Skip to content
Loading map…

9923 103 Street NW - Whirlpool

9923 103 Street NW Edmonton AB T5K 2J3 · Aquatic Facility

Inspection summary

9923 103 Street NW - Whirlpool has been inspected 3 times by Alberta Health Services (Environmental Public Health) since October 18, 2024. The most recent inspection, on February 10, 2026, found no infractions.

2 of 3 inspections on record found no infractions at all. In the past 12 months there were 2 inspections with 2 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded once on November 28, 2025. For example: Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?

  • Food safety training and certificationLower risk

    Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.

    Recorded once on November 28, 2025. For example: Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

3 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    2 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • The main drain installed is expired and requires replacing. Pool operator confirmed that site maintenance person has procured a replacement to be installed while the whirlpool is drained. Due to changes in the certification for the new drain cover it is not rated for the total flow of both the circulation and jet pump. The jet pump must remain off until further assessment by a pool professional can be done to determine options for compliance. Once the new cover is installed please forward a photo and notify the undersigned.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Anti-entrapment compliance plan must be updated to reflect the operational decision made by the facility to continue compliance with the anti-entrapment requirements. Please note the date of installation for the suction outlet as it will expire 5 years from that date.
  3. Monitoring Inspection

    0 infractions

Nearby inspected facilities