
- Canvass
4 infractions
- 29. PREVIOUS MINOR VIOLATION(S) CORRECTED 7-42-090
- OVENS NOT LOCATED UNDER EXHAUST HOOD ON SITE. INSTD TO HAVE EXHAUST HOODS IMMEDIATELY ABOVE OVENS. (ORIGINAL VIOLATION WRITTEN ON MAY 16, 2014). SERIOUS VIOLATION 7-42-090.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- CEILING IN THE BOYS WASHROOM ON THE SECOND FLOOR IS IN POOR REPAIR DUE TO URINALS ABOVE ON THE THIRD FLOOR IN POOR REPAIR; REPAIR CEILING.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- BUMPED UP TO A SERIOUS.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- THE FIRST THREE URINALS ON THE THIRD FLOOR IN THE BOYS WASHROOM ARE OUT OF ORDER; MUST REPAIR. PARTS ORDERED AND ENGINEER STATES THAT THEY WILL BE REPAIRED BY THE END OF THE WEEK.
- 29. PREVIOUS MINOR VIOLATION(S) CORRECTED 7-42-090
- Canvass
8 infractions
- 12. HAND WASHING FACILITIES: WITH SOAP AND SANITARY HAND DRYING DEVICES, CONVENIENT AND ACCESSIBLE TO FOOD PREP AREA
- NO SANITARY HAND DRYING DEVICES AT EXPOSED HANDSINKS IN PREP AREAS NOR IN LUNCHROOM STAFF TOILET ROOM. MGR STATES THEY HAVE NOT BEEN PROVIDED SANITARY HAND DRYING DEVICES FOR ABOUT A MONTH. INSTD TO HAVE AT SINKS AT ALL TIMES. CITATION ISSUED 7-38-030 CRITICAL
- 21. * CERTIFIED FOOD MANAGER ON SITE WHEN POTENTIALLY HAZARDOUS FOODS ARE PREPARED AND SERVED
- NO CITY OF CHICAGO CERTIFIED MANAGER ON DUTY WHILE HANDLING POTENTIALLY HAZARDOUS FOODS. (MILK, BREAKFAST BURRITOS, ETC). CITATION ISSUED 7-38-012 SERIOUS.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- SHELF LINING AT BOTTOM OF STORAGE SHELVES AT SERVING LINE. INSTD TO REMOVE SAME SO AS TO BE SMOOTH, EVEN, EASILY CLEANABLE SURFACE.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- CRACKED/MISSING FLOOR TILES IN MAIN PREP AREA. INSTD TO REPAIR FLOOR SO AS TO BE A SMOOTH, EVEN EASILY CLEANABLE SURFACE.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- DOORWAY LEADING TO MAIN PREP AREA IN POOR REPAIR, EXPOSED, CRUMBLING DRY WALL. INSTD TO REPAIR SAME SO AS TO BE SMOOTH, EVEN, EASILY CLEANABLE SURFACE.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- CRACKED LIGHTSHIELDS ABOVE SERVING LINE. REPLACE SAME.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- NO SPLASHGUARD AT EXPOSED HANDSINK THAT IS LOCATED DIRECTLY NEXT TO 3-COMPARTMENT SINK DRAINBOARD. PROVIDE SAME. OVENS NOT LOCATED UNDER EXHAUST HOOD ON SITE. INSTD TO HAVE EXHAUST HOODS IMMEDIATELY ABOVE OVENS. SOME STUDENT TOILET ROOMS NOT IDENTIFIED. INSTD TO IDENTIFY TO GIRLS AND BOYS TOILET ROOMS FOR ALL TOILET ROOMS.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- REMOVE NON-USED/NON-WORKING MILK COOLER PREMISES OR REPAIR.
- 12. HAND WASHING FACILITIES: WITH SOAP AND SANITARY HAND DRYING DEVICES, CONVENIENT AND ACCESSIBLE TO FOOD PREP AREA
- Canvass Re-Inspection
2 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- THE PIPE IN THE 2ND FLOOR BOYS SOUTH BATHROOM HAS EXPOSED FIBERGLASS, SEAL UP EXPOSED INSULATION.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- THE 3RD FLOOR HALLWAY CEILINGS ARE WATER DAMAGED, REPAIR SAID CEILINGS. THE 2ND GIRLS NORTH WASHROOM AND 3RD FLOOR BOYS WASHROOM HAVE HOLES IN THE WALLS STUFFED WITH SNACK WRAPPERS. REPAIR THE WALLS AND CEILINGS SO THEY ARE SMOOTH AND SANITARY.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
7 infractions
- 2. FACILITIES TO MAINTAIN PROPER TEMPERATURE
- THE TWO DOOR NORLAKE MILK COOLER HOLDS MILK AT 45.5 f INTERNAL TEMPERATURE, COOLER TAGGED HELD FOR INSPECTION, E-MAIL A TAG REMOVAL REQUEST TO [email protected] OR FAX TO 312-746-4240 WHEN READY TO REMOVE OR REPAIR COOLER.
- 3. POTENTIALLY HAZARDOUS FOOD MEETS TEMPERATURE REQUIREMENT DURING STORAGE, PREPARATION DISPLAY AND SERVICE
- 29 HALF PINTS OF MILK WERE FOUND AT 45.5 f. $ 7.25 WORTH OF MILK WAS DISCARDED AT THIS TIME.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- ONE DEAD MOUSE AND OVER THIRTY MOUSE DROPPINGS WERE FOUND IN THE ROOM UNDER THE STAIRS NEXT TO THE CAFETERIA, ACTIVE RODENT HOLES WERE FOUND ON BOTH SIDES OF THE WALK IN COOLER AND NEXT TO THE STAIRS IN THE EAST END OF THE LUNCHROOM. OVER TWENTY MOUSE DROPPINGS WERE FOUND IN ROOM 115 AND THE ADJACENT WASHROOM AND STORAGE CLOSET. AN ACTIVE RODENT HOLE WAS FOUND IN THE LIBRARY NEXT TO A CLOSET DOOR AND THE DOOR SWEEP AT THE TOP OF THE EAST CAFETERIA STAIRS IS GNAWED THROUGH. REMOVE ALL EVIDENCE OF PEST ACTIVITY; CLEAN AND SEAL UP ALL POSSIBLE AREAS OF RODENT HARBORAGE AND SANITIZE ALL AFFECTED AREAS. REVIEW TREATMENT AND REPORTS WITH YOUR PEST CONTROL COMPANY.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- THE PIPE IN THE 2ND FLOOR BOYS SOUTH BATHROOM HAS EXPOSED FIBERGLASS, SEAL UP EXPOSED INSULATION.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- THE 3RD FLOOR HALLWAY CEILINGS ARE WATER DAMAGED, REPAIR SAID CEILINGS. THE WALLS AROUND THE CAFETERIA PERIMETER AND KITCHEN HAVE GAPS AND OPENINGS, THE 2ND GIRLS NORTH WASHROOM AND 3RD FLOOR BOYS WASHROOM HAVE HOLES IN THE WALLS STUFFED WITH SNACK WRAPPERS. REPAIR THE WALLS AND CEILINGS SO THEY ARE SMOOTH AND SANITARY.
- 40. REFRIGERATION AND METAL STEM THERMOMETERS PROVIDED AND CONSPICUOUS
- THE METAL STEM THERMOMETER USED IN THE KITCHEN IS 32 DEGREES OFF, AN ICE SLUSH WAS MADE AND I CALIBRATED THE THERMOMETER TO 32 f AT THIS TIME.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- A BUCKET OF STAGNANT MOP WATER WAS FOUND IN THE MOP CLOSET ACROSS FROM ROOM 115, BUCKET DRAINED AT THIS TIME. THE SOAP DISPENSER HAS COME OF OF THE KITCHEN BATHROOM WALL, REPLACE THE DISPENSER.
- 2. FACILITIES TO MAINTAIN PROPER TEMPERATURE
- Canvass
2 infractions
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- MUST SEAL HOLE AROUND PIPE BEHIND TOILET AND UNDERNEATH HANDSINK IN WASHROOM OF ROOM 109. PLASTER WALL INSIDE OF ENTRANCE TO KITCHEN WHERE NEEDED.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- REPAIR ONE TOILET ON THIRD FLOOR IN BOYS WASHROOM.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- Canvass Re-Inspection
7 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Inspector Comments: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.MUST SEAL OR REPLACE MISSING LOCK ON BOILER ROOM DOOR,MISSING STALL DOOR IN GIRLS 2ND FL. (S),MISSING HANDLE ON CABINET IN PRE-K 115.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- Inspector Comments: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN REFRIGERATOR IN STAFF BREAK ROOM.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- Inspector Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPLACE DAMAGED & MISSING FLOOR TILES IN FOOD MANAGERS OFFICE,KITCHEN STAFF TOILET ROOM,STAFF LOUNGE,PRE-K ROOM 111& 115.MUST CLEAN FLOOR IN MOP SINK CLOSETS.MUST REPAIR BROKEN CONCRETE IN ELECTRICAL VAULT.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- Inspector Comments: The walls and ceilings shall be in good repair and easily cleaned.MUST REPAIR ,REPLACE OR SEAL LOOSE, MISSING & DAMAGED WALL BASES & WALLS IN FOOD MANAGERS OFFICE,LUNCH ROOM,JANITORS BREAK ROOM,MOP SINK CLOSETS,UNDER STAIR CASE IN STORAGE ROOM.MUST SCRAPE & PAINT PEELING PAINT ON WALLS IN SERVING LINE,LUNCH ROOM,PRE-K 109 TOILET ROOM,3RD FLOOR MEN'S & WOMEN'S TOILET ROOMS.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- Inspector Comments: Shielding to protect against broken glass falling into food shall be provided for all artificial lighting sources in preparation, service, and display facilities.MUST REPLACE CRACKED & DAMAGED LIGHT SHIELDS IN PREP AREA,SERVING LINE.BURNT OUT LIGHT BULB IN MOP SINK CLOSET,WALK IN COOLER & FREEZER.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Inspector Comments: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.MUST REMOVE PORTABLE HAND SINK IN PRE-K ROOM 111 AND CONNECT SINK TO CITY PLUMBING.MUST REPAIR LOW HOT WATER PRESSURE AT HAND SINK IN 3RD FL WOMEN'S TOILET ROOM.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- Inspector Comments: All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE & ORGANIZE MASSIVE AMOUNT OF ARTICLES ON FLOOR & ALONG WALLS IN BOILER ROOM.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass
8 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- All necessary control measures shall be used to effectively minimize or eliminate the presence of rodents, roaches, and other vermin and insects on the premises of all food establishments, in food-transporting vehicles, and in vending machines.OBSERVED EVIDENCE OF MORE THAN 500 RODENT DROPPINGS SCATTERED IN VARIOUS AREAS ON FLOORS,WALL BASES,CABINETS IN PREP AREA BEHIND OVENS,STOVE,REACH IN COOLERS,DRY FOOD STORAGE AREA,FOOD MANAGERS OFFICE,STAFF LUNCH ROOM,#2 FAN ROOM,ELEVATOR LIFT ROOM,JANITORS BREAK ROOM,BOILER ROOM,ELECTRICAL ROOM.ALSO A DEAD RAT & MOUSE,RODENTICIDE ON FLOORS & END WALLBASES IN FOOD MANAGERS OFFICE ,JANITORS BREAK ROOM.ALSO BOILER ROOM DOOR & KITCHEN DOOR NOT TIGHT FITTING.MUST REMOVE RODENT DROPPINGS,DEAD RAT & MOUSE,RODENT PROOF DOORS.PEST CONTROL IS ON SITE AT THIS TIME OF INSPECTION.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.MUST SEAL OR REPLACE MISSING LOCK ON BOILER ROOM DOOR,MISSING STALL DOOR IN GIRLS 2ND FL. (S),MISSING HANDLE ON CABINET IN PRE-K 115.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN REFRIGERATOR IN STAFF BREAK ROOM.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPLACE DAMAGED & MISSING FLOOR TILES IN FOOD MANAGERS OFFICE,KITCHEN STAFF TOILET ROOM,STAFF LOUNGE,PRE-K ROOM 111& 115.MUST CLEAN FLOOR IN MOP SINK CLOSETS.MUST REPAIR BROKEN CONCRETE IN ELECTRICAL VAULT.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- The walls and ceilings shall be in good repair and easily cleaned.MUST REPAIR ,REPLACE OR SEAL LOOSE, MISSING & DAMAGED WALL BASES & WALLS IN FOOD MANAGERS OFFICE,LUNCH ROOM,JANITORS BREAK ROOM,MOP SINK CLOSETS,UNDER STAIR CASE IN STORAGE ROOM.MUST SCRAPE & PAINT PEELING PAINT ON WALLS IN SERVING LINE,LUNCH ROOM,PRE-K 109 TOILET ROOM,3RD FLOOR MEN'S & WOMEN'S TOILET ROOMS.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- Shielding to protect against broken glass falling into food shall be provided for all artificial lighting sources in preparation, service, and display facilities.MUST REPLACE CRACKED & DAMAGED LIGHT SHIELDS IN PREP AREA,SERVING LINE.BURNT OUT LIGHT BULB IN MOP SINK CLOSET,WALK IN COOLER & FREEZER.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.MUST REMOVE PORTABLE HAND SINK IN PRE-K ROOM 111 AND CONNECT SINK TO CITY PLUMBING.MUST REPAIR LOW HOT WATER PRESSURE AT HAND SINK IN 3RD FL WOMEN'S TOILET ROOM.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE & ORGANIZE MASSIVE AMOUNT OF ARTICLES ON FLOOR & ALONG WALLS IN BOILER ROOM.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- Canvass
6 infractions
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- All utensils shall be thoroughly cleaned and sanitized after each usage. MUST CLEAN-SANITIZE; COOLERS AND MICROWAVE OVENS IN TEACHER'S LOUNGE.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST REPLACE MISSING AND BROKEN FLOOR TILES IN KITCHEN'S STAFF WASHROOM, AND CLEAN FLOORS THRU-OUT INSIDE MOP CLOSETS AND STORAGE ROOMS.
- 35. WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
- The walls and ceilings shall be in good repair and easily cleaned. MUST REPAIR WALLS IN LUNCHROOMS, SOME MOP CLOSETS AND SOME WASHROOMS. MUST SEAL OPENINGS WHERE NEEDED TO PREVENT PEST ENTRY SAME AREAS AND REMOVE PEELING PAINT, SAME AREAS.
- 36. LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
- MUST CLEAN LIGHT SHIELDS THRU-OUT LUNCHROOMS.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR FAUCETS AT HAND WASHING BOWLS INSIDE TEACHER'S 2ND FLOOR WASHROOM, NORTH AREA, AND JANITOR'S LOUNGE BASEMENT.
- 41. PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
- EXCESSIVE CLUTTER INSIDE PRE-K CLASSROOMS, MUST REMOVE UNNECESSARY ARTICLES, CLEAN AND ORGANIZE TO PREVENT PEST HARBORAGE. ARTICLES MUST BE STORED OFF FLOORS, AWAY FROM WALLS.
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS