Best Canadian Motor Inns - Whirlpool
9810 98 Street Peace River AB T8S 1J3 · Aquatic Facility
5 inspections
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample(s) (25-03-2026) result(s) indicated the presence of Pseudomonas aeruginosa.Ensure hot tub remains closed until satisfactory water results are received.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample(s) (25-03-2026) result(s) indicates HPC > 57000 CFU / mL.Ensure hot tub remains closed until satisfactory results are received.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- NON-COMPLINACE FROM LAST ONSITE INSPECTION:Manual TestFree Chlorine 1.4 ppm January 31, 2025 - Chlorine still too lowpH 7.5Automated meter ORP 782 pH 8.09January 31, 2025 -ORP 612 pH 7.5
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- NON-COMPLINACE FROM LAST ONSITE INSPECTION:The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Last sample result indicated the presence of Pseudomonas aeruginosa.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Last sample result indicates HPC > 57000 CFU / mL.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- NON-COMPLINACE FROM LAST ONSITE INSPECTION:Manual TestFree Chlorine 1.4 ppm January 31, 2025 - Chlorine still too lowpH 7.5Automated meter ORP 782 pH 8.09January 31, 2025 -ORP 612 pH 7.5
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- NON-COMPLINACE FROM LAST ONSITE INSPECTION:The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Last sample result indicated the presence of Pseudomonas aeruginosa.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Manual TestFree Chlorine 1.4 ppm January 31, 2025 - Chlorine still too lowpH 7.5Automated meter ORP 782 pH 8.09January 31, 2025 -ORP 612 pH 7.5
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Manual TestFree Chlorine 1.4 ppmpH 7.5Automated meter ORP 782pH 8.09
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total Alkalinity 50 mg/l
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Some test reagents are expired.Have not been recording results from the automated system.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Initial Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automated controller results are not consistent with the manual test results. Automated controller must be fixed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?