Best Canadian Motor Inns - Whirlpool

9810 98 Street Peace River AB T8S 1J3 · Aquatic Facility

5 inspections

  1. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample(s) (25-03-2026) result(s) indicated the presence of Pseudomonas aeruginosa.Ensure hot tub remains closed until satisfactory water results are received.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample(s) (25-03-2026) result(s) indicates HPC > 57000 CFU / mL.Ensure hot tub remains closed until satisfactory results are received.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • NON-COMPLINACE FROM LAST ONSITE INSPECTION:Manual TestFree Chlorine 1.4 ppm January 31, 2025 - Chlorine still too lowpH 7.5Automated meter ORP 782 pH 8.09January 31, 2025 -ORP 612 pH 7.5
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • NON-COMPLINACE FROM LAST ONSITE INSPECTION:The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
  2. Risk Management Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Last sample result indicated the presence of Pseudomonas aeruginosa.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Last sample result indicates HPC > 57000 CFU / mL.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • NON-COMPLINACE FROM LAST ONSITE INSPECTION:Manual TestFree Chlorine 1.4 ppm January 31, 2025 - Chlorine still too lowpH 7.5Automated meter ORP 782 pH 8.09January 31, 2025 -ORP 612 pH 7.5
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • NON-COMPLINACE FROM LAST ONSITE INSPECTION:The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
  3. Monitoring Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Last sample result indicated the presence of Pseudomonas aeruginosa.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Manual TestFree Chlorine 1.4 ppm January 31, 2025 - Chlorine still too lowpH 7.5Automated meter ORP 782 pH 8.09January 31, 2025 -ORP 612 pH 7.5
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
  4. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Manual TestFree Chlorine 1.4 ppmpH 7.5Automated meter ORP 782pH 8.09
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity 50 mg/l
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Some test reagents are expired.Have not been recording results from the automated system.
  5. Initial Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated controller results are not consistent with the manual test results. Automated controller must be fixed.