11710 100 Avenue NW - Swimming Pool

11710 100 Avenue NW Edmonton AB T5K 2G3 · Aquatic Facility

Inspection summary

11710 100 Avenue NW - Swimming Pool has been inspected 9 times by Alberta Health Services (Environmental Public Health) since February 8, 2024. The most recent inspection, on September 21, 2026, recorded 1 infraction.

1 of 9 inspections on record found no infractions at all. In the past 12 months there were 6 inspections with 10 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 12 times across 8 separate inspections, most recently on September 21, 2026. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

9 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  2. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 9/9/2026 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 9/9/2026 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  3. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 10 June 2026 was unsatisfactory: HPC 1330 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  5. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on Apr. 8, 2026, was unsatisfactory: HPC >100 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  7. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Check controller as the actual is less than the set point. Ensure the ORP is checked to ensure it is consistent with values of the free chlorine in the pool. ORP was <700mV even though the free chlorine was >6 ppm.
  8. Risk Management Inspection

    0 infractions

  9. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 7 Feb 2024 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.