Arris East - Swimming Pool
505 4 Street SE Calgary AB T2G 1V6 · Aquatic Facility
5 inspections
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH from the manual test was 7.0 while the automated reading was 7.3. Please calibrate the probes to ensure that the automated reading is consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was 130 GPM. The filtration rate was calculated to be 18.41 GPM/squared feet. Please ensure that the flow rate is within the required range (87.60-105.90 GPM) and that the filtration rate is below 15 GPM/squared feet.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (26ES-139E00011) collected on May 19th, 2026, came back unsatisfactory as the HPC level was elevated to 440CFU/mL. The maximum acceptable concentration is 100CFU/mL. Please resample the swimming pool as soon as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH from the manual test was 7.0 while the automated reading was 7.3. Please calibrate the probes to ensure that the automated reading is consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was 130 GPM. The filtration rate was calculated to be 18.41 GPM/squared feet. Please ensure that the flow rate is within the required range (87.60-105.90 GPM) and that the filtration rate is below 15 GPM/squared feet.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH from the manual test was 7.0 while the automated reading was 7.3. Please calibrate the probes to ensure that the automated reading is consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was 130 GPM. The filtration rate was calculated to be 18.41 GPM/squared feet. Please ensure that the flow rate is within the required range (87.60-105.90 GPM) and that the filtration rate is below 15 GPM/squared feet.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on February 18th, 2025, came back inconclusive as the HPC test results could not be determined. Please re-sample the swimming pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH from the manual test was 7.0 while the automated reading was 7.3. Please calibrate the probes to ensure that the automated reading is consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was 130 GPM. The filtration rate was calculated to be 18.41 GPM/squared feet. Please ensure that the flow rate is within the required range (87.60-105.90 GPM) and that the filtration rate is below 15 GPM/squared feet.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Initial Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The pH from the manual test was 7.0 while the automated reading was 7.3. Please calibrate the probes to ensure that the automated reading is consistent with the manual readings.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was 130 GPM. The filtration rate was calculated to be 18.41 GPM/squared feet. Please ensure that the flow rate is within the required range (87.60-105.90 GPM) and that the filtration rate is below 15 GPM/squared feet.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?