2914 109 Street NW - Whirlpool

2914 109 Street NW Edmonton AB T6J 7E8 · Aquatic Facility

11 inspections

  1. Risk Management Inspection

    0 infractions

  2. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 26EN-170E00106 submitted on June 19, 2026, was unsatisfactory: Total coliforms were present.
  3. Demand Inspection

    0 infractions

  4. Risk Management Inspection

    0 infractions

  5. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Rate of filtration for the filtration system was 15.92 gpm/sq ft based on a filtration area of 3.14 sq ft and flow rate 50 gpm.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 24EN-180E00188 submitted on June 28, 2024, was unsatisfactory: Pseudomonas aeruginosa isolated.
  8. Risk Management Inspection

    0 infractions

  9. Risk Management Inspection

    1 infraction

    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • Vacless unit installed on the jet pump was not operating properly: worked properly when closing the valve(s) but could not be easily reset. The manufacturer was contacted by the service provider for the follow-up.
  10. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No records for testing the secondary anti-entrapment device were available.
  11. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity was 18 ppm. Ensure that total alkalinity is maintained between 60 and 180 ppm.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • No records for testing the secondary anti-entrapment device were available.